INSTALLATION MANUAL
Z-D-IN
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

DOCUMENTATION Z-D-IN

SENECA s.r.l.; Via Austria, 26 ­ 35127 ­ PADOVA ­ ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287

CONTACT INFORMATION

Technical support

support@seneca.it

Product information

sales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

MI00205-7-EN

INSTALLATION MANUAL

1/4

MODULE LAYOUT
17.5 mm

102.5 mm

111 mm

Dimensions LxHxD 17.5 x 102.5 x 111 mm; Weight: 110 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL

LED

STATUS

LED meaning

PWR Green FAIL yellow FAIL yellow
RX Red RX Red TX Red

ON ON Flashing ON Flashing Flashing

The device is powered correctly Anomaly or fault Wrong setup Connection check
Receipt of packet completed Transmission of packet completed

TECHNICAL SPECIFICATIONS

CERTIFICATIONS

https://www.seneca.it/products/z-d-in/doc/CE_declaration

INSULATION

POWER SUPPLY USE
ENVIRONMENTAL CONDITIONS
ASSEMBLY CONNECTIONS

Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac; 50 ÷ 60Hz Absorption: Typical: 1.5W @ 24Vdc, Max: 2.5W

Use in environments with pollution degree 2. The power supply unit must be class 2.

Temperature:

-10÷ + 65°C

Humidity:

30%÷ 90% at 40°C non condensing.

Altitude:

Up to 2,000 m above sea level

Storage temperature: -20÷ + 85°C

Degree of protection: IP20.

IEC EN60715, 35mm DIN rail in vertical position.

3-way removable screw terminals, 5mm pitch, 2.5mm2 section Rear connector IDC10 for DIN bar 46277

MI00205-7-EN

INSTALLATION MANUAL

2/4

Type of supported inputs: Number of channels: Totalizer maximum frequency
UL (status OFF)
UH (status ON) Absorbed current Protection

INPUTS
Reed, Contatto, proximity PNP, NPN (with external resistance)
5 (4+ 1) self-powered at 16Vdc 100 Hz for channels from 1 to 5 10 kHz only for input 5 (after setting) 0 ÷ 10 Vdc, I < 2mA 12 ÷ 30 Vdc; I > 3mA 3mA (for each active input) By means of transient TVS suppressors of 600 W/ms.

CONFIGURATION OF FACTORY SETTINGS

All DIP-switches in
Communication parameters of ModBUS protocol: Input status inversion: Digital filter Totalizers Channel 5 at 10 KHz ModBUS latency time

OFF
38400 8, N, 1 Address 1 DISABLED 3ms Counting to increment Disabled 5ms

ModBUS CONNECTION RULES

1) Install the modules in the DIN rail (120 max) 2) Connect the remote modules using cables of an appropriate length. The following table shows cable length data: - Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect the two farthest modules (see Diagram 1). - Derivation length: maximum length of a derivation 2 m (see Diagram 1).

Bus length 1200 m

Derivation length
2 m

Diagram 1
Module 1

Module 4 Module 3
Ld

Module 2

Module 5

Bus length

Ld= derivation length

For maximum performance, it is recommended to use special shielded cables, such as BELDEN 9841.
IDC10 CONNECTOR
Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DINAL2-17.5 accessory.

RS485 GND RS485 A
RS485 B

Power Supply AC / + Power Supply AC / -
1 IDC 10

Rear Connector (IDC 10) The meaning of the various pins on the IDC10 connector is shown in the figure if you wish to supply signals directly via it.

MI00205-7-EN

INSTALLATION MANUAL

3/4

SETTING THE DIP-SWITCHES

The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate The following table shows the values of the Baud Rate and the Address according to the setting of the DIP-switches:

DIP-Switch status

SW1 POSITION 1 2 3 4 5 6 7 8

BAUD RATE

SW1 POSITION 3 4 5 6 7 8

ADDRESS

POSITION 10

TERMINATOR

9600

#1

Disabled

19200

#2

Enabled

38400

#...

57600

#63

From EEPROM

From EEPROM

Note: When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM). Note 2: The RS485 line must be terminated only at the ends of the communication line.

The settings of the dip-switches must be compatible with the settings on the registers. The description of the registers is available in the USER MANUAL.

ELECTRICAL CONNECTIONS

- Vac/Vdc
+ Vac/Vdc

1

Power supply: The upper limits must not be exceeded in order to avoid serious damage to the

2 module.

3

If the power supply source is not protected against overload, a safety fuse must be installed in the power supply line with a value suitable to what the situation requires.

GND
B-
A+
INPUTS
Z-D-IN-1 16V~
+

4 5 6
12
7 8 9 10 11 1

ModBus RS485
Connection for RS485 communication using the MODBUS master system as an alternative to the Z-PC-DINx bus. N.B.: The indication of the RS485 connection polarity is not standardised and in some devices may be inverted.

12
#1
7
#2
8
#3
9
#4
10
#5
11

12
PNP
#1 7 #2 8
#3
9
#4
10 #5 11

NPN

R=1k5 #1 1k5 #2 1k5 #3 1k5 #4 1k5
#5

1

1

INPUT SETTINGS:
Default settings:
Input #1: 0 ­ 100 Hz (16BIT) Input #2: 0 ­ 100 Hz (16BIT) Input #3: 0 ­ 100 Hz (16BIT) Input #4: 0 ­ 100 Hz (16BIT) Input #5: 0 ­ 100 Hz (16BIT)
Input #5 can be set as totalizer:
Input #5: 0 ­ 10 kHz (32BIT)

ATTENTION
The upper power supply limits must not be exceeded, as this might cause serious damage to the module. Switch the module off before connecting inputs and outputs. To meet the electromagnetic immunity requirements: · use shielded signal cables; · connect the shield to a preferential instrumentation earth system; · a fuse with a MAX. rating of 0,5 A must be installed near the module. · separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, etc...). · make sure that the module is not supplied with a supply voltage higher than that indicated in the technical specifications
in order not to damage it.

MI00205-7-EN

INSTALLATION MANUAL

4/4

