SENECA R-4RTD-8DIDO Series Mixed I O Module

INSTRUCTION MANUAL

MODEL: R-4RTD-8DIDO Series

PRELIMINARY WARNINGS

The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment.

The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

SYMBOL

WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.

SYMBOL

The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.

DISPOSAL

Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

QR

SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287

CONTACT INFORMATION

  • Technical support: supporto@seneca.it
  • Product information: commerciale@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies.
Stated data may be modified or supplemented for technical and/or sales purposes.

MODULE LAYOUT

VIEW

Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black

SIGNALS VIA LED ON FRONT PANEL

IO

TECHNICAL SPECIFICATIONS

IO

 

Installation

  1. Read the entire manual before proceeding with any operation.
  2. The module should only be installed by qualified electricians.
  3. Use the specific documentation available through the QR-CODE on page 1.
  4. Ensure appropriate measures are taken to prevent electrostatic discharges during installation.
  5. Dispose of electrical and electronic waste properly at authorized recycling centers.

Module Layout

Front: 106.6 mm x 108 mm

Side: 32.2 mm

Weight: 170 g

Enclosure: UL94-V0 self-extinguishing PC/ABS
material, black

ELECTRICAL CONNECTIONS

The upper power supply limits must not be exceeded, as this could cause serious damage to the module.
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
– use shielded signal cables;
– connect the shield to a preferential instrumentation earth system;
– separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).

 

IO

SETTING THE DIP-SWITCHES

WARNING

The DIP-switch settings are read only at boot time. At each change, perform a restart.

For use and settings via DIP-SWITCH, see the user manual available on the website on the web page dedicated to the product

SW1 DIP-SWITCH: DEFAULT SETTINGS

IO

DIP-SWITCH SW1 is located on the front of the device.

DAISY-CHAIN ETHERNET CONNECTION

CAUTION

IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES
Using the daisy-chain connection it is not necessary to use switches to connect the devices.

The following examples show the correct connections.

IO

 

IO

 

There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.

IO

 

 

IO

The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less than 100m.

ETHERNET CONNECTION RULES

For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.

FACTORY IP ADDRESS (ONLY R-4RTD-8DIDO)

The default module IP address is static: 192. 168. 90. 101

WEB SERVER

To access the maintenance Web Server, use the following credentials:
Default user: admin
Default password: admin

CAUTION

DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK

Specifications

  • Certifications: Insulation
  • Power Supply: RTD1, RTD2, RTD3, RTD4
  • Environmental Conditions: Assembly Configuration Connections/Communication Ports
  • Digital Inputs: 8
  • Digital Outputs: Voltage Threshold ON: > 11 Vdc; Threshold OFF:< 4 Vdc; Vmax: 24 Vdc; Impedance: 9 k
  • RTD Inputs: Compliant with IEC61131-2 type 3

 

FAQ

Q: Can the module be installed by anyone?

A: No, the module should only be installed by qualified electricians for safety and proper operation.

Q: How should I dispose of the product when no longer in use?

A: The product should be surrendered to authorized collection centers for recycling of electrical and electronic waste.

Q: What should I do if I encounter an LED signal that is not mentioned in the manual?

A: Contact technical support at supporto@seneca.it for assistance.