Instruction Manual for SENECA models including: R-4RTD-8DIDO Series Mixed I O Module, R-4RTD-8DIDO Series, Mixed I O Module, O Module

R-4RTD-8DIDO Series

1 день назад — For use and settings via DIP-SWITCH, see the user manual available on the website on the web page dedicated to the product. ... The fault-bypass function ...

For use and settings via DIP-SWITCH, see the user manual available on the website on the web page dedicated to the product. The DIP-switch settings are read ...

PDF preview unavailable. Download the PDF instead.

mi00711-1-en ?srsltid=AfmBOooIsAv4lEq180IDNBFI2baI5lPaBRGi3WWPJRzxhSCZypp3GHTr
INSTALLATION MANUAL
R-4RTD-8DIDO Series
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation. Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

DOCUMENTATION

SENECA s.r.l.; Via Austria, 26 ­ 35127 ­ PADOVA ­ ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287

CONTACT INFORMATION

Technical support

supporto@seneca.it

Product information

commerciale@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

MI00711-1-EN

INSTALLATION MANUAL

1/6

MODULE LAYOUT

FRONT
106.6 mm

SIDE
32.2 mm

108 mm

Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

SIGNALS VIA LED ON FRONT PANEL

LED
IO1/IO8
OUT SUP STS (Status only version R-4RTD-8DIDO) STS (Status only version R-4RTD-8DIDO-P)
COM (only version R- 4RTD-8DIDO-P)
FAIL RX (only version R- 4RTD-8DIDO) TX (only version R- 4RTD-8DIDO) ETH TRF (Yellow) ETH LNK (Green)

STATUS On Off On Off On
Flashing On
Flashing Off
Flashing On On
Flashing
Flashing
Flashing Flashing

LED meaning Digital input/output active Digital input/output not active Digital inputs/outputs powered Digital inputs/outputs not powered
IP address set Waiting for the IP address from the DHCP
IP address set No configured IP address No Profinet communication Profinet communication present
Digital output in FAIL RS485 port wiring error Reception of data packet completed on RS485
Transmission of data packet completed on RS485
Packet transit on Ethernet port Ethernet port connected

MI00711-1-EN

INSTALLATION MANUAL

2/6

TECHNICAL SPECIFICATIONS
CERTIFICATIONS

INSULATION

RTD1 RTD2 RTD3 RTD4

POWER SUPPLY ENVIRONMENTAL
CONDITIONS ASSEMBLY CONFIGURATION CONNECTIONS/ COMMUNICATION
PORTS DIGITAL INPUTS DIGITAL OUTPUTS
RTD INPUTS
MEASUREMENT ERROR

Voltage: 10 ÷ 40 Vdc; 19 ÷ 28 Vac; 45 ÷ 65 Hz; Absorption: 2 W
Operating temperature: from -25°C to 70°C; Humidity: 10% ÷ 90% non condensing. Storage temperature: from -30°C to +85°C Protection rating: IP20
35mm DIN rail IEC EN60715
With built-in WEB server (only version R-4RTD-8DIDO)

Removable 3.5 mm pitch terminal block, 1.5 mm2 max cable section 2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 1 RS485 port on terminals (only version R-4RTD-8DIDO)

Number of channels: 8; Voltage: Threshold ON: > 11 Vdc; Threshold OFF:< 4 Vdc; Vmax: 24 Vdc; Impedance: 9 k Compliant with IEC61131-2 type 3.

Number of channels: 8, MOSFET, PNP; Max voltage/current: 0.2 A; 12 ÷ 24 Vdc, Protected against short-circuit.

Number of channels:

4 with 2, 3 and 4 wires connection.

Type and measuring range: - PT100, EN 60751/A2 (ITS-90), -200 ÷ +650°C

- PT500, EN 60751/A2 (ITS-90), -200 ÷ +750°C

- PT1000, EN 60751/A2 (ITS-90), -200 ÷ +210°C

- CU50 GOST 6651-2009, -180 ÷ +200°C

- CU100 GOST 6651-2009, -180 ÷ +200°C

- NI100, EN 60751/A2 (ITS-90), -60 ÷ +250°C

- NI120 DIN 43760, -60 ÷ +250°C

- NI1000 DIN 43760, -60 ÷ +250°C

Resolution:

24 bit (Adc)

Accuracy class:

0.05% on the resistive value

Stability (noise):

18 bit ENOB

Temperature drift:

< 30 ppm/K

Sampling time:

from 25 to 400 ms

Scan time:

from 25 to 400 ms for all channels.

CMR @50/60 Hz:

>100 dB

NMR @ 50/60 Hz:

>75 dB

Sensor detection/interrupted conductors YES, disconnectable

Maximum cable resistance: 50 

Referred to RTD resistive value: 2-wire measurement 0.05 % + cable resistance 3-wire measurement 0.05 % + 0.005 % + per ohm cable resistance 4-wire measurement 0.05 %

MI00711-1-EN

INSTALLATION MANUAL

3/6

ELECTRICAL CONNECTIONS

CAUTION
The upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs. To meet the electromagnetic immunity requirements: - use shielded signal cables; - connect the shield to a preferential instrumentation earth system; - separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).

POWER SUPPLY

RS485 SERIAL PORT

+ /

20

­/

21

22

23 B(-) 24 A(+) 25 GND

Connection to the RS485 port. Polarity is not standardised and in some devices may be inverted.

RTD INPUTS 4 WIRE CONNECTION

A (40, 45, 53, 58)

+

B (41, 46, 54, 59)

C (42, 47, 55, 60)

D (43, 48, 56, 61)

S (44, 49, 57, 62)

3 WIRE CONNECTION

A (40, 45, 53, 58)

+

B (41, 46, 54, 59)

C (42, 47, 55, 60)

D (43, 48, 56, 61)

S (44, 49, 57, 62)

+

DIGITAL INPUTS (PNP) With external power
V EXT

DIGITAL OUTPUTS (PNP) With external power

10

LOAD

10

11

LOAD

11

12

LOAD

12

....

LOAD

....

17

LOAD

17

18+

+

V EXT

18+

19-

19-

The digital inputs must be powered The digital outputs must be powered externally to function properly (V EXT). externally to function properly (V EXT).

2 WIRE CONNECTION

A (40, 45, 53, 58)

+

B (41, 46, 54, 59)

C (42, 47, 55, 60)

D (43, 48, 56, 61)

S (44, 49, 57, 62)

SETTING THE DIP-SWITCHES
WARNING
The DIP-switch settings are read only at boot time. At each change, perform a restart. For use and settings via DIP-SWITCH, see the user manual available on the website on the web page dedicated to the product.

SW1 DIP-SWITCH: DEFAULT SETTINGS

SW1
DIP1 OFF DEFAULT DIP2 OFF SETTINGS

DIP-SWITCH SW1 is located on the front of the device.

MI00711-1-EN

INSTALLATION MANUAL

4/6

DAISY-CHAIN ETHERNET CONNECTION
CAUTION
IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES Using the daisy-chain connection it is not necessary to use switches to connect the devices. The following examples show the correct connections.

MODULE 1 MODULE 2 MODULE 3

MODULE 1 MODULE 2 MODULE 3

There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.

LOOP

LOOP

MODULE 1

MODULE 1 MODULE 2 MODULE 3

The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less than 100m.
ETHERNET CONNECTION RULES
For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.
FACTORY IP ADDRESS (ONLY R-4RTD-8DIDO)
The default module IP address is static: 192. 168. 90. 101
WEB SERVER
To access the maintenance Web Server, use the following credentials: Default user: admin Default password: admin
CAUTION DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK

MI00711-1-EN

INSTALLATION MANUAL

5/6


Adobe PDF Library 17.0 Adobe InDesign 18.5 (Windows)