ميگا ٽيڪ نيٽ 485-وائي ايٿرنيٽ ڊيوائس سرور
تعارف
خاصيتون
Net485 is to convert RS232 signals of [MegaTec] and other protocols to RS422 or RS485 signals.
خاصيتون:
- CPU is ARM 266MHz 32Bit, system clock is 208MHz, flash memory is 4M, SDRAM is 16M, and built-in watchdog.
- Net485 normal operating temperature and humidity range is 0℃ to 50℃ and 5% to 95%.
- FCC, Class B, CE, Rosh approved.
پاور وضاحتون
شيءِ | گھٽ ۾ گھٽ | وڌ ۾ وڌ |
ڊي سي ان پٽ Voltage | +5.3V | +40V |
ڊي سي ان پٽ ڪرنٽ | 3W وڌ ۾ وڌ |
پن کي تفويض
پن | انٽيپشن / ٻاھران | وصف |
P1 GND | جي اين ڊي | گرائونڊ پن |
P2 Power In | ان پٽ | ڊي سي پاور ان پٽ |
P3 RS232_TXD | ٻاھر | +5.5V and -5.5V Voltage level for RS232 |
P4 RS232_RXD | ان پٽ | -3V to -15V for logic ‘1’, +3V to +15V for logic ‘0’ |
P5-P7 No USE | ||
P8 SNMPSIG | NET485 card plug in detect, connect to PIN 10 | |
P9 GND | جي اين ڊي | گرائونڊ پن |
P10 SNMPSIG | NET485 card plug in detect, connect to PIN 8 | |
P11 RS232_DCD | ان پٽ | +/-3V to +/-15V for RS232 |
P12 RS232_DTR | ٻاھر | +5.5V and -5.5V for RS232 |
P13 RS232_DSR | ان پٽ | +/-3V to +/-15V for RS232 |
P14 RS232_RTS | ٻاھر | +5.5V and -5.5V for RS232 |
P15 RS232_CTS | ان پٽ | +/-3V to +/-15V for RS232 |
P16 RS232_RI | ان پٽ | +/-3V to +/-15V for RS232 |
P17-P26 No Use |
Signal Specification
وصول ڪندڙ ان پٽ
PARAMETER | حالتون | منٽ | ٽائيپ | MAX |
انٽ واليمtage حد | -25V | +25V | ||
داخل ٿيڻ جي حد گھٽ | ٽي اي = ± 25 ℃ | +0.6V | +1.2V | |
ان پٽ جي حد اعلي | ٽي اي = ± 25 ℃ | +1.5V | +2.4V | |
ان پٽ Hysteresis | 0.3V | |||
ان پٽ مزاحمت | ٽي اي = ± 25 ℃ | 3k ohm | 5k ohm | 7k ohm |
ٽرانسميٽر آئوٽ پُٽ
PARAMETER | حالتون | منٽ | ٽائيپ | MAX |
اوٽ وولٽtage جھول | All transmitter outputs loaded with 3k ohm to ground | ±5.0V | ±5.4V | |
پيداوار جي مزاحمت | ٽي اي = ± 25 ℃ | 300 | 10 ايم | |
آئوٽ پٽ شارٽ سرڪٽ | ±35mA | ±60mA | ||
موجوده |
سائيز جي وضاحت
Net485-Y Internal Card
طول و عرض | 137.7mm(L) × 60mm(W) × 43.0mm(H) |
وزن | 53g±2g |
ڳنڍيندڙ | 26pin gold finger |
Net485-Y External Card
طول و عرض | 156mm(L) × 82mm(W) × 32mm(H) |
وزن | 195g±2g |
Net485-Y Adapter
طول و عرض | 42.15mm(L) × 31.08mm(W) × 17.38mm(H) |
وزن | 12.8g±2g |
استعمال
فيڪٽري سيٽنگون
Net485 will be set according to the parameters related to the receiving data side provided by the user before shipping. Because the Net485 parameter setting requires the user to use a direct serial cable (1 to 1, 2 to 2… 9 to 9) connected to the computer side and set up using HyperTerminal. The external card requires the user to remove the case. To see the advanced user settings,
مهرباني ڪري اسان جي ٽيڪنيڪل سپورٽ سان رابطو ڪريو.
Ordinary users need to provide the following parameters at the receiving end to our company to make factory settings;
RS232 | RS422 | RS485 | |
ڊوائيس جو پتو | 01(Default Value) | 01 | 01 |
MODBUS Connection Mode | RTU (Default Value) | آر ٽي يو | آر ٽي يو |
RS Baud Rate | 9600(Default Value) | 9600 | 9600 |
RS Connection Type | RS232 (Default Value) | RS485 | RS485 |
Half Duplex / Full Duplex | Full Duplex (Default Value) | مڪمل ڊپلڪس | اڌ ڊپلڪس |
Serial Communication Electrical Level | عام موڊ (ڊفالٽ قدر) |
عام موڊ | عام موڊ |
درخواستون
Users can connect Net485 to UPS and MODBUS receiver or PC for testing.
هيٺ ڏنل مواد هڪ اڳوڻي آهيample of [Modscan] software testing.
If you connect Net485 to PC side for testing, you need to prepare your own RS485 to RS232 cable. You can refer to the following diagram for the connection method.
- Run [Modscan], click Connection, select the PC serial port connected to the Net485 output, and Modbus related settings. As shown in the figure.
- Select the holding register and start address to view حاصل ڪيل ڊيٽا.
- Look up the UPS data represented by the corresponding address bit in the provided register address file.
دستاويز / وسيلا
![]() |
ميگا ٽيڪ نيٽ 485-وائي ايٿرنيٽ ڊيوائس سرور [pdf] هدايت نامو Net485, Net485-Y, MegaTec 2023-7-6, Net485-Y Ethernet Device Server, Net485-Y, Ethernet Device Server, Device Server |