MegaTec Net485-Y Ethernet Device Server

MegaTec Net485-Y Ethernet Device Server

Introduction

Features

Net485 is to convert RS232 signals of [MegaTec] and other protocols to RS422 or RS485 signals.

Features:

  1. CPU is ARM 266MHz 32Bit, system clock is 208MHz, flash memory is 4M, SDRAM is 16M, and built-in watchdog.
  2. Net485 normal operating temperature and humidity range is 0℃ to 50℃ and 5% to 95%.
  3. FCC, Class B, CE, Rosh approved.
Power Specifications
Item Minimum Maximum
DC Input Voltage +5.3V +40V
DC Input Current 3W Maximum
Pin Assignment
Pin Input / Output Description
P1 GND GND Ground PIN
P2 Power In Input DC power input
P3 RS232_TXD Output +5.5V and -5.5V Voltage level for RS232
P4 RS232_RXD Input -3V to -15V for logic ‘1’, +3V to +15V for logic ‘0’
P5-P7 No USE
P8 SNMPSIG NET485 card plug in detect, connect to PIN 10
P9 GND GND Ground PIN
P10 SNMPSIG NET485 card plug in detect, connect to PIN 8
P11 RS232_DCD Input +/-3V to +/-15V for RS232
P12 RS232_DTR Output +5.5V and -5.5V for RS232
P13 RS232_DSR Input +/-3V to +/-15V for RS232
P14 RS232_RTS Output +5.5V and -5.5V for RS232
P15 RS232_CTS Input +/-3V to +/-15V for RS232
P16 RS232_RI Input +/-3V to +/-15V for RS232
P17-P26 No Use
Signal Specification

Receiver Inputs 

PARAMETER CONDITIONS MIN TYP MAX
Input Voltage Range -25V +25V
Input Threshold Low TA=±25℃ +0.6V +1.2V
Input Threshold High TA=±25℃ +1.5V +2.4V
Input Hysteresis 0.3V
Input Resistance TA=±25℃ 3 k ohm 5 k ohm 7 k ohm

Transmitter Outputs

PARAMETER CONDITIONS MIN TYP MAX
Output Voltage Swing All transmitter outputs loaded with 3k ohm to ground ±5.0V ±5.4V
Output Resistance TA=±25℃ 300 10M
Output Short-Circuit ±35mA ±60mA
Current
Size Specification

Net485-Y Internal Card 

Dimension 137.7mm(L) × 60mm(W) × 43.0mm(H)
Weight 53g±2g
Connector 26pin gold finger

Net485-Y Internal Card

Net485-Y External Card 

Dimension 156mm(L) × 82mm(W) × 32mm(H)
Weight 195g±2g

Net485-Y Internal Card

Net485-Y Adapter

Dimension 42.15mm(L) × 31.08mm(W) × 17.38mm(H)
Weight 12.8g±2g

Net485-Y Adapter

Usage

Factory Settings

Net485 will be set according to the parameters related to the receiving data side provided by the user before shipping. Because the Net485 parameter setting requires the user to use a direct serial cable (1 to 1, 2 to 2… 9 to 9) connected to the computer side and set up using HyperTerminal. The external card requires the user to remove the case. To see the advanced user settings,
Please contact our technical support.

Ordinary users need to provide the following parameters at the receiving end to our company to make factory settings;

RS232 RS422 RS485
Device Address 01(Default Value) 01 01
MODBUS Connection Mode RTU (Default Value) RTU RTU
RS Baud Rate 9600(Default Value) 9600 9600
RS Connection Type RS232 (Default Value) RS485 RS485
Half Duplex / Full Duplex Full Duplex (Default Value) Full Duplex Half Duplex
Serial Communication Electrical Level Normal Mode
(Default Value)
Normal Mode Normal Mode

Applications

Users can connect Net485 to UPS and MODBUS receiver or PC for testing.
The following content is an example of [Modscan] software testing.

If you connect Net485 to PC side for testing, you need to prepare your own RS485 to RS232 cable. You can refer to the following diagram for the connection method.

Applications

  1. Run [Modscan], click Connection, select the PC serial port connected to the Net485 output, and Modbus related settings. As shown in the figure.
    Applications
    Applications
  2. Select the holding register and start address to view the received data.
    Applications
  3. Look up the UPS data represented by the corresponding address bit in the provided register address file.

Documents / Resources

MegaTec Net485-Y Ethernet Device Server [pdf] Instruction Manual
Net485, Net485-Y, MegaTec 2023-7-6, Net485-Y Ethernet Device Server, Net485-Y, Ethernet Device Server, Device Server