AIMS LogoOperation Manual

AIMS-4X Analog to Modbus Combiner-AIMS-8U-PPI-Converter

 This brief manual is primarily meant for quick reference to wiring connections and parameter searching.
For more details on operation and application; please log on to www.ppiindia.net

Input Registers (Read-Only Parameters)

Parameter MODBUS Address Values
Process Value 1561 to 1564 (4 Channels)
1561 to 1568 (8 Channels)
Value PV Error Type
-32768 Under Range
+32752 Over Range
+32767 Sensor Open
Alarm-1 Status 1577 AIMS 4X Analog to Modbus Combiner AIMS 8U PPI Converter

Bit Value

Status

0 Alarm OFF
1 Alarm ON

For 4 Channel Version (AIMS-4X), ignore Bit-4 to Bit-15
For 8 Channel Version (AIMS-8X), ignore Bit-8 to Bit-15

Alarm-2 Status 1578
Alarm-3 Status 1579
Alarm-4 Status 1580
Ambient Temperature 82 Signed integer values from -30000 to +30000 representing  them easured  Ambient Temperature through the semi-conductor sensor mounted on the Module. The measured value is always in °C with 0.1 resolution. For example, 30.0°C is represented as 300.

Holding Registers (Read / Write Parameters)

Parameter MODBUS Address

Settings (Default Value)

Input Type 83 to 86 (4 Channels) 83 to 90 (8 Channels) Applicable for Input Type TC / RTD Pt100 / V / mV / m

Value

Type

0 Type J Thermocouple
1 Type K Thermocouple
2 Type T Thermocouple
3 Type R Thermocouple
4 Type S Thermocouple
5 Type B Thermocouple
6 Type N Thermocouple
7 Reserved TC (Default: Type J)
8 RTD Pt100, 3-wire
9 0 to 20 mA
10 4 to 20 mA
11 0 to 80 mV
12 Reserved (Default: 0 to 80 mV)
13 0 to 1.25 V
14 0 to 5 V
15 0 to 10 V
16 1 to 5 V

(Default : 0 to 10 V)
Applicable for Input Type RTD Pt100 

Value Type
0 RTD Pt100, 3-wire (This is a Read Only parameter)
0 Type J Thermocouple
1 Type K Thermocouple
2 Type T Thermocouple
3 Type R Thermocouple
4 Type S Thermocouple
5 Type B Thermocouple
6 Type N Thermocouple
7 Reserved TC (Default: Type J)
8 0 to 80 mV

Applicable for Input Type TC / (Default : Type K)

Parameter MODBUS Address Settings(Default Value)
Input Type 83 to 86 (4 Channels) 83 to 90 (8 Channels) Applicable for Input Type V / mA
Value Type
0 Oto 20 mA
1 4 to 20 mA
2 Oto 1.25 V
3 Oto 5V
4 Oto 10V
5 1 to 5V
(Default : 0 to 10 V)
Temperature Units 99 to 102
(4 Channels)
99 to 106
(8 Channels)
Conditional Parameter (Note 2)
Value Unit
0 °C
1 °F
(Default : °C)
DC
Resolution (Note’)
115 to 118
(4 Channels)
115 to 122
(8 Channels)
Conditional Parameter No e 2)
Value Resolution
0 1
1 0.1
2 0.01
3 0.001
4 0.0001
(Default : 1 Unit for DC Linear input &
0.1 for Thermocouple & RTD)
Signal Low 501 to 504 (4 Channels) 501 to 508 (8 Channels) Conditional Parameter “eV
Input Type Settings Default
0 to 20 mA 0.00 to Signal High 0.00
4 to 20 mA 4.00 to Signal High 4.00
0 to 80 mV 0.00 to Signal High 0.00
0 to 1.25 V 0.000 to Signal High 0.000
0 to 5 V 0.000 to Signal High 0.000
0 to 10 V 0.00 to Signal High 0.00
1 to 5 V 1.000 to Signal High 1.000
Signal High 517 to 520 (4 Channels) 517 to 524 (8 Channels) Conditional Parameter (N°Ie 2)
Input Type Settings Default
0 to 20 mA Signal Low to 20.00 20.00
4 to 20 mA Signal Low to 20.00 20.00
0 to 80 mV Signal Low to 80.00 80.00
0 to 1.25 V Signal Low to 1.250 1.250
0 to 5 V Signal Low to 5.000 5.000
0 to 10 V Signal Low to 10.00 10.00
1 to 5 V Signal Low to 5.000 5.000
Range Low 131 to 134 (4 Channels)131 to 138 (8 Channels) (Nolo 2) Conditional Parameter -30000 to 30000 (Default : 0)
Range High 147 to 150 (4 Channels) 147 to 154 (8 Channels) (Nolo 2) Conditional Parameter -30000 to 30000 (Default : 1000)
Offset for PV (Note” 163 to 166 (4 Channels) 163 to 170 (8 Channels) -30000 to 30000 (Default : 0)
Alarm-1 Type 179 to 182 (4 Channels) 179 to 186 (8 Channels)
Alarm-2 Type 243 to 246 (4 Channels) 243 to 250 (8 Channels)
Value Type
0 None
1 Process Low
Alarm-3 Type 307 to 310 (4 Channels) 307 to 314 (8 Channels)
2 Process High
(Default : None)
Alarm-4 Type 371 to 374 (4 Channels) 371 to 378 (8 Channels)
Parameter MODBUS Address Settings (Default Value)
Alarm-1 Set-point (Note “ 195 to 198 (4 Channels)
195 to 202 (8 Channels)
Min. to Max. Range specified for the selected Input Type
Refer Table 1 (Default : MM or Max Range depending on the Alarm type)
Alarm-2 Set-point (Note “ 259 to 262 (4 Channels)
259 to 266 (8 Channels)
Alarm-3 Set-point (Note “ 323 to 326 (4 Channels)
323 to 330 (8 Channels)
Alarm-4 Set-point (Note “ 387 to 390 (4 Channels)
387 to 394 (8 Channels)
Alarm-1 Hysteresis (Note V 211 to 214 (4 Channels)
211 to 218 (8 Channels)
1 to 30000 (Default : 20)
Alarm-2 Hysteresis (Note I) 275 to 278 (4 Channels)
275 to 282 (8 Channels)
Alarm-3 Hysteresis (Note V 339 to 342 (4 Channels)
339 to 346 (8 Channels)
Alarm-4 Hysteresis (Note 1) 403 to 406 (4 Channels)
403 to 410 (8 Channels)
Alarm-1 Inhibit 227 to 230 (4 Channels)
227 to 234 (8 Channels)
Alarm-2 Inhibit 291 to 294 (4 Channels)
291 to 298 (8 Channels)
Value Inhibit
0 Disable
Alarm-3 Inhibit 355 to 358 (4 Channels)
355 to 362 (8 Channels)
1 Enable
(Default : Disable)
Alarm-4 Inhibit 419 to 422 (4 Channels)
419 to 426 (8 Channels)
Enable Bottom Cliping 435 to 438 (4 Channels)
435 to 442 (8 Channels)
Value Enable
0 No
1 Yes
Default : No)
Bottom Clip Value 451 to 454 (4 Channels)
451 to 458 (8 Channels)
-30000 to 30000 (Default : 0)
Enable Top Cliping 467 to 470 (4 Channels)
467 to 474 (8 Channels)
Value Enable
0 No
1 Yes
Default : No)
Top Clip Value 483 to 486 (4 Channels) 483 to 490 (8 Channels) -30000 to 30000 (Default : 1000)

Configuring Communication Parameters

Parameter MODBUS Address

Settings (Default Value)

Modbus Slave ID 1 1 to 247 (Default : 1)
Baud Rate 2
Value 2400 bps
0 4800 bps
1 9600 bps
2 19200 bps
3 38400 bps
4 57600 bps
5 115200 bps
6 Baud Rate

(Default : 9600 bps)

Parity 3
Value Parity
0 None
1 Even
2 Odd

(Default : Even)

Note 1
Thermocouples (J, K, T, R, S, B, N) and RTD Pt100 (3-wire) Inputs
The process value is always measured in 0.1°C/°F resolution. That is, for example, the value 300 means 30.0°C / °F.
The same should be followed while setting the values for the parameters that are resolution based (like Zero Offset,
Alarm Set-point, Alarm Hysteresis, etc.). That is for example, set 300 counts for 30.0°C / °F.
DC mA / mV / V Inputs
(Also Refer Appendix A : DC Linear Signal Interface)
The measured PV is a Resolution-less Scaled Value derived using the values for the parameters : Signal Low, Signal
High, Range Low and Range High. The parameter ‘DC Resolution’ holds the desired resolution that can be used to insert appropriate Decimal Place in the scaled PV. For example, if the DC Resolution value is 2 (0.01) then the scaled value of 3000 can be read as 30.00.
Similarly the corresponding parameters like Zero Offset, Alarm Set-point, Alarm Hysteresis, etc., are also resolution less and, if desired, the parameter value for ‘DC Resolution’ should be used for appropriate Decimal Place.
Note 2
Conditional Parameters are those whose usage depend upon the values set for some other parameters. For example; the parameters ‘Signal Low’ & ‘Signal High’ for a selected channel are used only if the input type for the selected channel is DC Input (mV / V / mA). The access to the conditional parameters for Read / Write operation, however, is not restricted.

Input Type Range (Min. to Max.) Resolution
Type J Thermocouple 0 to +960.0°C / +32.0 to +1760.0°F 0.1 °C / °F
Type K Thermocouple -200.0 to +1376.0°C / -328.0 to +2508.0°F
Type T Thermocouple -200.0 to +387.0°C / -328.0 to +728.0°F
Type R Thermocouple 0 to +1771.0°C / +32.0 to +3219.0°F
Type S Thermocouple 0 to +1768.0°C / +32.0 to +3214.0°F
Type B Thermocouple 0 to +1826.0°C / +32.0 to +3218.0°F
Type N Thermocouple 0 to +1314.0°C / +32.0 to +2397.0°F
3-wire, RTD Pt100 -199.0 to +600.0°C / -328.0 to +1112.0°F
0 to 20mA DC current -30000 to 30000 units 1
0.1
0.01
0.001
0.0001
Units
4 to 20mA DC current
0 to 80mV DC voltage
0 to 1.25V DC voltage
0 to 5.0V DC voltage
0 to 10.0V DC voltage
1 to 5.0V DC voltage

CONFIGURING COMMUNICATION

Switch Position AIMS 4X Analog to Modbus Combiner AIMS 8U PPI Converter - Down AIMS 4X Analog to Modbus Combiner AIMS 8U PPI Converter - Up
Mode Indicator OFF ON
Operation Mode Normal Configuration
Communication Parameter Values User Set values for Module Slave ID, Baud Rate & Parity Module Slave ID : 1 Baud Rate : 9600 Parity : Even

AIMS 4X Analog to Modbus Combiner AIMS 8U PPI Converter - CONFIGURING

OVERALL DIMENSION

AIMS 4X Analog to Modbus Combiner AIMS 8U PPI Converter - DIMENSION

Width (W) : 22.5 mm  Height (H) : 101.0 mm  Depth (D) : 119.0 mm

ELECTRICAL CONNECTIONS

AIMS 4X Analog to Modbus Combiner AIMS 8U PPI Converter - DIMENSION 1

Note : For 4 Channel Version the connectors for AI-5 to AI-8 are not fitted.

AIMS LogoAIMS-4/8X
4 / 8 Channel DIN-Rail Analog Input Modules
MODBUS over RS485 Serial Interface
(Single-Ended & Differential Input Versions)
PPI 101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net
support@ppiindia.net
Jan 2022

Documents / Resources

PPI AIMS-4X Analog to Modbus Combiner-AIMS-8U-PPI-Converter [pdf] Instruction Manual
AIMS-4X Analog to Modbus Combiner-AIMS-8U-PPI-Converter, AIMS-4X, Analog to Modbus Combiner-AIMS-8U-PPI-Converter, Combiner-AIMS-8U-PPI-Converter, PPI-Converter