Pepperl Fuchs FB6208C Digital Output With Shutdown - Front view

Pepperl Fuchs FB6208C Digital Output With Shutdown -

Pepperl Fuchs FB6208C Digital Output With Shutdown - icon 1

Digital Output with Shutdown Input FB6208C

  • 8-channel
  • Outputs Ex ib
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Galvanic group isolation
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown

Function

The device features 8 independent channels.
The device can be used to drive low power solenoids, sounders, or LEDs.
Open and short-circuit line faults are detected.
The outputs are galvanically isolated from the bus and the power supply.
The outputs can be switched off via a contact. This can be used for bus-independent safety applications.

Connection

Pepperl Fuchs FB6208C Digital Output With Shutdown - Connection

Technical Data

Slots
Occupied slots 2
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Performance level (PL) PL d
Supply
Connection backplane bus
Rated voltage Ur 12 V DC , only in connection with the power supplies FB92**
Power dissipation 2.35 W
Power consumption 2.35 W
Internal bus
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Digital output
Number of channels 8
Suitable field devices
Field device Solenoid Valve
Field device [2] audible alarm
Field device [3] visual alarm
Connection channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V:  9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+,  16-
 

Current limit

Imax 5.2 mA
 

Open loop voltage

Us 21.6 V
Line fault detection can be switched on/off for each channel via configuration tool
Test current 0.33 mA
Short-circuit < 300 Ω
Open-circuit > 50 kΩ
Response time 20 ms (depending on bus cycle time)
Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication
Indicators/settings
LED indication LED green: supply
LED red: line fault , communication error red flashing
Coding optional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Conformity
Electromagnetic compatibility NE 21
Degree of protection IEC 60529
Environmental test EN 60068-2-14
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Damaging gas EN 60068-2-42
Relative humidity EN 60068-2-78
Ambient conditions
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Storage temperature -25 … 85 °C (-13 … 185 °F)
Relative humidity 95 % non-condensing
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
ibration reistance frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 … 100 Hz; transition frequency: 13.2 Hz   mplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection IP20 (module) , a separate housing is required acc. to the system description
Connection removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14… 1.5 mm2) or screw terminals  (0.08…. 1.5 mm2)
Mass approx. 750 g
Dimensions 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-type examination certificate PTB 97 ATEX 1074 U
Marking 1 II 2 G Ex d [ib] IIC Gb
1 II (2) D [Ex ib Db] IIIC
Output
Voltage Uo 30 V
Current Io 13.5 mA
Power Po 404 mW (characteristic curve rectangular type)
Galvanic isolation
Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-1:2014
EN 60079-11:2012
International approvals
ATEX approval PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U
General information
System information The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity,
Attestation of Conformity and instructions have to be observed where applicable. For
information see www.pepperl-fuchs.com.

Assembly

Pepperl Fuchs FB6208C Digital Output With Shutdown - Front view

Accessories

FB9224* Field Unit
FB9225* Redundancy Field Unit
FB9248* Field Unit

Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.

Pepperl Fuchs FB6208C Digital Output With Shutdown - Front viewRelease date: 2022-07-06
Date of issue: 2022-07-06
Filename: 542157_eng.pdf
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com