RKP-CMU1 1U Rack Mountable Control and Monitor Unit

MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - QRhttps://www.meanwell.com/webapp/product/search.aspx?prod=RKP-CMU1&pdf=UktQLUNNVTEsUktQLTFVLUNNVTEtRS5wZGY=&a=4

Features

  • 1 U low profile/19-inch rack mountable
  • Front panel LCD and buttons for on-site service without PC
  • USB-, RS-232 or Ethernet interface for PC connection locally or remote monitoring and control via GSM modem
  • Alarm/event log with time and date
  • Windows-based PC communication software
  • Easy wire connections on rear side
  • 4 user programmable relay outputs for traditional remote monitoring or warning
  • 5 years warranty

Applications

  • Industrial automation
  • Distributed power architecture system
  • Wireless/telecommunication solution
  • Redundant power system
  • Electric vehicle charger system
  • Constant current source system

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

RKP-CMU1 is a fully digitalized control / monitor unit for the RKP-1U power system. Equipped with USB, RS-232, and ethernet interface, it can be connected locally to PC to execute the control and monitoring tasks. With built-in 4 configurable relay contacts, users can flexibility monitor specific events or alarms and react suitable action accordingly.

Model Encoding

MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - fig

MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - icon 20 Note: Due to compatibility issue between old and new firmware of RKP-CMU1 and PSU, when choosing Rack PSU, please pay attention to the firmware revision of PSU and RKP-CMU1. Details please refer to the user’s manual of RKP-CMU1.

SPECIFICATION

MODELRKP-CMU1RKP-1U❑ -CMU1
OUTPUTDIGITAL METER Note.6Display the DC output voltage, current, and internal temperature
CONTROL OUTPUT Note.6PMBus signal
LED INDICATORGreen: Power on Red:Alarm
RELAY CONTACT4 user programmable relay, relay contact rating(max.): 30V/1A resistive
INPUTVOLTAGE RANGE Note.312 – 15VDC
CURRENT1A112VDC 0.8A/15VDC
MONITORING INPUTS Note.6PMBus signal
FUNCTIONDISPLAYLCD 16×2 Alphanumeric Matrix Display / PC Web Page Display
MONITOROutput Voltage! Load Current! Temperature! Input Voltage
CONTROLOutput Voltage, Current Limit, ON/OFF
COMM. INTERFACEUSB, RS-232, Ethernet
MODEL SUPPORTEDRCP-1600, RCP-2000, DRP-3200RCP-2000
ENVIRONMENTWORKING TEMP. Note.1-25 -+70°C
WORKING HUMIDITY20 – 90% RH non-condensing
STORAGE TEMP., HUMIDITY-40 – +85t, 10 – 95% RH non-condensing
VIBRATION10 – 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY &
EMC (Note 4)
SAFETY STANDARDSEAC TP TC 004 approved, design refer to TUV BS EN/EN62368-1UL62368-1, CSA C22.2 No. 62368-1,TUV BS EWEN62368-1, EACTPTC 004 approved
WITHSTAND VOLTAGE Note.201P-FG:0.7KVDC1/P-01P:3KVAC 11P-FG:2KVAC 0/P-FG:0.7KVDC
ISOLATION RESISTANCE Note.20/P-FG:100M Ohms / 500VDC ! 25°C! 70% RH1/P-011), I/P-FG,O/P-FG:100M Ohms / 500VDC / 25t/ 70% RH
EMC EMISSIONCompliance to BS EN/EN55032 (CISPR32) Conduction Class B, Radiation Class A; BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITYCompliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN1EN61000-6-1(BS EN/EN50082-2), BS EN/EN55035, light industry level, EAC TP TC 020
OTHERSMTBF671.5K hrs min. Telcordia SR-332 (Bellcore) ; 110.5K hrs min. MIL-HDBK-217F (25°C)
DIMENSION147.5*127*41mm (L*W*H)350.8*483.6*44mm (L*W*H)
PACKING0.8Kg; 16pcs/13.8Kg/0.79CUFT4.4Kg; 3pcs/14.2Kg12.67CUFT
NOTE1.LCD may freeze under -10t .
2.SK100 and all of signal connectors (except CN502, CN503, and USB port) are considered as 0/P.
3.Recommanded use MEAN WELL power adaptor series: GS12, GS15, GS18, GE12, GE18, GST18.
4.The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwellcom)
5.The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft).
6.Please refer to respective specs of PSU models for the maximum number RKP-CMU1 can control and monitor.
* Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimeraspx

Function Manual

  1. Communication interface
    MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - icon 20 RKP-CMU1 can control and monitor parameters of power units via PMBus communication, and PC can manage the whole system by using USB, RS232, or Ethernet to connect to RKP-CMU1.
    MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - icon 20 PMBus: RKP-CMU1 supports PMBus Rev. 1.1 with maximum 100KHz bus speed, allowing information reading, status monitoring and output trimming. For details, please refer to the Installation Manual.MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - USB
  2. Monitoring and control
    RKP-CMU1 can monitor parameters of power units such as output voltage, output current, internal temperature, status, serial number, and firmware version. It also can turn power units on/off together or separately by using “ON/OFF’ pin in CN500 or PMBus “CONTROL” pin in JK1 or PMBus ‘OPERATION” command, shows below. By using PMBus, output voltage and over load protection of power units are adjustable. Please refer to the Installation Manual.
  3. Real time clock, Data Log and Event Log
    RKP-CMU1 has a build-in real time clock data to display actual date/time and for log time stamp. The data logger is designed to store operating data when the systems works. It has 1000 recodes and the interval of log is programmable from 1 to 60 minutes. The event log store system condition when alarm occur and remove. There are 600 records in event log.
  4. Programmable relay
    There are 4 relays and each relay has normal open, normal close and common contact in terminal block. Their active conditions are programmable for flexible application, like charger and generator control.
FunctionSub-functionPSUParameter
Alarm1 Any alarm
2.0VP 3.0LP 4.Short circuit
5.0TP
6.High Temperature
7.AC fail
8.Fan lock
9.PMBus error
N/AN/A
PSU ON1.1mmediatelyPSUO- 310 sec.
2.Delay1 – 600 sec.
PSU OFF1.1mmediatelyPSUO- 310 sec.
2.Delay1 – 600 sec.
Digital inputD-IN1 – D-1N4N/AN/A

MEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - USB MechanicalMEAN WELL RKP-CMU1 1U Rack Mountable Control and Monitor Unit - USB Mechanical 1※ IN/OUT Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions

Pin No.FunctionDescription
1,7ON/OFFEach unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B(pin 1,7) and +5V-AUX(pin 13). Short: ON, Open:OFF. (Note.2)
2,8AC-OKLow : When the input voltage is 1 87Vrms. High : when the input voltage in 75Vrms. (Note.2)
3,9DC-OKHigh : When the Vout 80±5%. Low : When Vout -:= 80±5%. (Note.2)
4,10PVConnection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
5,11T-ALARMHigh : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm. Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
6,12FAN FAILHigh : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
13+5V-AUXAuxiliary voltage output, 4.5 — 5.5V, referenced to GND-AUX (pin 15). The maximum load current is 0.3A. This output has the built-in “Oring diodes” and is not controlled by the remote ON/OFF control.
14+12V-AUXAuxiliary voltage output, 10.8 —13.2V, referenced to GND-AUX (pin 15). The maximum load current is 0.8A. This output has the built-in “Oring diodes” and is not controlled by the remote ON/OFF control.
15GND-AUXAuxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
16∼21N.C.Not used.
22+SPositive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
23SNegative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
24+V(signal)Positive output voltage. For local sense use only, can’t be connected directly to the load.
25-V(signal)Negative output voltage. For local sense use only, can’t be connected directly to the load.

※ IN/OUT Connector Pin No. Assignment(JK1) : RJ45 8 positions

Pin No.FunctionDescription
1,2DA,DBDifferential digital signal for parallel control. (Note.1)
3-V(signal)Negative output voltage. For parallel control, can’t be connected directly to the load.
4CONTROLRemote ON/OFF control pin used in the PMBus interface. (Note.2)
5NCNot use.
6SDASerial Data used in the PMBus interface. (Note.2)
7SCLSerial Clock used in the PMBus interface. (Note.2)
8GND-AUXAuxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).

Note.1: Non-isolated signal, referenced to -V(signal).
Note.2: Isolated signal, referenced to GND-AUX.
※ IN/OUT Connector Pin No. Assignment(CN502) : D-type Male 9 positions

Pin No.FunctionDescription
1,4,6,7,8,9NCNot used.
2RXDData receiving pin of RS-232 interface.
3TXDData transmitting pin of RS-232 interface.
4GND-FGRS-232 common GND. This signal connects to FG and isolated from -V and GND-AUX.

※ IN/OUT Connector Pin No. Assignment(CN503) :HRS DF11-8DP-2DS or equivalent

Pin No.FunctionDescription
1,3,5,7D-IN1 D-IN2 D-IN3 D-IN4The isolated digital input signal and referenced to GND-FG. Open from GND-FG or -F5V : Logic “1” input to RKP-CMU1 short to GND-FG or OV : Logic “0” input to RKP-CMU1
2,4,6,8GND-FGCommon GND for D-IN. This signal connects to FG and isolated from -V and GND-AUX.

※ IN/OUT Connector Pin No. Assignment(JK500) :RJ45 8 position

Pin No.FunctionDescription
1,2TX+/TX-Transmit data used in the Ethernet interface.
3,6RX+/RX-Receive data used in the Ethernet interface.
4,5,7,8NCNot used.

※ IN/OUT Connector Pin No. Assignment(TB4) :DECA MX422-25412 or equivalent

Pin No.FunctionDescription
1,4,7,10Relay-NONormal-open contact of programmable relay.
2,5,8,11Relay-NCNormal-close contact of programmable relay.
3,6,9,12Relay-COMCommon for NO/NC contact.

Note: Relay contact rating (max.) : 30Vdc/1A resistive.
※ IN/OUT Connector Pin No. Assignment(SK100): Schurter 4840.2201 or equivalent

Pin No.FunctionDescription
1+VINPositive input voltage for RKP-CMU1.
2-VINNegative input voltage for RKP-CMU1.

MEAN WELL logoFile Name:RKP-CMUl-SPEC 2022-08-08