MEAN WELL RCP-1U Rack System 1000 – 3000W 1U Distributed Power System

MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System

Features

  • Universal AC input / Full range
  • 1U profile 19″ rack shelf, fitting three 1000W modules up to 3000W with active current sharing
  • Output voltage programmable
  • Support hot swap (hot plug)
  • 5 years warranty

Applications

  • Industrial automation
  • Distributed power architecture system
  • Wireless/telecommunication solution
  • Redundant power system
  • Electric vehicle charger system
  • Constant current source system

GTIN CODE

Description
RCP-1U rack system is a power distribution solution utilizing the rack configuration with 1U low profile. Starting with a single unit of 1000W, RCP-1000 is the front end rectifier (or, power supply). With the active current sharing function, up to 3000W is able to be provided by 1 stack of the 19″ rack mountable shelf RCP-1U and 8000W by 3 stacks. The design flexibility for system applications is ideally fulfilled by various in features, such as output programming, remote ON-OFF, auxiliary power, etc.

Model Encoding/Order Information

MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-1

SPECIFICATION – Power Supply System

MODEL RCP-3K1U-12 RCP-3K1U-24 RCP-3K1U-48
 

 

 

OUTPUT

RECTIFIER RCP-1000-12 RCP-1000-24 RCP-1000-48
RACK SHELF RCP-1UI or RCP-1UT
OUTPUT VOLTAGE 12V 24V 48V
MAX. OUTPUT CURRENT 180A 120A 63A
MAX. OUTPUT POWER Note.5 2160W 2880W 3024W
 

 

INPUT

VOLTAGE RANGE                                  Note.4 90 ~ 264VAC 127 ~ 370VDC        
FREQUENCY RANGE 47 ~ 63Hz
AC CURRENT (Typ.)PER MODULE 8.5A/115VAC 4.5A/230VAC   10.5A/115VAC 5.5A/230VAC 11A/115VAC 5.5A/230VAC
LEAKAGE CURRENT <3.5mA / 230VAC
 

 

 

 

FUNCTION

AUXILIARY POWER 5V @ 0.3A
REMOTE ON-OFF CONTROL By electrical signal or dry contact  ON:short  OFF:open
REMOTE SENSE Compensate voltage drop on the load wiring up to 0.5V.
OUTPUT VOLTAGE PROGRAMMABLE Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual.
DC OK SIGNAL The isolated TTL signal out, Please refer to the Installation Manual
AC OK SIGNAL The isolated TTL signal out, Please refer to the Installation Manual
OVER TEMP WARNING Logic ” High” for over temperature warning, Please refer to the Installation Manual, isolated signal
 

 

 

ENVIRONMENT

WORKING TEMP. -20 ~ +60℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ±0.02%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
 

 

 

 

 

 

 

 

 

 

 

SAFETY & EMC

(Note 6)

SAFETY STANDARDS UL62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC      
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
 

 

 

EMC EMISSION

Parameter Standard Test Level / Note
Conducted BS EN/EN55032 (CISPR32) Class B
Radiated BS EN/EN55032 (CISPR32) Class B
Harmonic Current BS EN/EN61000-3-2 —–
Voltage Flicker BS EN/EN61000-3-3 —–
 

 

 

 

 

 

EMC IMMUNITY

BS EN/EN55035, BS EN/EN61000-6-2
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 3, 8KV air ; Level 2, 4KV contact
Radiated BS EN/EN61000-4-3 Level 3
EFT / Burst BS EN/EN61000-4-4 Level 3
Surge BS EN/EN61000-4-5 Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Conducted BS EN/EN61000-4-6 Level 3
Magnetic Field BS EN/EN61000-4-8 Level 4
Voltage Dips and Interruptions BS EN/EN61000-4-11 >95% dip 0.5 periods, 30% dip 25 periods,

>95% interruptions 250 periods

 

OTHERS

DIMENSION Rack 350.8*483.6*44(L*W*H)
PACKING 13.2Kg; 1pcs/13.2Kg/2.67CUFT
NOTE 1 All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature

2 Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0 1uf & 47uf parallel capacitor Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition It will go back to normal ripple level once the output load is more than 10%

3 Tolerance : includes set up tolerance, line regulation and load regulation

4 Derating may be needed under low input voltages Please check the derating curve for more details 5 Output of all the RCP-1000 modules are connected in parallel in the rack

6 The power supply is considered a component which will be installed into a final equipment All the EMC tests are been executed by mounting the unit on a 720mm*360mm metal plate with 1mm of thickness The final equipment must be re-confirmed that it still meets EMC directives For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies ”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)

7 The ambient temperature derating of 3 5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft)

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Function Manual

  1. Remote ON/OFF Control
    The PSU can be turned ON/OFF together or separately by using the “Remote ON-OFF” function.MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-2
  2. Voltage Drop Compensation
    1. Remote Sense
      The remote sense compensates voltage drop on the load wiring up to 0.5V.MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-3
    2. Local Sense
      Notice: The +S,-S, on CN500 have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-4
    3. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
      1. Output voltage can be trimmed between 90~110% of its rated value by the following method.
      2. +S & +V, -S & -V also need to be connected on CN500.MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-5RCP-1000-12MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-6RCP-1000-24MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-7
        RCP-1000-48MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-8
    4. I C Bus Interface 2
      For the details of I C bus used on this product, please refer to the Installation Manual.

Mechanical Specification (Rack System)

MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-9

MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-10

MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-11

IN/OUT Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions(female type)MEAN-WELL-RCP-1U-Rack-System-1000-3000W-1U-Distributed-Power-System-fig-12

Pin No. Function Description
1,8,15 RemoteON-OFF Each unit can separately turn the output on and off by electrical or dry contact between Remote ON-OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.
2,9,16 AC-OK Low : When input voltage is ≧82Vrms +/-4V. High : When input voltage in≦82Vrms +/-4V.
3,10,17 DC-OK High : When Vout≦80%+/-5%. Low : When Vout ≧80%+/-5%
4,11,18 V-TRIM Connection for output voltage programming.
5,12,19 T-ALARM High : When the internal temperature is within safe limit. Low : 10℃ below the thermal shut down limit.
6 +5V-AUX Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7).

The maximum load current is 0.3A. This output has the built-in “Oring diodes” and is not controlled by the remote ON/OFF control.

7 GND-AUX Auxiliary voltage output GND.

The signal return is isolated from the output terminals (+V & -V).

14 CS Current sharing signal.

When units are connected in parallel, the CS pins of the units should be connected to allow current balance between units.

20 +S Positive sensing for Remote Sense.
21 -S Negative sensing for Remote Sense.
22 +V Positive output voltage.
23 SCL 2

Serial clock used in the I C interface option. Refer to the Instruction Manual.

24 SDA 2

Serial data used in the I C interface option. Refer to the Instruction Manual.

25 -V Negative output voltage.

File Name:RCP-1U Rack System-SPEC 2024-01-26.

Documents / Resources

MEAN WELL RCP-1U Rack System 1000 - 3000W 1U Distributed Power System [pdf] Owner's Manual
RCP-3K1U-12, RCP-3K1U-24, RCP-3K1U-48, RCP-1000-12, RCP-1000-24, RCP-1000-48, RCP-1U Rack System 1000 3000W 1U Distributed Power System, RCP-1U Rack System, 1000 3000W 1U Distributed Power System, 1U Distributed Power System, Distributed Power System, Power System, System

References

Leave a comment

Your email address will not be published. Required fields are marked *