MeanWELL

MEAN WELL DUPS20 20A DIN Rail Type Uninterruptible DC-UPS Module

MEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module

Features

  • Uninterruptible DC-UPS controller
  • Parallel connection to DC BUS (Power supply +DC-UPS Module + Batteries +Load)
  • Suitable for 24V system, up to 20A
  • 2A Battery charging current
  • Allows 4AH-135AH lead-acid various battery capacities
  • Complete diagnostic and monitoring for DC BUS OK, battery discharge, battery fail
  • LED indicator for signal status
  • Protections: Battery reverse polarity protection & Short circuit(By inte
  • Battery discharge/Over discharge current
  • Cooling by free air convection
  • Width only by 40mm
  • 3 years warranty

Description

The DUPs20 is a 20A DIN rail type DC-UPS module, and it is paired with a power supply and an external battery to achieve the backup function. When the AC mains fails or isinterrupted, the load will be immediately connected to the battery pack to avoid interruption and to ensure the continuous operation of the entire system (the operating time depends on the capacity of the battery pack). The main features of DUPS20 include: fast installation, small size (only 40mm wide)suitability for 24V battery packs and various capacities of 4AH-135AH, 2A battery charging current, low voltage disconnect for battery protection and more. The product is suitable for use in data centers, security systems, emergency lighting, wireless communication UPS, central monitoring systems, etc.

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

Model EncodingMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-2

Specifications

MODEL DUPS20
 

DC UPS INPUT

NORMAL INPUT VOLTAGE 24Vdc
INPUT VOLTAGE RANGE 24 ~ 29Vdc
RATED CURRENT 20A
 

DC UPS OUTPUT

VOLTAGE RANGE 21 ~ 29Vdc
DISCHARGE CURRENT RANGE 0 ~ 20A
CHARGING CURRENT 2A
 

BATTERY

NORMAL BATTERY VOLTAGE 24Vdc ( 2 x 12Vdc in series or 1 x 24Vdc)
BATTERY TYPE Lead-acid battery
EXTERNAL BATTERY CAPACITIES 4AH ~ 135AH
 

 

 

PROTECTION

BATTERY POLARITY Protected by internal detection, No Damage, recovers automatically after fault conduction is removed
 

SHORT CIRCUIT

This protection only works when batteries are not connected, No Damage. External fuse is recommended

when batteries are connected.

OVER DISCHARGE CURRENT 21~23A,After 3 sec., unit will cut-off battery discharging by relay
BATTERY DEEP DISCHARGE Cut-off battery discharging by relay
 

 

 

 

 

FUNCTION

RELAY CONTACT RATINGS (max.) 30VDC/1A resistive load
 

DC BUS OK

Relay contact : Short when DC voltage between 21~29V(±2%), relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
 

BATTERY FAIL                                                        Note.2

Short when battery voltage falls below 22V(±2%) or battery failure is observed through the battery test function, relay contacts
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery OK : dark
 

BATTERY DISCHARGE

Relay contact : Short when battery in discharge condition, relay contacts
LED(Yellow) : light : Battery discharging ; dark : Battery is not discharging or discharging current < 1.0A
 

 

 

 

ENVIRONMENT

COOLING Free air convection
WORKING TEMP.                                                        Note.3 -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 5 ~ 95% RH non-condensing
STORAGE TEMP. -40 ~ +85℃
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 60℃)
VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE                                                        Note.4 2000 meters/OVC II
 

 

 

 

 

 

 

 

 

 

SAFETY & EMC

(Note.5)

SAFETY STANDARDS EAC TP TC 004 approved
WITHSTAND VOLTAGE IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ; Relay – Chassis : 0.5KVac
ISOLATION RESISTANCE IP/OP – Chassis, IP/OP- Relay, Relay – Chassis:>100M Ohms / 500Vdc / 25℃/ 70% RH
 

 

 

EMC EMISSION

Parameter Standard Test Level / Note
Conducted —– —–
Radiated BS EN/EN55032(CISPR32) Class B
Voltage Flicker —– —–
Harmonic Current —– —–
 

 

 

 

 

 

 

 

EMC IMMUNITY

BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter Standard Test Level / Note
 

ESD

 

BS EN/EN61000-4-2

Level 3, 8KV air ; Level 2, 4KV contact; criteria B

Level 2, 4KV air ; Level 1, 2KV contact; criteria A

Radiated BS EN/EN61000-4-3 Level 3, 10V/m ; criteria A
EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV ; criteria A
Surge BS EN/EN61000-4-5 Level 3, 0.5KV(DC input ports)
Conducted BS EN/EN61000-4-6 Level 3, 10V ; criteria A
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ; criteria A
 

OTHERS

MTBF 421.0K hrs min.       Telcordia SR-332 (Bellcore) ;        482.1K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION 40*125.2*113.5mm (W*H*D)
PACKING 0.31Kg; 20pcs/7.2Kg/1.16CUFT
 

 

 

 

 

 

NOTE

1. All parameters NOT specially mentioned are measured at normal input(24V) , rated load and 25℃ of ambient temperature.

2. Every 30 seconds, unit will test the battery.If the testing result is faulty, unit will turn on “Battery Fail” relay contact and “Red LED” indicator.

3. Derating may be needed over high ambient temperature. Please check the derating curve for more details.

4.  The ambient temperature derating of 3.5℃I1000m with fanless models and of 5℃I1000m with fan models for operating altitude higher than 2000m(6500ft).

5.The unit is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360*720mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests,please refer to “EMI testing of component power supplies.”(as available on http:IIwww.meanwell.com)

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block DiagramMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-3

Derating CurveMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-4

Buffering TimeMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-5

Mechanical SpecificationMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-6

Installation InstructionMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-7

Suggested Application

  1. Back up connection for AC interruptionMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-8
  2. Combine redundancy module (DRDN20) to back up AC interruption or failure of PSUMEAN-WELL-DUPS20-Rail-Uninterruptible-DC-UPS-Module-9
Installation Manual

Please refer to : http://www.meanwell.com/manual.html