Features

  • Support 1+1 and N+1 redundancy system
  • 2 channels input and 1 output
  • Suitable for redundancy operation of 12V/24V/48V system
  • Output current up to 40A
  • Cooling by free air convection
  • -40~+80°C ultra-wide operating temperature (>+60°C derating)
  • 55mm slim width
  • Built-in 2 channels DC OK signal and alarm relay contact
  • 3 years warranty

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

The DRDN40 series is a 40A redundancy module that can be used with a power supply to improve overall system operation reliability. Product key features include:12V/24V/48V input voltage for selection, support N+1 and 1+1 redundancy systems, built-in two rails DC input contacts and single output. The MOSFET technology implemented can reduce heat loss and reduce the voltage difference between the input and output voltages, built-in 2 channels DC OK relay contacts for monitoring output status, ultra-wide operating temperature of -40 to +80°C and narrow width (55mm).

Model EncodingMEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-1

SPECIFICATION

 

MODEL

DRDN40-
=12V, 24V, 48V
 

 

 

 

 

INPUT

NUMBER OF INPUT 2 Channels
DC NORMAL VOLTAGE 12Vdc 24Vdc 48Vdc
DC VOLTAGE RANGE 9~14Vdc 19~29Vdc 36~60Vdc
RATED CURRENT 0~40A per input       Continuous
VOLTAGE DROP (Vin-Vout)  (max.) 0.3V
PEAK CURRENT 0~60A per input        5Sec.
EFFICIENCY (Typ.) 98%
INPUT REVERSE CURRENT (max.) 1mA
INPUT REVERSE VOLTAGE (max.) 40Vdc 40Vdc 65Vdc
 

 

OUTPUT

RATED CURRENT 0~40A, Continuous
PEAK CURRENT (max.) 60A, 5Sec.
CAPACITANCE(Typ.) 320uF
STANDBY POWER LOSSES(Typ.) 1.5W
 

PROTECTION

OVERLOAD <60A,5Sec. No damage
SHORT CIRCUIT <60A,5Sec. No damage
 

 

 

FUNCTION

REDUNDANCY For 1+1 redundancy ,and support N+1 redundancy
BOTH INPUTS VOLTAGE ALARM <8.5V or >14.7V (±5%) <18V or >31V (±5%) <34.2V or >63V (±5%)
RELAY 30Vdc/1A resistive load
LED STATUS DISPLAY Green LED OK
 

 

 

 

 

ENVIRONMENT

COOLING Free air convection
WORKING TEMP.                                                       Note.2 -40 ~ +80℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 5 ~ 95% RH non-condensing
STORAGE TEMP. -40 ~ +85℃
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 60℃)
VIBRATION Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE                                                       Note.3 5000 meters/OVC II
 

 

 

 

 

 

 

 

 

SAFETY & EMC

(Note.4)

SAFETY STANDARDS IEC62368-1, UL62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ; Relay – Chassis : 0.5KVac
ISOLATION RESISTANCE IP/OP – Chassis, IP/OP- Relay, Relay – Chassis:>100M Ohms / 500Vdc / 25℃/ 70% RH
 

 

 

EMC EMISSION

Parameter Standard Test Level / Note
Conducted BS EN/EN55032(CISPR32) Class B
Radiated BS EN/EN55032(CISPR32) Class B
Voltage Flicker —– —–
Harmonic Current —– —–
 

 

 

 

 

 

 

EMC IMMUNITY

BS EN/EN55035, BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 4, 15KV air ; Level 3, 8KV contact; criteria A
Radiated BS EN/EN61000-4-3 Level 3, 10V/m ; criteria A
EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV ; criteria A
Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-Chassis ;criteria A
Conducted BS EN/EN61000-4-6 Level 3, 10V ; criteria A
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ; criteria A
 

OTHERS

MTBF 1672.9K hrs min.       Telcordia SR-332 (Bellcore) ;       499.5K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION 55*125.2*100mm (W*H*D)
PACKING 0.5Kg;20psc/11Kg/1.49CUFT
 

 

 

 

 

NOTE

1. All parameters NOT specially mentioned are measured at normal input(12V/24V/48V) , rated load and 25℃ of ambient temperature.

2. Derating may be needed over high ambient temperature. Please check the derating curve for more details.

3.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EM testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-2

DC OK Relay Contact

Contact Ratings (max.) 30V/1A resistive load
Contact Close(DC OK) PSU turns on
Contact Open(DC Fail) PSU turns off / over or under input voltage

Derating Curve

MEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-3

Output Derating VS Input Voltage

MEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-4

Typical Application Notes

  1. 1+1 Redundancy:
    Using 1 more PSU as the redundant unitMEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-5
  2. 1+N Redundancy:
    Using more PSUs as the redundant units to increase the reliabilityMEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-6
  3. Single Use:
    Connecting only one PSU to one DRDN40 to reduce the stress of the and hence increase the reliability MOSFET

MEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-7

Mechanical Specification

MEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-8

Installation Instruction

MEAN-WELL-DRDN40-DIN-Rail-Type-Redundancy-Module-fig-9

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.

Installation Manual
Please refer to: http://www.meanwell.com/manual.html

Documents / Resources

MEAN WELL DRDN40 DIN Rail Type Redundancy Module [pdf] Owner's Manual
DRDN40 DIN Rail Type Redundancy Module, DRDN40, DIN Rail Type Redundancy Module, Type Redundancy Module, Redundancy Module