MEAN WELL DRDN40 DIN Rail Type Redundancy Module
Features
- Support 1+1 and N+1 redundancy system
- 2 channels input and 1 output
- Suitable for redundancy operation of 12V/24V/48V system
- Output current up to 40A
- Cooling by free air convection
- -40~+80°C ultra-wide operating temperature (>+60°C derating)
- 55mm slim width
- Built-in 2 channels DC OK signal and alarm relay contact
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
The DRDN40 series is a 40A redundancy module that can be used with a power supply to improve overall system operation reliability. Product key features include:12V/24V/48V input voltage for selection, support N+1 and 1+1 redundancy systems, built-in two rails DC input contacts and single output. The MOSFET technology implemented can reduce heat loss and reduce the voltage difference between the input and output voltages, built-in 2 channels DC OK relay contacts for monitoring output status, ultra-wide operating temperature of -40 to +80°C and narrow width (55mm).
Model Encoding
SPECIFICATION
MODEL |
DRDN40- | ||||
=12V, 24V, 48V | |||||
INPUT |
NUMBER OF INPUT | 2 Channels | |||
DC NORMAL VOLTAGE | 12Vdc | 24Vdc | 48Vdc | ||
DC VOLTAGE RANGE | 9~14Vdc | 19~29Vdc | 36~60Vdc | ||
RATED CURRENT | 0~40A per input Continuous | ||||
VOLTAGE DROP (Vin-Vout) (max.) | 0.3V | ||||
PEAK CURRENT | 0~60A per input 5Sec. | ||||
EFFICIENCY (Typ.) | 98% | ||||
INPUT REVERSE CURRENT (max.) | 1mA | ||||
INPUT REVERSE VOLTAGE (max.) | 40Vdc | 40Vdc | 65Vdc | ||
OUTPUT |
RATED CURRENT | 0~40A, Continuous | |||
PEAK CURRENT (max.) | 60A, 5Sec. | ||||
CAPACITANCE(Typ.) | 320uF | ||||
STANDBY POWER LOSSES(Typ.) | 1.5W | ||||
PROTECTION |
OVERLOAD | <60A,5Sec. No damage | |||
SHORT CIRCUIT | <60A,5Sec. No damage | ||||
FUNCTION |
REDUNDANCY | For 1+1 redundancy ,and support N+1 redundancy | |||
BOTH INPUTS VOLTAGE ALARM | <8.5V or >14.7V (±5%) | <18V or >31V (±5%) | <34.2V or >63V (±5%) | ||
RELAY | 30Vdc/1A resistive load | ||||
LED STATUS DISPLAY | Green LED OK | ||||
ENVIRONMENT |
COOLING | Free air convection | |||
WORKING TEMP. Note.2 | -40 ~ +80℃ (Refer to “Derating Curve”) | ||||
WORKING HUMIDITY | 5 ~ 95% RH non-condensing | ||||
STORAGE TEMP. | -40 ~ +85℃ | ||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 60℃) | ||||
VIBRATION | Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373 | ||||
OPERATING ALTITUDE Note.3 | 5000 meters/OVC II | ||||
SAFETY & EMC (Note.4) |
SAFETY STANDARDS | IEC62368-1, UL62368-1, EAC TP TC 004 approved | |||
WITHSTAND VOLTAGE | IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ; Relay – Chassis : 0.5KVac | ||||
ISOLATION RESISTANCE | IP/OP – Chassis, IP/OP- Relay, Relay – Chassis:>100M Ohms / 500Vdc / 25℃/ 70% RH | ||||
EMC EMISSION |
Parameter | Standard | Test Level / Note | ||
Conducted | BS EN/EN55032(CISPR32) | Class B | |||
Radiated | BS EN/EN55032(CISPR32) | Class B | |||
Voltage Flicker | —– | —– | |||
Harmonic Current | —– | —– | |||
EMC IMMUNITY |
BS EN/EN55035, BS EN/EN61000-6-2(BS EN/EN50082-2) | ||||
Parameter | Standard | Test Level / Note | |||
ESD | BS EN/EN61000-4-2 | Level 4, 15KV air ; Level 3, 8KV contact; criteria A | |||
Radiated | BS EN/EN61000-4-3 | Level 3, 10V/m ; criteria A | |||
EFT / Burst | BS EN/EN61000-4-4 | Level 3, 2KV ; criteria A | |||
Surge | BS EN/EN61000-4-5 | Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-Chassis ;criteria A | |||
Conducted | BS EN/EN61000-4-6 | Level 3, 10V ; criteria A | |||
Magnetic Field | BS EN/EN61000-4-8 | Level 4, 30A/m ; criteria A | |||
OTHERS |
MTBF | 1672.9K hrs min. Telcordia SR-332 (Bellcore) ; 499.5K hrs min. MIL-HDBK-217F (25℃) | |||
DIMENSION | 55*125.2*100mm (W*H*D) | ||||
PACKING | 0.5Kg;20psc/11Kg/1.49CUFT | ||||
NOTE |
1. All parameters NOT specially mentioned are measured at normal input(12V/24V/48V) , rated load and 25℃ of ambient temperature.
2. Derating may be needed over high ambient temperature. Please check the derating curve for more details. 3. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft). 4. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EM testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf ) ※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Block Diagram
DC OK Relay Contact
Contact Ratings (max.) | 30V/1A resistive load |
Contact Close(DC OK) | PSU turns on |
Contact Open(DC Fail) | PSU turns off / over or under input voltage |
Derating Curve
Output Derating VS Input Voltage
Typical Application Notes
- 1+1 Redundancy:
Using 1 more PSU as the redundant unit - 1+N Redundancy:
Using more PSUs as the redundant units to increase the reliability - Single Use:
Connecting only one PSU to one DRDN40 to reduce the stress of the and hence increase the reliability MOSFET
Mechanical Specification
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
Installation Manual
Please refer to: http://www.meanwell.com/manual.html
Documents / Resources
![]() |
MEAN WELL DRDN40 DIN Rail Type Redundancy Module [pdf] Owner's Manual DRDN40 DIN Rail Type Redundancy Module, DRDN40, DIN Rail Type Redundancy Module, Type Redundancy Module, Redundancy Module |