MEAN WELL DRDN20 DIN Rail Type Redundancy Module 

MEAN WELL DRDN20 DIN Rail Type Redundancy Module 

Features

  • Support 1 + 1 and N+ 1 redundancy system
  • 2 channels input and 1 output
  • Suitable for red undance operation of 12V/24V/48V system
  • Output current up to 20A
  • Cooling by free air convection
  • -40~+80°C ultra-wide operating temperature ( >+60°C derating)
  • 32mm slim width
  • Built-in 2 channels DC OK signal and alarm relay contact
  • Installed on DIN Rail TS35/7.5 or 15
  • 3 years warranty

Applications

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

The DRDN20 series is a 20A redundancy module that can be used with a power supply to improve overall system operation reliability. Product key features include:12V/24V/48V input voltage for selection, support N+1 and 1 +1 redundancy systems, built-in two rails DC input contacts and single output. The MOSFET technology implemented can reduce heat loss and reduce the voltage difference between the input and output voltages, built-in 2 channels DC OK relay contacts for monitoring output status, ultra-wide operating temperature of -40 to +80°C and narrow width (32mm).

Model Encoding

Model Encoding

SPECIFICATION

MODELORON20-▯
▯ =12V, 24V. 48V
INPUTNUMBER OF INPUT2 Channels
DC NORMAL VOLTAGE12Vdc24Vdc48Vdc
DC VOLTAGE RANGE9-14Vdc19- 29Vdc36-60Vdc
RATED CURRENT0-20A per input Continuous
VOLTAGE DROP (Vin-Vou)t (max.)0.25V
PEAK CURRENT0-30A per input       SSec.
EFFICIENCY (Typ.)98%
INPUT REVERSE CURRENT (max.)1mA
INPUT REVERSE VOLTAGE (max.)40Vdc 40Vdc40Vdc65Vdc
OUTPUTRATED CURRENT0-20A, Continuous
PEAK CURRENT (max.)30A, 5Sec.
CAPACITANCE (Typ.)320 uF
STANDBY POWER LOSSES(Typ.)1.5W
PROTECTIONOVERLOAD< 30A,5Sec. No damage
SHORT CIRCUIT< 30A,5Sec. No damage
FUNCTIONREDUNDANCYFor 1+1 redundancy, and support N+1 redundancy
BOTH INPUTS VOLTAGE ALARM<8.SVor >14.7V(±  5%)<18V or >31V (± 5%)<34.2Vor >63V ( ± 5%1
RELAY30Vdc/1A resistive load
LEO STATUS DISPLAYGreen LED OK
ENVIRONMENTCOOLINGFree air connection
WORKING TEMP.Note.2-40 – +ado’s (Referto’ Derating Curve”)
WORKING HUMIDITY5- 95%RH non-condensing
STORAGE TEMP.-40 – +85’C
TEMP. COEFFICIENT± 0 03%/’C 10 – 60′ Cl
VIBRATIONComponent:10- 500Hz, 5G 10 min./cycle 6,0min.echelon, Y, Zaxes; Mounting: Compliance to IEC 61373
OPERATING ALTITUDENote.35000 meters/OVC11
SAFETY & EMC (Note. 4)SAFETY STANDARDSIEC 6236-81, UL 62368-,1EAC TP TC 004 approved
WITHSTAND VOLTAGEIP/OP· Chassis: 0.5KVac; IP/OP-Relay: 0.5KVac ; Relay· Chassis: O.SKVac
ISOLATION RESISTANCEIP/OP· Chassis, IP/OP-Relay, Relay· Chassis:>10M0Ohms/ 500Vdc/ 25″C/ 70% RH
EMC EMISSIONParameterStandardTest Level Note
ConductedBS EN/EN55032(CISPR 32Class B
RadiatedBS EN/EN55032t(SCPR32Class B
Voltage Flicker—–—–
Harmonic Current-··—–
EMC IMMUNITYBS EN/EN 55035, BS EN/EN 61000-6-2(BS EN/EN 50082-2)
ParameterStandardTest Level  Note
ESDBS EN/EN6100-4-2Level 4,15KV air; Level 3, 8KV contact; criteria A
RadiatedBS EN/EN 6100-4-3Level3, 10V/m; criteria A
EFT/ BurstBS EN/EN 6100-4-4Level3, 2KV; criteria A
SurgeBS EN/EN6100-4-5Level 3 1KV/line line; level 3 2KV/line-
Line Chassis; criteria A
ConductedBS EN/EN 6100-4-6Level 3, 10V; criteria A
Magnetic FieldBS EN/EN6100-4-8Level 4, 30A/m; criteria A
OTHERSMTBF1836.0Khrsmin. Telcordia SR-332 (Bellcore) ;   482.1K hrsmin. MIL-HDBK-217F(25’C)
DIMENSION32’125.21′ 02mm(W’H’ D)
PACKING0.35Kg;28ps/1c0.8Kg/1.24 CUT
NOTE
  1. All parameters NOT specially mentioned are measured at normal input(12V/24V/48V), rated load and 25″C of ambient temperature.
  2. Operating may be needed over high ambient temperature. Please check the derating curve for more details.
  3. The ambient temperature derating of 3.•s cn  ooom with fanless models and of 5’C/1000m with fan models for operating altitude higher than 2000m(6500f)t.
  4. The power supply is considered as an independent nit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/POF/EMl_slatement_en.pdf)
    ※ Product liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Block Diagram

DC OK Rela Contact

Contact Ratinos (max.)30V/1Aresistive load
Contact Close (DCOK)PSU turns on
Contact Open (DC Fail)PSU turns off/ over or under input voltage

Derating Curve

Derating Curve

Output Derating VS Input Voltage

Output Derating VS Input Voltage

Typical Application Notes

  1. 1+1 Redundancy:
    Using 1 more PSU as the redundant unit
    Typical Application Notes
  2. 1+N Redundancy:
    Using more PS Us as the redundant units to increase the reliability
    Typical Application Notes
  3. Single Use:
    Connecting only one PSU to one DRDN20 to reduce the stress of the MOSFET and hence increase the reliability
    Typical Application Notes

Mechanical Specification

Mechanical Specification

Terminal Pin No. Assignment (TB 1,TB2)

CaseNo. 221 D Unit: mm

Pin No.Assignment
1,2Alarm1 DC OK
3,4Alarm2 DC OK
5FG
6,7DC output +Vout
8DC output •Vout

Terminal Pin No. Assignment (TB3)

PinNo.Assignment
1DC input +Vint
2DC input -Vinl
3DC input +Vln2
4DC input -Vin2

Installation Instruction

Installation Instruction

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.

ADMISSIBLE DIN-RAIL:TS35n .5 OR TS35/15 (For retc, once only. Not included with unit.)

Installation Manual

Please refer to: http://www.meanwell.com/manual.html

Customer Support

Symbol

User Manual

QR Code

Video

QR Code

Logo

Documents / Resources

MEAN WELL DRDN20 DIN Rail Type Redundancy Module [pdf] Owner's Manual
DRDN20, DRDN20 DIN Rail Type Redundancy Module, DIN Rail Type Redundancy Module, Rail Type Redundancy Module, Redundancy Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *