ModMAG® Electromagnetic Flow Meters

M-Series® | B-MAG Electromagnetic Flow Meters

M2000 Modbus RTU Communication Daughterboard

OVERVIEW

The Modbus RTU Communication daughterboard expands the connectivity of the M2000 flow meter by facilitating communication over RS485 using the Modbus RTU protocol. The RS485 allows for greater communication distances than RS232 and provides for multi-point networking.

External Connections (Pins 31 – 39)

A diagram shows a horizontal row of 9 rectangular blocks, labeled sequentially from left to right: 39, 38, 37, 36, 35, 34, 33, 32, 31. The title above this row is 'External Connections (Pins 31 – 39)'.

J4 RS485 / RS232 Mode Selection Jumper

A diagram illustrates jumper J4, labeled 'RS485 / RS232 Mode Selection Jumper'. It shows three pins. Pin 1 is connected to RS485. Pin 2 is connected to RS232. The jumper selects between these two modes.

J3 120 Ω Termination Jumper

A diagram illustrates jumper J3, labeled '120 Ω Termination Jumper'. It shows three pins. Pin 1 is connected to a 120 Ω termination. The jumper can be set for '120 Ω' or 'No Termination'.

A 11-pin plug is shown, labeled: "Connect to 'COMMUNICATION' plug on Amplifier Board".

Pinout Description

Pin No.Pin NameDescription
31Analog Output0...20 mA, 0...10 mA, 2...10 mA, 4...20 mA
32COMCommon ground connection
33RS232 RXReceive input for RS232
34RS232 TXTransient output for RS232
35COMCommon ground connection
36RS485 (-)Inverting signal for RS485
37RS485 (+)Non-inverting signal for RS485
38RS232/485 ShieldShield input for RS232 or RS485
39ChassisConnection for coupling shield to chassis

INSTALLING THE DAUGHTERBOARD

  1. Use the provided self-adhesive tape to secure the foam pad near the 11-pin COMMUNICATION connector.
  2. Remove the board support screw near the 11-pin COMMUNICATION connector to install the green chassis connection wire (with an eye washer). Connect the other end of the chassis connection wire to pin 39.
  3. Select operation mode RS485 or RS232 for the daughterboard using J4.
  4. For RS485 mode only: Select the termination (that is, 120 Ω or No termination) using J3.

? NOTE: 120 Ω termination is typically required when the meter is the first or last device in the communication link.

? NOTE: It is assumed all signal biasing is accomplished at the Modbus RTU master node. For biasing calculations, receiver input impedance is 96 kΩ or 1/8 unit loads.

⚠️ CAUTION: DISCONNECT THE INPUT POWER BEFORE ACCESSING THE EQUIPMENT.

  1. Turn off the meter and insert the daughterboard into the keyed 11-pin COMMUNICATION connector on the amplifier.

CONFIGURING PORT B MODBUS RTU

The Modbus RTU Communication Daughterboard is a slave device that communicates over Port B. The following Port B settings are configurable from the meter's menu manager.

SettingOptions
Port address1 to 247
Ext. port addressNot applicable for Modbus RTU daughterboard
Baud rate9600 (default), 19200, 38400
Data bits5, 7, 8 (default)
ParityNone, Even (default), Odd
Stop bits1 (default), 2

To change the configuration of Port B to match your system requirements:

  1. Turn on the meter.
  2. Navigate to Main Menu > Communication > Port B Settings.
  3. Verify that the settings are an appropriate match for the application. If not, change the settings as necessary.

Please refer to the M2000 Modbus Memory Map Application Brief for accessible registers.

Models: M2000, Modbus RTU Communication Daughterboard, RTU Communication Daughterboard, Communication Daughterboard, M2000, Daughterboard

PDF preview unavailable. Download the PDF instead.

ModMAG-M2000-Modbus-RTU-Communication-Daughterboard Adobe PDF Library 15.0 Adobe InDesign 16.3 (Windows)

Related Documents

Preview M5000 Firmware Upgrade Guide for Badger Meter Electromagnetic Flow Meters
Step-by-step instructions for upgrading the firmware on Badger Meter M5000 Electromagnetic Flow Meters using RS232 or IrDA connections. Includes preparation steps and troubleshooting notes.
Preview Badger Meter M5000 Data Logging Electromagnetic Flow Meters User Manual
User manual for the Badger Meter M5000 Electromagnetic Flow Meter, detailing data logging features, firmware compatibility, event recording, and software installation for extracting logged data via RS232 or IrDA connections.
Preview Cox Precision Turbine Flow Meters User Manual | Badger Meter
Comprehensive user manual for Cox Precision Turbine Flow Meters by Badger Meter, covering operation, installation, maintenance, troubleshooting, specifications, and calibration. Includes detailed diagrams and part information.
Preview Badger Meter M5000: Converting a Standard Mount to a Remote Mount
Step-by-step guide for converting a Badger Meter ModMAG M5000 electromagnetic flow meter from a standard mount to a remote mount using the Remote Junction Box Kit.
Preview Badger Meter ORION Cellular Endpoint Installation and Status Guide
Comprehensive guide for installing, removing, and managing Badger Meter ORION Cellular Endpoints, including the HR-E Integral Assembly, inline connectors, and the BEACON Endpoint Status Tool. Covers connection procedures, status monitoring, and troubleshooting.
Preview Badger Meter ORION Water Endpoints Installation Manual
Comprehensive installation manual for Badger Meter ORION Water Endpoints, covering various models including Cellular, Fixed Network, Migratable, and Classic endpoints. Details connection methods, installation guidelines for different environments (pit, vault, remote), and troubleshooting.
Preview Badger Meter Recordall Industrial Meters: Nutating Disc Meter Specifications and Operation
Detailed product data sheet for Badger Meter's Recordall Industrial Meters, covering nutating disc meters in bronze and thermoplastic. Includes specifications, operation principles, materials of construction, and performance data.
Preview ORION® Water Endpoints Installation Manual
Comprehensive installation manual for Badger Meter's ORION Water Endpoints, covering Cellular, Mobile M, ME, SE, and Classic models. Includes setup, activation, and installation kit details.