R. STAHL CMP-32A2FRC Cable Gland

Art. Nr. 243629

Product Description

The CMP-32A2FRC metal cable glands from the A2FRC series are designed for all types of unarmored cables and cables with wire braid armor, intended for installation in flexible or rigid conduits. A freely rotating connection piece simplifies installation. The cable glands are designed to prevent cold flow.

Key features include:

Explosion Protection Data

Feature Specification
Ex-Execution Ex eb & Ex db & Ex nR & Ex ta
Area of Application (Zones) 1, 2, 20, 21, 22
IECEx Certification Gas IECEX CML 18.0179X
IECEx Gas Explosion Protection Ex db eb IIC Gb
IECEx Certification Dust IECEX CML 18.0179X
IECEx Dust Explosion Protection Ex ta IIIC Da
IECEx Certification Impact Resistance IECEX CML 18.0179X
IECEx Certification Shroud Safety IECEX CML 18.0179X
IECEx Shroud Safety Ex nR IIC Gc
ATEX Certification Gas CML18ATEX1321X
ATEX Certification Gas 2 CML18ATEX4313X
ATEX Gas Explosion Protection II 2 G Ex db eb IIC Gb
ATEX Certification Dust CML18ATEX1321X
ATEX Dust Explosion Protection II 1 D Ex ta IIIC Da
ATEX Certification Impact Resistance CML18ATEX1321X
ATEX Certification Shroud Safety CML18ATEX1321X
ATEX Shroud Safety II 3G Ex nR IIC Gc
Note Product certifications and certificates can be downloaded from the manufacturer's homepage (www.cmp-products.com).

Mechanical Data

Feature Specification
IP Protection (IEC 60079) IP66
IP Protection UL IP66
Seal Material SOLO LSF
Silicone-Free Yes
Halogen-Free Yes
Clamping Range 17 – 26.3 mm
Armor Type 2 Shielded braided cable
Clamping Range 17 ... 26.3 mm
Standard BS 6121, IEC/EN 62444
Overall Length 45.1 mm
Wrench Size 41 mm
Thread Size M32
Thread Length 15 mm
Thread Pitch 1.5
Thread Standard Metric
Gland Size 32
Inner Jacket 17 ... 26.3 mm
Inner Conduit Thread M32
Protrusion Length 55.5 mm
Impact Resistance (IEC 60079) 7 J
Impact Resistance 20 J
PVC Bushing PVC10
Weight 240 g
Weight 0.53 lb

Dimensional Drawing (all dimensions in mm [inches]) – Subject to change

A = Inner jacket

C = Thread size

D = Flat-to-flat dimension

D = Wrench size

E = Thread length

F = Protrusion length

G = Inner conduit thread

Changes to technical data, dimensions, weights, constructions, and delivery options are reserved. Illustrations are non-binding.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-prensaestopas-cmp-32a2frc-243629-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL CMP-32A2FRC Cable Gland: Technical Specifications and ATEX/IECEx Certifications
Detailed technical specifications, ATEX, IECEx, and CSA certifications for the R. STAHL CMP-32A2FRC cable gland, designed for armored and unarmored cables in hazardous environments.
Preview CMP-32A2FRC Cable Gland Technical Specifications | R. STAHL
Detailed technical specifications for the R. STAHL CMP-32A2FRC cable gland, including ATEX and IECEx certifications, mechanical data, and application zones.
Preview CMP-40A2FRC Cable Gland - Technical Specifications and Features
Detailed technical specifications, features, and application information for the CMP-40A2FRC cable gland by R. STAHL, including explosion protection, mechanical characteristics, and certifications.
Preview CMP-63sA2FRC Cable Gland - Technical Specifications and Installation
Detailed technical specifications and installation information for the R. STAHL CMP-63sA2FRC cable gland, including explosion protection data, mechanical dimensions, and certifications.
Preview CMP-63A2FRC Cable Gland: Technical Specifications and Installation
Detailed technical specifications and installation information for the R. STAHL CMP-63A2FRC cable gland, including explosion protection data, mechanical properties, and certifications.
Preview R. STAHL CMP-20sA2FRC Industrial Cable Gland - Technical Specifications
Detailed technical specifications for the R. STAHL CMP-20sA2FRC industrial cable gland, including explosion protection, mechanical data, and certifications.
Preview CMP-50A2FRC Cable Gland - Technical Specifications and Installation
Detailed technical specifications and installation information for the R. STAHL CMP-50A2FRC cable gland, including explosion protection, mechanical data, and certifications.
Preview R. STAHL CMP-25A2FRC Cable Gland - Technical Specifications and Installation
Detailed technical specifications and installation information for the R. STAHL CMP-25A2FRC cable gland, including explosion protection, mechanical data, and certifications.