R. STAHL Remote I/O IS1+ CPU Module for Zone 1
Article No.: 279953
Model: 9442/32-10-00
Key Features
- Supports PROFIBUS DP, PROFINET, Modbus TCP+RTU, and EtherNet/IP™; includes HART transmission and redundancy.
- RS485-IS interface (max. 1.5 Mbit/s) and Ethernet 100BASE-TX (max. 100 Mbit/s) interfaces.
- Extensive diagnostics based on NE 107.
- Supports FDT/DTM, OPC UA, and web servers for integration in asset management systems.
- Extended ambient temperature range from -40 to +75 °C.
Overview
The 9442/32 CPU module serves as a gateway between the IS1+ Remote I/O system and the automation system. It supports various communication protocols that can be configured by the user. The module facilitates the transmission of process values, diagnostics, parameterization, and configuration data. Communication with I/O modules is achieved using the 9496 socket and the 9494 BusRail. Integration into control systems and plant asset management tools is enabled through standards like GSD, EDS, web servers, and FDT/DTM.
Technical Data
Explosion Protection
- Application range (zones): 1, 2
- Ex interface zone: 1, 2
- IECEx gas certificate: IECEX PTB 22.0001 X
- IECEx gas explosion protection: Ex ib [ia Ga] [ib Gb] IIC T4 Gb
- ATEX gas certificate: PTB 21 ATEX 2004 X
- ATEX gas explosion protection: II 2 (1) (2) G Ex ib [ia Ga] [ib Gb] IIC T4 Gb
Certificates
- Ship approval: BVIS, EU RO MR (DNV), KR, LR
- Declaration of conformity: ATEX (EUK)
- Installation: Zone 1
Electrical Data
- Protocol setting: Via rotary switch S1
- Redundancy: Full redundancy, Line redundancy, Supply redundancy
- Type RS-485 connector: Sub-D connector
- No. of pins RS-485 conn.: 9
- RS485 interface protocol: As per PROFIBUS specification (RS 485-IS), Profibus DP V1 HART, Profibus DP V1, Modbus RTU
- Address range RS485: 1 - 127
- Copper RS485 transmission length/rate: 1200 m at 9.6 to 93.75 kbit/s, 1000 m at 187.5 kbit/s, 400 m at 500 kbit/s, 200 m at 1.5 Mbit/s, 100 m at 12 Mbit/s
- Transfer length/rate FO RS485: Approx. 2000 m at 1.5 Mbit/s
- Ethernet interface connection: 2 x RJ45 (EIA/TIA 568B) socket
- USB version: USB 2.0 IS
- Interface RJ45: Unmanaged switch function, 100BASE-TX-IS
- RJ45 protocols: MODBUS TCP, EtherNet/IP™, PROFINET
- Transfer rate RJ45: Max. 10/100 Mbit/s, Auto-negotiation
- Transfer length copper RJ45: 100 m
- Transfer length FO RJ45: 2000 m multi mode, 30 km single mode
- USB interface: Type A socket
- USB address setting: Identical to RS485 address
- Max. USB transfer rate: 480 (unece.unit.MBI)
- Max. USB current: 250 mA
- USB protocols: Service bus
Auxiliary Power
- Power supply: via base 9496 and PM 9445/32
- Max. current consumption: 300 mA
- Max. power dissipation: 5 W
Galvanic Isolation
- Galv.sep. CPU to CPU (red.)AC: 1500 V
- Galv.sep. AUX PWR to CPU AC: 1500 V
Device Specific Data
Software
- IS1 device DTM: IS1 Wizard
- Diagnostic/parameterisation functions: Web server
- Diagnostic/parameterisation connectable software packages: IS Wizard (via USB ServiceBus), R. STAHL DTM devices with fdt frames, AMS from Emerson Process Management, PDM from Siemens, PRM and Fieldmate from Yokogawa, FieldCare from Endress+Hauser, FDM from Honeywell
Retrievable parameters
- Hardware revision: Manual
- Manufacturer: Serial number
- Software revision: Type
- LED module requires maintenance: LED "M/S", blue
- LED operating conditions: LED "PWR", green
- LED data traffic automatic system: LED "AS EXCH", green
- LED configuration: LED "CFG ERR", red
- LED data traffic RS485: LED "RXTX X1 RS-485", green
- LED port connection RJ45 port 1: LED "LINK X2 LAN P1", yellow
- LED data traffic RJ45 port 1: LED "RXTX X2 LAN P1", green
- LED port connection RJ45 port 2: LED "LINK X2 LAN P2", yellow
- LED data traffic RJ45 port 2: LED "RXTX X2 LAN P2", green
- LED USB data traffic: LED "RXTX X3 USB", green
Diagnostics
- LED group error: LED "ERR", red
- LED status: LED "STATUS", yellow
Ambient Conditions
- Ambient temperature: -40 °C to 65 °C (without mounting plate); -40 °C to 70 °C (with 3 mm sheet steel mounting plate); -40 °C to 75 °C (with 6 mm aluminium mounting plate)
- Ambient temperature (°F): -40 °F to 149 °F (without mounting plate); -40 °F to 158 °F (with 3 mm sheet steel mounting plate); -40 °F to 167 °F (w. 6 mm alum. mounting plate)
- Storage temperature: -40 °C to 80 °C
- Storage temperature (°F): -40 °F to 176 °F
- Max. operating altitude: 2000 m
- Max. relative humidity: 95%
- max. relative humidity note: without condensation
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP30
- Module enclosure: Polyamide 6GF, Seawater-resistant aluminium
- Fire resistance (UL 94): V2
- Pollutant class: Corresponds to G3
- Width: 32 mm (1.26 in)
- Depth: 123 mm (4.843 in)
- Length: 152 mm (5.98 in)
- Weight: 1 kg (2.2 lb)
Mounting / Installation
- Mounting orientation: Horizontal, Vertical
Accessories
Accessory | Art. No. |
---|---|
Ethernet media converter (Multi-mode media converter for installation in Zone 1, for fieldbuses (PROFIBUS DP, Modbus TCP) via fibre optic cables in Zone 1) | 294420 |
Ethernet media converter (Single-mode media converter for installation in Zone 1, for fieldbuses (PROFIBUS DP, Modbus TCP) via fibre optic cables in Zone 1) | 294451 |
Sub-D plug, RS-485 IS, angled (9-pin for connecting fieldbus or ServiceBus to CPU & power module Series 9440/22, 9185 fieldbus isolating repeater and 9786/12-11 media converter) | 162693 |
Sub-D plug, RS-485 IS, angled (9-pin for connecting 9185 fieldbus isolating repeater and 9786/12-11 media converter) | 201805 |
IS1 DTM devices Series 9499/DTM (Parameterisation and configuration of the IS1+ system, Communication with HART-capable field devices) | 251237 (30 HART devices), 251239 (300 HART devices), 251240 (unlimited HART devices) |
IS1 PCS7 APL field device library (Simple integration of IS1+ systems in SIEMENS PCS7) | N/A (Information from Siemens) |
AOI tool (Simple integration of IS1+ systems in Rockwell ControlLogix and CompactLogix via EtherNet/IP and AOI) | N/A (Download from r-stahl.com) |
RS485 media converter (Media converter for installation in Zone 1, for fieldbuses (PROFIBUS DP, Modbus RTU) using optical intrinsically safe "Ex op is" fibre optic in Zone 1) | 308562 |
RS485 media converter (Media converter for installation in Zone 2, for fieldbuses (PROFIBUS DP, Modbus RTU) using optical intrinsically safe "Ex op is" fibre optic in Zone 1) | 308563 |
USB RS485 converter (USB/RS485-IS converter for installation in Zone 2) | 295356 |
USB RS485 converter (USB-IS/RS485-IS converter for installation in Zone 1) | 285849 |
Mounting / Installation
Module fuse
Torx T20 screws
Dimensional Drawings
Detailed dimensional drawings are provided, showing the module's dimensions and how it connects with various sockets. These are subject to alterations.
Note: R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.