Friedrich Universal Heat Pump Extended Capacity Charts

This document provides extended capacity charts and performance data for Friedrich Universal Heat Pumps, covering various outdoor condenser and air handler unit combinations. It details cooling and heating performance across a range of operating conditions, including different airflow rates, indoor dry bulb (IDB) temperatures, and indoor wet bulb (IWB) temperatures.

Outdoor Condenser and Air Handler Unit Compatibility

Outdoor CondenserAir Handler Unit
WFPU17Y243DWFH24Y193D
WFPU17Y363DWFH36Y193D
WFPU17Y483DWFH48Y223D
WFPU17Y603DWFH60Y223D

Capacity Characteristic Charts

The following charts detail the characteristics of outdoor unit capacity corresponding to the operating ambient temperature of the outdoor unit. Conditions include:

Note: Capacity loss due to white frost and defrost operation is not included.

Remarks:

Piping Length Correction Factor

The correction factor is based on the equivalent piping length in meters (EL) and the height difference between outdoor and indoor units in meters (H).

H: Height difference between indoor unit and outdoor unit (m).

L: Actual one-way piping length between indoor unit and outdoor unit (m).

EL: Equivalent one-way piping length between indoor unit and outdoor unit (m).

90° Elbow Correction Factor

Gas Diameter (mm/inch)9.52 (3/8')12.7 (1/2')15.88 (5/8')19.05 (3/4')22.22 (7/8')
90° Elbow0.150.20.250.350.40

Cooling Correction Factors by Equivalent Piping Length (EL)

EL[ft.(m)] Model25(7.6)38(10)50(15)66(20)82(25)100(30)115(35)131(40)
24K1.000.990.970.950.930.91--
36K1.000.940.920.900.880.840.80-
48K/60K1.000.980.960.930.900.880.850.83

Heating Correction Factors by Equivalent Piping Length (EL)

EL[ft.(m)] Model25(7.6)38(10)50(15)66(20)82(25)100(30)115(35)131(40)
24K1.000.990.990.980.970.96--
36K1.000.980.950.930.910.880.86-
48K/60K1.000.980.960.940.920.900.890.88

Height Difference Correction Factor

Height difference16ft (5m)33ft (10m)108ft (30m)
Factor0.010.020.025

To ensure correct unit selection, consider the farthest indoor unit.

NOTE:

  1. Above data assumes the height difference between indoor unit and outdoor unit is 0m.
  2. To minimize length of connection pipes for optimal performance, if the outdoor unit is installed higher or lower than the indoor unit, apply height correction factor additionally to length correction factor. If the outdoor unit is higher, apply correction to cooling capacity; if lower, apply to heating capacity.

Performance Data Tables

The following tables provide detailed performance data for various Friedrich Universal Heat Pump models under different operating conditions. Data includes Total Capacity (TC), Sensible/Total Capacity Ratio (S/T), and Power Input (kW) for both cooling and heating operations.

(Detailed tables for 24K, 36K, 48K, and 60K outdoor units are presented here, covering various airflow rates and temperature conditions.)

Correction Factors According to Defrosting Operation

The heating capacity data excludes defrosting operation periods. Heating capacity is corrected using the following formula:

Corrected heating capacity = Defrost correction factor × unit capacity

Defrost Correction Factor by Outdoor Temperature

Outdoor temperature [°F(°C)DB]5(-15)14(-10)23(-5)32(0)44.6(7)50(10)59(15)
Correction factor (humidity rate 85% RH)0.950.950.930.851.01.01.0

(A diagram illustrates the reduction in capacity due to white frost during a defrost cycle.)

NOTE: The correction factor is not valid for special conditions like snowfall or transitional periods.

PDF preview unavailable. Download the PDF instead.

Breeze Select Universal Heat Pump Condenser Extended Capacity Charts Adobe Acrobat (64-bit) 25.1.20531 Adobe Acrobat (64-bit) 25.1.20531

Related Documents

Preview Friedrich Breeze Series Inverter Heat Pumps for Efficient Home Comfort
Discover the Friedrich Breeze Series inverter-driven universal ducted heat pumps, offering precise temperature control, significant energy savings, and quiet operation for year-round home comfort. Learn about Premier and Select models, universal compatibility, and advanced features.
Preview Friedrich Breeze Universal Heat Pumps: Specifications and Dimensions
Comprehensive submittal sheet for Friedrich Breeze Universal Heat Pumps, detailing features, specifications, and dimensions for 2-ton to 5-ton models, including indoor and outdoor units.
Preview Friedrich Breeze Universal Heat Pump: Installation and Wiring Diagrams
Comprehensive guide to the Friedrich Breeze Universal Heat Pump, covering installation, wiring diagrams for various configurations, and operational parameters. Learn about its features, energy savings, and low-temperature performance.
Preview Friedrich Breeze Select 2025 R-454B Heat Pump Quick Start Guide
A quick start guide for Friedrich Breeze Select 2025 R-454B Universal Heat Pump models, covering installation, operation, and troubleshooting.
Preview Friedrich VRP Variable Refrigerant Packaged Heat Pump Installation & Operation Manual
This manual provides comprehensive installation and operation guidelines for the Friedrich VRP Variable Refrigerant Packaged Heat Pump, model VRP36K. It covers safety precautions, general specifications, installation procedures, electrical data, air flow data, clearances, and warranty information.
Preview Friedrich VRP Variable Refrigerant Packaged Heat Pump Product Profile
Discover the Friedrich VRP, an innovative and intelligent Variable Refrigerant Packaged Heat Pump system. It provides superior cooling, efficient heating, advanced humidity control, and optional fresh air integration, ensuring optimal comfort and energy savings with its Precision Inverter technology.
Preview Friedrich VRP Variable Refrigerant Packaged Heat Pump Technical Specifications and Submittal
Comprehensive technical specifications, unit features, dimensional data, and performance metrics for the Friedrich VRP series of Variable Refrigerant Packaged Heat Pumps, emphasizing Precision Inverter Technology and unitary package design.
Preview Friedrich Ductless Floating Air Pro X Single Zone Service Manual
Comprehensive service manual for Friedrich Ductless Floating Air Pro X Single Zone air conditioning units (9-18k BTU) using R-454B refrigerant. Covers specifications, installation, operation, maintenance, and troubleshooting.