Friedrich Breeze Universal Heat Pumps: Specifications and Dimensions

Friedrich Breeze™ Universal Heat Pumps

Brand: Friedrich

Key Features

  • Universal compatibility with existing air handlers or gas furnaces.
  • Accommodates long piping runs up to 246 ft. for Premier models and up to 131 ft. for Select models, with height differentials up to 98 ft.
  • Precision Inverter® technology delivers efficiencies of up to 19.0 SEER2 and 10 HSPF2.
  • Operates in extreme temperatures down to -22° F in heat pump mode, with cooling in temperatures as low as 5°F.
  • Includes built-in base pan heater and optional auxiliary heater kit.
  • Soft-Start™ technology for quiet start-up and precise temperature control.
  • Quiet operation as low as 35 dB(A).
  • Ultra-compact design with a 40% smaller footprint than traditional and top-discharge units.
  • Multi-position Air Handler capability.
  • ENERGY STAR® Certified for Cold Climate models available.
  • Eligible for many federal & local tax credit & rebate incentives.

Product Units

Indoor Air Handler Units

Models: WFH24Y193C, WFH36Y193C, WFH48Y223C, WFH60Y223C

Description: Two distinct indoor air handler units are depicted, both featuring a dark grey finish with the Friedrich logo. The units are shown side-by-side, representing different capacities.

Inverter Heat Pump Condenser/Outdoor Units

Models: WFH24Y193D, WFH36Y193D, WFH48Y193D, WFH60Y193D

Description: Three distinct outdoor condenser units are shown, each with a fan grille and a compact, modern design. The units represent different capacities and are labeled with their respective model numbers.

Heater Kits

  • AUX5KWA
  • AUX7KWA
  • AUX10KWA
  • AUX15KWA
  • AUX20KWA

Specifications

Specification 2-Ton
(WFH24Y193D / WFPU17Y243D)
3-Ton
(WFH36Y193D / WFPU17Y363D)
4-Ton
(WFH48Y223D / WFPU17Y483D)
5-Ton
(WFH60Y223D / WFPU17Y603D)
Indoor Model WFH24Y193D WFH36Y193D WFH48Y223D WFH60Y223D
Outdoor Model WFPU17Y243D WFPU17Y363D WFPU17Y483D WFPU17Y603D
ENERGY STAR® Standard No No Yes No
ENERGY STAR® Cold Climate Yes No Yes No
A2L Sensor Yes Yes Yes Yes
Power Supply 208-230V / 60Hz / 1ph 208-230V / 60Hz / 1ph 208-230V / 60Hz / 1ph 208-230V / 60Hz / 1ph
Rated Current - Indoor 2.6 Amps 3.8 Amps 5.4 Amps 5.4 Amps
MOP Indoor 10 Amps 10 Amps 10 Amps 10 Amps
MCA Indoor 3.3 Amps 4.8 Amps 6.8 Amps 6.8 Amps
Thermostat Type 24V 24V 24V 24V
Rated Current - Outdoor 8.77 Amps 13.09 Amps 17.22 Amps 20.84 Amps
MCA Outdoor 16 Amps 21 Amps 33 Amps 33 Amps
Max. Circuit Breaker 25 Amps 30 Amps 50 Amps 50 Amps
Communication Cable 6 x 18AWG 6 x 18AWG 6 x 18AWG 6 x 18AWG
Rated Capacity @ 95°F 24,000 Btu/h 35,000 Btu/h 48,000 Btu/h 54,000 Btu/h
Cooling Capacity Range (Min.-Max.) 6,000-24,600 Btu/h 11,000-36,500 Btu/h 14,000-48,600 Btu/h 14,000-54,000 Btu/h
Cooling Capacity Range (Min.-Max.) 1,760-7,200 W 3,223-10,700 W 4,100-14,200 W 4,100-15,800 W
Capacity @ 115°F 22,600 Btu/h 28,200 Btu/h 40,000 Btu/h 44,400 Btu/h
Power Input 2,616 W 3,104 W 4,720 W 5,246 W
Current 11.6 Amps 13.72 Amps 22 Amps 24 Amps
EER2 @ 95°F 10 Btu/h/W 9.8 Btu/h/W 10 Btu/h/W 8.8 Btu/h/W
SEER2 18 Btu/h/W 17.5 Btu/h/W 18 Btu/h/W 17 Btu/h/W
Operating Temp. Range - Indoor 45-95°F (7-35°C) 45-95°F (7-35°C) 45-95°F (7-35°C) 45-95°F (7-35°C)
Operating Temp. Range - Outdoor 5-115°F (-15-46°C) 5-115°F (-15-46°C) 5-115°F (-15-46°C) 5-115°F (-15-46°C)
Rated Capacity @ 47°F 24,000 Btu/h 36,000 Btu/h 48,000 Btu/h 55,000 Btu/h
Heating Capacity Range (Min.-Max.) 3,750-25,500 Btu/h 6,100-39,400 Btu/h 7,490-49,300 Btu/h 7,490-57,300 Btu/h
Heating Capacity Range (Min.-Max.) 1,100-7,471 W 1,787-11,544 W 2,194-14,444 W 2,190-16,789 W
Power Input 1,917 W 2,859 W 3,761 W 4,554 W
COP @ 47°F 3.67 W/W 3.69 W/W 3.74 W/W 3.54 W/W
COP @ 5°F 2 W/W 2 W/W 2 W/W 1.95 W/W
HSPF2 9 Btu/h/W 9 Btu/h/W 9 Btu/h/W 8.5 Btu/h/W
Rated Heating Capacity @ 17°F (-8.3°C) 17,000 Btu/h 22,200 Btu/h 32,200 Btu/h 33,200 Btu/h
Max. Heating Capacity @ 5°F (-15°C) 18,000 Btu/h 22,000 Btu/h 35,000 Btu/h 36,000 Btu/h
Max. Heating Capacity @ -5°F (-20.5°C) 11,400 Btu/h 18,000 Btu/h 26,600 Btu/h 29,600 Btu/h
Operating Temp. Range - Indoor 45-95°F (7-35°C) 45-95°F (7-35°C) 45-95°F (7-35°C) 45-95°F (7-35°C)
Operating Temp. Range - Outdoor -4-75°F (-20-24°C) -4-75°F (-20-24°C) -4-75°F (-20-24°C) -4-75°F (-20-24°C)
Indoor Fan Motor Output 1/3 HP 1/2 HP 3/4 HP 3/4 HP
Indoor Fan Motor RLA 2.4-2.6 Amps 3.6-3.8 Amps 5.0-5.4 Amps 5.0-5.4 Amps
Indoor Fan Motor Speed 350-1,400 RPM 350-1,400 RPM 350-1,400 RPM 350-1,400 RPM
Indoor Airflow Rated (Multi-speed ECM) 800 CFM (1,360 m³/h) 1,120 CFM (1,905 m³/h) 1,706 CFM (2,900 m³/h) 1,706 CFM (2,900 m³/h)
Indoor Airflow (Min.-Max.) 530-800 CFM (902-1,360 m³/h) 785-1,120 CFM (1,334-1,905 m³/h) 1,157-1,706 CFM (1,967-2,900 m³/h) 1,157-1,706 CFM (1,967-2,900 m³/h)
Indoor Airflow Ultra-low Speed 530 CFM (902 m³/h) 785 CFM (1,334 m³/h) 1,157 CFM (1,967 m³/h) 1,157 CFM (1,967 m³/h)
Static Pressure Rated 0.58 in. W.C. (145 Pa) 0.58 in. W.C. (145 Pa) 0.58 in. W.C. (145 Pa) 0.58 in. W.C. (145 Pa)
Static Pressure Range 0-0.8 in. W.C. (0-200 Pa) 0-0.8 in. W.C. (0-200 Pa) 0-0.8 in. W.C. (0-200 Pa) 0-0.8 in. W.C. (0-200 Pa)
Outdoor Fan Motor Output 1/12 HP 1/7 HP 1/3 HP 1/3 HP
Outdoor Fan Motor RLA 0.32 Amps 0.8 Amps 1.5 Amps 1.5 Amps
Outdoor Fan Motor Speed 880 RPM 880 RPM 850 RPM 850 RPM
Outdoor Airflow (High) 3,150 CFM (1,853 m³/h) 3,800 CFM (2,235 m³/h) 5,700 CFM (3,350 m³/h) 5,700 CFM (3,350 m³/h)
Outdoor Fan Motor Input 1,500 W 1,805 W 2,410 W 2,410 W
Outdoor Fan Motor Rated Current 4.6 Amps 8.2 Amps 5.18 Amps 5.18 Amps
Compressor FV68S/950 VG74/920 VG74/1,200 VG74/1,200
Refrigerant Oil 70.5 ml (2.0 oz.) 88.2 ml (2.5 oz.) 137.6 ml (3.9 oz.) 137.6 ml (3.9 oz.)
Refrigerant Charge 25 oz. (7.6 kg) 25 oz. (7.6 kg) 25 oz. (7.6 kg) 25 oz. (7.6 kg)
Factory Pre-charge 25 ft. (7.6 m) 25 ft. (7.6 m) 25 ft. (7.6 m) 25 ft. (7.6 m)
Additional Charge for Each ft. 0.38 oz./ft. 0.38 oz./ft. 0.38 oz./ft. 0.38 oz./ft.
Refrigerant Piping (Liquid Side / Gas Side) 3/8 in. / 5/8 in. (9.52 / 15.88 mm) 3/8 in. / 5/8 in. (9.52 / 15.88 mm) 3/8 in. / 3/4 in. (9.52 / 19.05 mm) 3/8 in. / 3/4 in. (9.52 / 19.05 mm)
Max. Pipe Length 100 ft. (30 m) 115 ft. (35 m) 130 ft. (40 m) 130 ft. (40 m)
Max. Difference in Level 66 ft. (20 m) 80 ft. (25 m) 100 ft. (30 m) 100 ft. (30 m)
Design Pressure (H/L) 600/380 PSIG (4.14/2.62 MPa) 600/380 PSIG (4.14 / 2.62 MPa) 600/380 PSIG (4.14 / 2.62 MPa) 600/380 PSIG (4.14 / 2.62 MPa)
Indoor Noise Level (High) 55 dB(A) 57 dB(A) 57 dB(A) 57 dB(A)
Drainage Water Pipe Diameter 3/4 in. 3/4 in. 3/4 in. 3/4 in.
Outdoor Throttle Type EEV EEV EEV EEV
Moisture Removal 4.6 pints/hr (2.2 L/hr) 9.5 pints/hr (4.5 L/hr) 13.2 pints/hr (6.2 L/hr) 15.8 pints/hr (7.5 L/hr)
Indoor Unit Dimensions (W×H×D) 19-5/8 x 46-1/8 x 21-5/8 in.
(500 x 1,170 x 550 mm)
19-5/8 x 46-1/8 x 21-5/8 in.
(500 x 1,170 x 550 mm)
22 x 53-7/8 x 24 in.
(560 x 1,370 x 610 mm)
22 x 53-7/8 x 24 in.
(560 x 1,370 x 610 mm)
Indoor Unit Packing (L×W×H) 22-1/2 x 49-5/8 x 25-3/8 in.
(570 x 1,260 x 645 mm)
22-1/2 x 49-5/8 x 25-3/8 in.
(570 x 1,260 x 645 mm)
25-1/4 x 55-1/2 x 28 in.
(640 x 1,410 x 710 mm)
25-1/4 x 55-1/2 x 28 in.
(640 x 1,410 x 710 mm)
Indoor Unit Net Weight 130.5 lbs. (59.2 kg) 135.1 lbs. (61.3 kg) 180.6 lbs. (82 kg) 180.6 lbs. (82 kg)
Indoor Unit Shipping Weight 153.6 lbs. (69.7 kg) 158.1 lbs. (71.7 kg) 204.4 lbs. (92.7 kg) 204.4 lbs. (92.7 kg)
Outdoor Unit Dimensions (W×H×D) 33-7/8 x 26-3/8 x 12-1/4 in.
(860 x 670 x 310 mm)
35-3/8 x 29-1/2 x 13-3/8 in.
(900 x 750 x 340 mm)
43-1/4 x 34-1/2 x 17-3/4 in.
(1,100 x 875 x 450 mm)
43-1/4 x 34-1/2 x 17-3/4 in.
(1,100 x 875 x 450 mm)
Outdoor Unit Packing (L×W×H) 39 x 28-3/4 x 17-3/4 in.
(990 x 730 x 450 mm)
41 x 32-5/8 x 18-1/8 in.
(1,040 x 830 x 460 mm)
45-7/8 x 39-1/2 x 21-1/4 in.
(1,165 x 1,005 x 540 mm)
45-7/8 x 39-1/2 x 21-1/4 in.
(1,165 x 1,005 x 540 mm)
Outdoor Unit Net Weight 104.5 lbs. (47 kg) 116.8 lbs. (53 kg) 186.7 lbs. (84 kg) 186.7 lbs. (84 kg)
Outdoor Unit Shipping Weight 112.2 lbs. (50.5 kg) 125.7 lbs. (57 kg) 210.9 lbs. (95 kg) 210.9 lbs. (95 kg)

Dimension Details

Indoor Air Handler Units (2-Ton / 3-Ton)

Diagram showing the external dimensions of the Friedrich Breeze indoor air handler units (2-Ton/3-Ton models WFH24Y193D, WFH36Y193D). Key dimensions are provided in inches (mm): Height: 46 (1170), Width: 19-5/8 (500), Depth: 21-5/8 (550). Connections for gas pipe, liquid pipe, drain pipe, and electrical box are indicated.

Indoor Air Handler Units (4-Ton / 5-Ton)

Diagram showing the external dimensions of the Friedrich Breeze indoor air handler units (4-Ton/5-Ton models WFH48Y223D, WFH60Y223D). Key dimensions are provided in inches (mm): Height: 53-7/8 (1370), Width: 22 (560), Depth: 24 (610). Connections for gas pipe, liquid pipe, drain pipe, and electrical box are indicated.

Outdoor Condenser/Unit (2-Ton)

Diagram showing the external dimensions of the Friedrich Breeze outdoor condenser unit (2-Ton model WFPU17Y24A3D). Front, side, and top views are presented. Key dimensions include: Height: 26-3/8 (670), Width: 33-7/8 (860), Depth: 12-1/4 (312). Connections for gas pipe, liquid pipe, drain pipe, and electrical box are indicated.

Outdoor Condenser/Unit (3-Ton)

Diagram showing the external dimensions of the Friedrich Breeze outdoor condenser unit (3-Ton model WFPU17Y36A3D). Front, side, and top views are presented. Key dimensions include: Height: 29-1/2 (750), Width: 35-3/8 (900), Depth: 13-1/2 (344). Connections for gas pipe, liquid pipe, drain pipe, and electrical box are indicated.

Outdoor Condenser/Units (4-Ton / 5-Ton)

Diagram showing the external dimensions of the Friedrich Breeze outdoor condenser units (4-Ton/5-Ton models WFPU17Y48A3D, WFPU17Y60A3D). Front, side, and top views are presented. Key dimensions include: Height: 34-1/2 (875), Width: 43-3/8 (1100), Depth: 17-1/2 (444). Connections for gas pipe, liquid pipe, drain pipe, and electrical box are indicated. A note mentions a 2-1/2 (12) x 3/4 (20) hole for air inlet.

Notes

System rated performance is only guaranteed when paired with a properly installed Friedrich air handler. Performance may be diminished when paired with a non-Friedrich air handler, and eligibility for rebates may be voided.

Due to continuing research in new energy-saving technology, specifications are subject to change without notice.

High Efficiency Electric Home Rebates are dependent on state participation and available funding. Visit Friedrich.com/Federal-Incentives for complete details.

© 2024 Friedrich Air Conditioning. Friedrich trademarks are owned by Friedrich Air Conditioning LLC.

Note: Pipe lengths over 100 feet require an increase in communication cable to 16 AWG. Lengths over 262 feet require an increase in communication cable to 14 AWG.

PDF preview unavailable. Download the PDF instead.

Breeze Select Submittal 2025 Adobe InDesign 20.3 (Macintosh) Adobe PDF Library 17.0

Related Documents

Preview Friedrich Breeze Series Inverter Heat Pumps for Efficient Home Comfort
Discover the Friedrich Breeze Series inverter-driven universal ducted heat pumps, offering precise temperature control, significant energy savings, and quiet operation for year-round home comfort. Learn about Premier and Select models, universal compatibility, and advanced features.
Preview Friedrich Breeze Universal Heat Pumps: Features, Specifications, and Dimensions
Comprehensive overview of Friedrich's Breeze Universal Heat Pump systems, detailing features, technical specifications, and unit dimensions for 2-ton, 3-ton, and 4-ton models. Includes ENERGY STAR certification and cold climate operation.
Preview Friedrich Universal Heat Pump Extended Capacity Charts
Extended capacity charts for Friedrich Universal Heat Pumps, including outdoor condenser and air handler unit compatibility, piping length correction factors, and detailed performance data for cooling and heating operations across various models and conditions.
Preview Friedrich VRP Variable Refrigerant Packaged Heat Pump Product Profile
Discover the Friedrich VRP, an innovative and intelligent Variable Refrigerant Packaged Heat Pump system. It provides superior cooling, efficient heating, advanced humidity control, and optional fresh air integration, ensuring optimal comfort and energy savings with its Precision Inverter technology.
Preview Friedrich Breeze Select 2025 R-454B Heat Pump Quick Start Guide
A quick start guide for Friedrich Breeze Select 2025 R-454B Universal Heat Pump models, covering installation, operation, and troubleshooting.
Preview Friedrich VRP Variable Refrigerant Packaged Heat Pump Technical Specifications and Submittal
Comprehensive technical specifications, unit features, dimensional data, and performance metrics for the Friedrich VRP series of Variable Refrigerant Packaged Heat Pumps, emphasizing Precision Inverter Technology and unitary package design.
Preview Friedrich Breeze Universal Heat Pump: Installation and Wiring Diagrams
Comprehensive guide to the Friedrich Breeze Universal Heat Pump, covering installation, wiring diagrams for various configurations, and operational parameters. Learn about its features, energy savings, and low-temperature performance.
Preview Friedrich Endeavor™ F-Series Plus iM Heat Pumps: Specifications and Performance Data
Detailed specifications, features, performance data, and model information for the Friedrich Endeavor™ F-Series Plus iM Heat Pumps (FRP15AZ series). Includes efficiency ratings, capacities, dimensions, and warranty details.