Klaxon Nexus 110 AC Sounder & Sounder-Beacon Installation Instructions
Introduction
This document provides installation instructions for the Klaxon Nexus 110 AC Sounder & Sounder-Beacon, a device designed for audible and visual signaling.
Installation
IMPORTANT:
- The unit must be fitted with a fused spur incorporating an all-pole disconnection device with 3mm contact separation. Ensure the fuse, cable size, and gland type are rated sufficiently for the total load on the sounder circuit.
- Isolate the unit from the electricity supply before removing the cover. Only suitably qualified personnel should access the unit for tone or volume adjustments. WARNING: no user-serviceable parts are contained within the unit.
- Installation involves mounting the base unit first, then making external wiring connections. The head unit automatically connects when attached to the base.
- The sounder head separates from the base by unlocking four 1/4-turn fasteners. A Philips No. 2 screwdriver, minimum 100mm long, is recommended.
- Note that the head fits the base in only one orientation. If a beacon is fitted, ensure correct positioning of the base to align the beacon after the sounder is attached.
Wiring
Power: The sounder and beacon have separate power terminals, marked as follows:
Device | Common (Neutral) | 110V | 230V |
Sounder | N | 110V | 230V |
Beacon (Where fitted) | N | 110V | 230V |
Wiring Diagram Description: The wiring diagram illustrates connections from a controller to two units. It shows input terminals labeled 'Beacon L', 'Sounder L', and 'Common N' for each unit, along with '2nd Stage' and '3rd Stage' inputs, indicating separate power and stage control capabilities.
Remote Tone Switching (If required): Connect control terminals externally as shown below:
Alarm Stage | Example Signal | Activation |
Stage 1 | 'Alert' | No Connection (Default) |
Stage 2 | 'Evacuate' | Link Terminal S2 to terminal |
Stage 3 | 'All Clear' | Link Terminal S3 to terminal |
Controls
Tone Selection: The first and second stage alarm tones are independently set using 6-way dipswitches S1 and S2. The third stage alarm tone is pre-set to complement the selected first stage tone. Refer to the Tone Selection Table for specific settings.
Volume Control: The sound output can be reduced by up to 20dBA by adjusting the potentiometer.
Technical Specifications
- Supply Voltage Range: 110/230V 50/60Hz
- Current: Sounder - 40mA max., Beacon (where fitted) - 70mA
- Peak Sound Level: 103-115 dBA at 1m*
- Number of Tones: 64
- Frequency Range: 340 - 2900 Hz*
- Volume Control: 20 dBA typical reduction
- Remote Tone Switching: Provision for 3 volt-free contact activated alarm stages
- Operating Temperature: -25°C to +55°C
- Casing: High Impact Polycarbonate/ABS
- IP Rating: IP66 with suitable cable glands
- Synchronisation: Automatic with Klaxon Nexus and Sonos Sounders
*Depends on selected tone.
Tone Selection Table
Tone | Tone Type | Tone Description / Application | Dip Switch (S1/S2) | 3rd Stage Tone | Peak Sound Level (dBA@1m) |
1 | 970Hz | 970Hz (BS5839-1:2002) | 0-0-0-0-0-0 | 18 | 110 |
2 | 800Hz/970Hz @ 2Hz (BS5839-1:2002) | 0-0-0-0-0-1 | 1 | 110 | |
3 | MM | 800Hz – 970Hz @ 1Hz (BS5839-1:2002) | 0-0-0-0-1-0 | 1 | 110 |
4 | 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) | 0-0-0-0-1-1 | 1 | 110 | |
5 | 970Hz, 0.5s/630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002) | 0-0-0-1-0-0 | 1 | 110 | |
6 | 554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001) | 0-0-0-1-0-1 | 1 | 107 | |
7 | ΛΛΛ | 500-1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) Dutch Slow Whoop | 0-0-0-1-1-0 | 1 | 110 |
8 | 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) | 0-0-0-1-1-1 | 1 | 105 | |
9 | ΛΛΛ | 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone) | 0-0-1-0-0-0 | 1 | 110 |
10 | 550Hz/440Hz @ 0.5Hz | 0-0-1-0-0-1 | 19 | 107 | |
11 | 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone) | 0-0-1-0-1-0 | 1 | 110 | |
12 | 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone) | 0-0-1-0-1-1 | 1 | 112 | |
13 | N7 | 1200Hz – 500Hz @ 1Hz (DIN 33 404) | 0-0-1-1-0-0 | 1 | 110 |
14 | 400Hz | 0-0-1-1-0-1 | 18 | 105 | |
15 | 550Hz, 0.7s/1000Hz, 0.33s | 0-0-1-1-1-0 | 1 | 111 | |
16 | M | 1500Hz – 2700Hz @ 3Hz (Vandal Alarm) | 0-0-1-1-1-1 | 1 | 116 |
17 | Simulated Bell | 0-1-0-0-0-0 | 1 | 112 | |
18 | 2130Hz | 0-1-0-0-0-1 | 1 | 113 | |
19 | 660Hz | 0-1-0-0-1-0 | 10 | 109 | |
20 | 660Hz 1.8s ON/1.8s OFF | 0-1-0-0-1-1 | 19 | 108 | |
21 | 660Hz 0.15s ON/0.15s OFF | 0-1-0-1-0-0 | 19 | 107 | |
22 | 510Hz, 0.25s/610Hz, 0.25s | 0-1-0-1-0-1 | 1 | 107 | |
23 | 800/1000Hz 0.5s each (1Hz) | 0-1-0-1-1-0 | 1 | 111 | |
24 | M | 250Hz – 1200Hz @ 12Hz | 0-1-0-1-1-1 | 1 | 105 |
25 | 500Hz – 1200Hz @ 0.33Hz. | 0-1-1-0-0-0 | 1 | 110 | |
26 | M | 2400Hz – 2900Hz @ 9Hz | 0-1-1-0-0-1 | 1 | 116 |
27 | M | 2400Hz – 2900Hz @ 3Hz | 0-1-1-0-1-0 | 1 | 116 |
28 | M | 800Hz – 970Hz @ 100Hz | 0-1-1-0-1-1 | 1 | 110 |
29 | M | 800Hz – 970Hz @ 9Hz | 0-1-1-1-0-0 | 1 | 110 |
30 | MM | 800Hz – 970Hz @ 3Hz | 0-1-1-1-0-1 | 1 | 110 |
31 | 800Hz, 0.25s ON/1s OFF | 0-1-1-1-1-0 | 1 | 108 | |
32 | ΛΛΛ | 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) | 0-1-1-1-1-1 | 1 | 110 |
33 | 340Hz | 1-0-0-0-0-0 | 1 | 106 | |
34 | 1000Hz | 1-0-0-0-0-1 | 18 | 111 | |
35 | 1400Hz-1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265) | 1-0-0-0-1-0 | 1 | 110 | |
36 | 660Hz 6.5s ON/13s OFF | 1-0-0-0-1-1 | 19 | 108 | |
37 | 1000Hz/2000Hz, 1s each | 1-0-0-1-0-0 | 1 | 113 | |
38 | 720Hz, 0.7s ON/0.3s OFF | 1-0-0-1-0-1 | 1 | 106 | |
39 | 970Hz, 0.25s ON/OFF | 1-0-0-1-1-0 | 1 | 110 | |
40 | 2800Hz, 1s ON/OFF | 1-0-0-1-1-1 | 1 | 113 | |
41 | 2800Hz 0.25s ON/OFF | 1-0-1-0-0-0 | 1 | 113 | |
42 | 2400/2900 @ 2Hz | 1-0-1-0-0-1 | 1 | 115 | |
43 | Chime, 554Hz/440Hz Single shot 'ding dong' | 1-0-1-0-1-0 | 1 | 104 | |
44 | Chime, 554Hz/440Hz Repeating 'ding dong' | 1-0-1-0-1-1 | 1 | 107 | |
45 | Chime, 970Hz/800Hz Single shot 'ding dong' | 1-0-1-1-0-0 | 1 | 106 | |
46 | Chime, 970Hz/800Hz Repeating 'ding dong' | 1-0-1-1-0-1 | 1 | 106 | |
47 | Hooter, Repeating | 1-0-1-1-1-0 | 1 | 107 | |
48 | Gentle alarm - Tone 2, rises slowly to full volume over 30s | 1-0-1-1-1-1 | 1 | 109 | |
49 | Time-Out Alarm – As Tone 2, cuts off after 10 mins | 1-1-0-0-0-0 | 1 | 109 | |
50 | Time-Out Alarm – As Tone 2, cuts off after 2 mins | 1-1-0-0-0-1 | 1 | 109 | |
51 | 750Hz 0.33s ON/0.51s OFF | 1-1-0-0-1-0 | 1 | 106 | |
52 | 750Hz 0.51s ON/0.33s OFF | 1-1-0-0-1-1 | 1 | 107 | |
53 | 550Hz, 0.33s/1000Hz, 0.7s | 1-1-0-1-0-0 | 1 | 111 | |
54 | 600Hz – 900Hz/ 0.9s | 1-1-0-1-0-1 | 1 | 109 | |
55 | 660Hz – 680Hz/ 0.9s | 1-1-0-1-1-0 | 1 | 105 | |
56 | 670Hz – 725Hz/ 0.9s | 1-1-0-1-1-1 | 1 | 107 | |
57 | 920Hz – 750Hz/ 0.9s | 1-1-1-0-0-0 | 1 | 110 | |
58 | 700Hz - 900Hz, 0.3s/0.6s OFF | 1-1-1-0-0-1 | 1 | 109 | |
59 | 900Hz - 760Hz, 0.6s/0.3s OFF | 1-1-1-0-1-0 | 1 | 110 | |
60 | 750Hz | 1-1-1-0-1-1 | 18 | 107 | |
61 | Power Only - Use with Stage 3 control for manual/intermittent chime triggering | 1-1-1-1-0-0 | 43 | 107 | |
62 | Power Only - Use with Stage 3 control for manual/intermittent chime triggering | 1-1-1-1-0-1 | 43 | 107 | |
63 | Power Only - Use with Stage 3 control for manual/intermittent horn triggering | 1-1-1-1-1-0 | 47 | 107 | |
64 | Reserved for future use | 1-1-1-1-1-1 | - | - |
Manufacturer Information
Texecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK
+44 1706 233879 | +44 1706 223450
sales@klaxonsignals.com | www.klaxonsignals.com
Issue 5.0 (August 2010) 18-186459-5