Klaxon Sonos DC Sounder Beacon Installation Instructions

This document provides detailed installation instructions for the Klaxon Sonos DC Sounder Beacon.

Installation

To secure the sounder to its base, the locking mechanism can be activated by removing the thin plastic section shown in Fig. 1a using side cutters or a similar tool. To release a locked head, remove the small rubber bung from the side hole of the sounder, insert a tool into the hole, and depress the clip while twisting the head. The O-ring and bung must be refitted to maintain weatherproofing.

An alternative locking method is shown in Fig. 1b. Drive the hexagonal locking screw forward by turning a 1.5mm hexagonal key clockwise until the head is locked.

Wiring

The sounder and beacon 0V terminals can be linked together for simultaneous control of sound and light using a 2-core connection. A separate earth terminal is provided on the deep base for connecting the screen or functional earth. On the shallow base, terminal 5 can be used for this purpose.

Line Terminal Marking
Common Positive Supply (3) IN+
Sounder Negative Supply (2) - or COM -
Beacon Negative Supply (1) ♫

Tone Selection and Volume Control

The tone is selected using the 5-way dipswitch on the bottom of the sounder head. Refer to the tone table for details of available tones and the required switch settings. The sound output of the unit can be reduced by adjusting the potentiometer on the bottom of the sounder.

Tone Details

Tone Tone Type Tone Description/Application DIP SWITCH (1-2-3-4-5) dBA @ 1m mA
1.970Hz0-0-0-0-09921
2.800Hz/970Hz @ 2Hz0-0-0-0-110020
3.800Hz-970Hz @ 1Hz0-0-0-1-010020
4.970Hz 1s OFF/1s ON0-0-0-1-19914
5.970Hz, 0.5s/630Hz, 0.5s0-0-1-0-09919
6.554Hz, 0.1s/440Hz, 0.4s (AFNOR NF S 32 001)0-0-1-0-19713
7.500-1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000 Dutch Slow Whoop)0-0-1-1-09916
8.420Hz 0.6s ON/0.6s OFF (Australia AS1670 Alert tone)0-0-1-1-1969
9.1000-2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation)0-1-0-0-010414
10.550Hz/440Hz @ 0.5Hz0-1-0-0-19714
11.970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201)0-1-0-1-09812
12.2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)0-1-0-1-19421
13.1200Hz-500Hz @ 1Hz (DIN 33 404)0-1-1-0-09917
14.400Hz0-1-1-0-19513
15.550Hz, 0.7s/1000Hz, 0.33s0-1-1-1-09817
16.1500Hz-2700Hz @ 3Hz0-1-1-1-110434
17.750Hz1-0-0-0-09918
18.2400Hz1-0-0-0-110645
19.660Hz1-0-0-1-09617
20.660Hz 1.8s ON/1.8s OFF1-0-0-1-19612
21.660Hz 0.15s ON/0.15s OFF1-0-1-0-09611
22.510Hz, 0.25s/610Hz, 0.25s1-0-1-0-19815
23.800/1000Hz 0.5s each (1Hz)1-0-1-1-010021
24.250Hz-1200Hz @ 12Hz1-0-1-1-19813
25.500Hz-1200Hz @ 0.33Hz1-1-0-0-09917
26.2400Hz-2900Hz @ 9Hz1-1-0-0-110140
27.2400Hz-2900Hz @ 3Hz1-1-0-1-010440
28.500-1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation)1-1-0-1-19810
29.800Hz-970Hz @ 9Hz1-1-1-0-09920
30.800Hz-970Hz @ 3Hz1-1-1-0-110020
31.800Hz, 0.25s ON/1s OFF1-1-1-1-0998
32.500Hz-1200Hz, 3.75s/0.25s OFF (AS2220)1-1-1-1-19917

Technical Specifications

Specification Value
Supply Voltage17 - 60V DC
CurrentSounder: 4- 45mA*
Beacon: 5mA
Peak Sound Level94 - 106 dBA at 1m*
Number of tones32
Frequency Range400 - 2850 Hz*
RatingContinuous
Operating Temperature-25°C to +70°C
CasingHigh Impact Polycarbonate
IP RatingIP21/IP65 (deep base)
SyncronisationAutomatic

*Depends on selected tone and input voltage. See tone table for details. EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17v DC only.

Compliance and References

Type CPR Reference CPD Number Essential Characteristics Declared Performance (EN54-3:2001+A1:2002 A2:2006 Subclause)
Fire Alarm Device - Sounder PSS-0068 Reference 0832-CPR-0297 PSS-0068/73/79/80 & PSC-0055 :0832-CPD-0297 Reproducibility 5.2
PSC-0045 Reference 0832-CPR-0546 PSC-0045/54/62/63/51 :0832-CPD-0546 Operational performance 5.3
Durability 5.4
Dry Heat (operational) 5.5
Dry Heat (endurance) 5.6
Cold (operational) 5.7
Damp heat, cyclic (operational) 5.8
Damp heat, steady state (endurance) 5.9
Damp Heat, cyclic (endurance) 5.10
SO2 corrosion (endurance) 5.11
Shock (operational) 5.12
Impact (operational) 5.13
Vibration (operational) 5.14
Vibration (endurance) 5.15
Electrostatic discharge (operational) 5.16
Radiated electromagnetic fields (operational) 5.16
Voltage transients, fast transient bursts (operational) 5.16
Enclosure Protection 5.17

Technical Data Doc: 18-186215

Type A: For indoor use (Shallow Base)

Type B: For outdoor use (Deep Base)

Manufacturer Information

Texecom Ltd (Incorporating Klaxon Signals)

St Crispin Way, Haslingden, BB4 4PW, UK.

Tel: +44 1706 233879

Email: sales@klaxonsignals.com

Website: www.klaxonsignals.com

Issue 16 (Dec 2014) INS532-16

Copyright © Texecom Ltd.

Environmental Information (WEEE Directive)

The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimise the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol [symbol: do not dispose in public waste systems] must not be disposed of in European public disposal systems. European users of electrical equipment must now return end-of-life equipment for disposal. Further information can be found on the following website: http://www.recyclethis.info/.

Models: Sonos DC Sounder Beacon, DC Sounder Beacon, Sounder Beacon, Beacon

File Info : application/pdf, 6 Pages, 339.47KB

PDF preview unavailable. Download the PDF instead.

SonosSounderBeacon-DC-INS

References

Adobe InDesign CC 2014 (Macintosh) Adobe PDF Library 11.0

Related Documents

Preview Klaxon Sonos AC Sounder & Sounder-Beacon Installation Guide
Comprehensive installation guide for the Klaxon Sonos AC Sounder & Sounder-Beacon, detailing mounting, tone selection, volume control, and technical specifications. Includes multilingual support information.
Preview Klaxon Nexus DC Voice-Enhanced Sounder & Sounder with Beacon Installation Instructions
Detailed installation instructions for the Klaxon Nexus DC Voice-Enhanced Sounder & Sounder with Beacon, covering wiring, configuration, technical specifications, and environmental compliance.
Preview Klaxon Nexus 120 AC Sounder & Sounder-Beacon Installation Instructions
Comprehensive installation guide for the Klaxon Nexus 120 AC Sounder and Sounder-Beacon, detailing setup, wiring, tone selection, and technical specifications.
Preview Klaxon Nexus 110 AC Sounder & Sounder-Beacon Installation Instructions
Comprehensive installation guide for the Klaxon Nexus 110 AC Sounder & Sounder-Beacon, detailing setup, wiring, tone selection, and technical specifications. Includes a full list of 64 available tones.
Preview Klaxon Nexus 110 Xenon Beacon Sounder Datasheet
Datasheet for the Klaxon Nexus 110 Xenon Beacon Sounder, a powerful and reliable audible signalling solution for industrial and commercial applications. Features include AC or DC compatibility, 64 tones, adjustable volume, and first-fix wire to base technology.
Preview Klaxon Nexus 120 DC Sounder & Sounder-Beacon Installation Instructions
Detailed installation instructions for the Klaxon Nexus 120 DC Sounder and Sounder-Beacon, covering wiring, tone selection, volume control, and technical specifications. Includes EN54-3 compliance information.
Preview Klaxon Master Blaster Siren SLM-0001 Installation Manual
Installation instructions and specifications for the Klaxon Master Blaster Siren (Model SLM-0001), detailing electrical connections, mounting, and operation for security and fire systems.
Preview Klaxon Nexus 105/110/120 Sounder Beacon - Product Specifications
Detailed specifications and features for the Klaxon Nexus 105, 110, and 120 Sounder Beacons, including part numbers, lens colors, beacon types, and technical ratings.