Klaxon Sonos DC Sounder Beacon Installation Instructions
This document provides detailed installation instructions for the Klaxon Sonos DC Sounder Beacon.
Installation
To secure the sounder to its base, the locking mechanism can be activated by removing the thin plastic section shown in Fig. 1a using side cutters or a similar tool. To release a locked head, remove the small rubber bung from the side hole of the sounder, insert a tool into the hole, and depress the clip while twisting the head. The O-ring and bung must be refitted to maintain weatherproofing.
An alternative locking method is shown in Fig. 1b. Drive the hexagonal locking screw forward by turning a 1.5mm hexagonal key clockwise until the head is locked.
Wiring
The sounder and beacon 0V terminals can be linked together for simultaneous control of sound and light using a 2-core connection. A separate earth terminal is provided on the deep base for connecting the screen or functional earth. On the shallow base, terminal 5 can be used for this purpose.
Line | Terminal Marking |
---|---|
Common Positive Supply | (3) IN+ |
Sounder Negative Supply | (2) - or COM - |
Beacon Negative Supply | (1) ♫ |
Tone Selection and Volume Control
The tone is selected using the 5-way dipswitch on the bottom of the sounder head. Refer to the tone table for details of available tones and the required switch settings. The sound output of the unit can be reduced by adjusting the potentiometer on the bottom of the sounder.
Tone Details
Tone | Tone Type | Tone Description/Application | DIP SWITCH (1-2-3-4-5) | dBA @ 1m | mA |
---|---|---|---|---|---|
1. | 970Hz | 0-0-0-0-0 | 99 | 21 | |
2. | 800Hz/970Hz @ 2Hz | 0-0-0-0-1 | 100 | 20 | |
3. | 800Hz-970Hz @ 1Hz | 0-0-0-1-0 | 100 | 20 | |
4. | 970Hz 1s OFF/1s ON | 0-0-0-1-1 | 99 | 14 | |
5. | 970Hz, 0.5s/630Hz, 0.5s | 0-0-1-0-0 | 99 | 19 | |
6. | 554Hz, 0.1s/440Hz, 0.4s (AFNOR NF S 32 001) | 0-0-1-0-1 | 97 | 13 | |
7. | 500-1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000 Dutch Slow Whoop) | 0-0-1-1-0 | 99 | 16 | |
8. | 420Hz 0.6s ON/0.6s OFF (Australia AS1670 Alert tone) | 0-0-1-1-1 | 96 | 9 | |
9. | 1000-2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation) | 0-1-0-0-0 | 104 | 14 | |
10. | 550Hz/440Hz @ 0.5Hz | 0-1-0-0-1 | 97 | 14 | |
11. | 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201) | 0-1-0-1-0 | 98 | 12 | |
12. | 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201) | 0-1-0-1-1 | 94 | 21 | |
13. | 1200Hz-500Hz @ 1Hz (DIN 33 404) | 0-1-1-0-0 | 99 | 17 | |
14. | 400Hz | 0-1-1-0-1 | 95 | 13 | |
15. | 550Hz, 0.7s/1000Hz, 0.33s | 0-1-1-1-0 | 98 | 17 | |
16. | 1500Hz-2700Hz @ 3Hz | 0-1-1-1-1 | 104 | 34 | |
17. | 750Hz | 1-0-0-0-0 | 99 | 18 | |
18. | 2400Hz | 1-0-0-0-1 | 106 | 45 | |
19. | 660Hz | 1-0-0-1-0 | 96 | 17 | |
20. | 660Hz 1.8s ON/1.8s OFF | 1-0-0-1-1 | 96 | 12 | |
21. | 660Hz 0.15s ON/0.15s OFF | 1-0-1-0-0 | 96 | 11 | |
22. | 510Hz, 0.25s/610Hz, 0.25s | 1-0-1-0-1 | 98 | 15 | |
23. | 800/1000Hz 0.5s each (1Hz) | 1-0-1-1-0 | 100 | 21 | |
24. | 250Hz-1200Hz @ 12Hz | 1-0-1-1-1 | 98 | 13 | |
25. | 500Hz-1200Hz @ 0.33Hz | 1-1-0-0-0 | 99 | 17 | |
26. | 2400Hz-2900Hz @ 9Hz | 1-1-0-0-1 | 101 | 40 | |
27. | 2400Hz-2900Hz @ 3Hz | 1-1-0-1-0 | 104 | 40 | |
28. | 500-1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation) | 1-1-0-1-1 | 98 | 10 | |
29. | 800Hz-970Hz @ 9Hz | 1-1-1-0-0 | 99 | 20 | |
30. | 800Hz-970Hz @ 3Hz | 1-1-1-0-1 | 100 | 20 | |
31. | 800Hz, 0.25s ON/1s OFF | 1-1-1-1-0 | 99 | 8 | |
32. | 500Hz-1200Hz, 3.75s/0.25s OFF (AS2220) | 1-1-1-1-1 | 99 | 17 |
Technical Specifications
Specification | Value |
---|---|
Supply Voltage | 17 - 60V DC |
Current | Sounder: 4- 45mA* Beacon: 5mA |
Peak Sound Level | 94 - 106 dBA at 1m* |
Number of tones | 32 |
Frequency Range | 400 - 2850 Hz* |
Rating | Continuous |
Operating Temperature | -25°C to +70°C |
Casing | High Impact Polycarbonate |
IP Rating | IP21/IP65 (deep base) |
Syncronisation | Automatic |
*Depends on selected tone and input voltage. See tone table for details. EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17v DC only.
Compliance and References
Type | CPR Reference | CPD Number | Essential Characteristics | Declared Performance (EN54-3:2001+A1:2002 A2:2006 Subclause) |
---|---|---|---|---|
Fire Alarm Device - Sounder | PSS-0068 Reference 0832-CPR-0297 | PSS-0068/73/79/80 & PSC-0055 :0832-CPD-0297 | Reproducibility | 5.2 |
PSC-0045 Reference 0832-CPR-0546 | PSC-0045/54/62/63/51 :0832-CPD-0546 | Operational performance | 5.3 | |
Durability | 5.4 | |||
Dry Heat (operational) | 5.5 | |||
Dry Heat (endurance) | 5.6 | |||
Cold (operational) | 5.7 | |||
Damp heat, cyclic (operational) | 5.8 | |||
Damp heat, steady state (endurance) | 5.9 | |||
Damp Heat, cyclic (endurance) | 5.10 | |||
SO2 corrosion (endurance) | 5.11 | |||
Shock (operational) | 5.12 | |||
Impact (operational) | 5.13 | |||
Vibration (operational) | 5.14 | |||
Vibration (endurance) | 5.15 | |||
Electrostatic discharge (operational) | 5.16 | |||
Radiated electromagnetic fields (operational) | 5.16 | |||
Voltage transients, fast transient bursts (operational) | 5.16 | |||
Enclosure Protection | 5.17 |
Technical Data Doc: 18-186215
Type A: For indoor use (Shallow Base)
Type B: For outdoor use (Deep Base)
Manufacturer Information
Texecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK.
Tel: +44 1706 233879
Email: sales@klaxonsignals.com
Website: www.klaxonsignals.com
Issue 16 (Dec 2014) INS532-16
Copyright © Texecom Ltd.
Environmental Information (WEEE Directive)
The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimise the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol [symbol: do not dispose in public waste systems] must not be disposed of in European public disposal systems. European users of electrical equipment must now return end-of-life equipment for disposal. Further information can be found on the following website: http://www.recyclethis.info/.