INSTALLATION INSTRUCTIONS
WALL MOUNTED PACKAGE AIR CONDITIONERS
MODELS
- W18A1
- W18L1
- W24A1
- W24L1
- W30A1
- W30L1
- W36A1
- W36L1
- W42A1
- W42L1
- W48A1
- W48L1
- W60A1
- W60L1
© Copyright 2008
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual: 2100-508
Supersedes: NEW
File: Volume III Tab 16
Date: 07-07-08
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult the current edition of each standard.
- National Electrical Code: ANSI/NFPA 70
- Standard for the Installation of Air Conditioning and Ventilating Systems: ANSI/NFPA 90A
- Standard for Warm Air Heating and Air Conditioning Systems: ANSI/NFPA 90B
- Load Calculation for Residential Winter and Summer Air Conditioning: ACCA Manual J
- Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection: ACCA Manual D
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
- ACCA
Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721 - ANSI
American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286 - ASHRAE
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478 - NFPA
National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manufactured under the following U.S. Patent numbers: 5,485,878; 5,301,777; 5,002,116; 4,924,934; 4,875,520; 4,825,936
Wall Mount General Information
Wall Mount Model Nomenclature
The model nomenclature indicates specific features of the unit:
- W: Wall Mounted
- Capacity (e.g., 18, 24, 30, 36, 42, 48, 60): Represents tonnage (1.5 Ton, 2 Ton, etc.).
- A or L: A = Air Conditioner, L = Left Hand Air Conditioner (compressor and controls on the left).
- Volts & Phase (e.g., A=230/208/60/1, B=230/208/60/3, C=460/60/3): Specifies electrical requirements.
- Revisions (e.g., 10): Indicates model revisions.
- KW: Kilowatts of electric heat.
- Ventilation Options (X, B, M, V, E, R): Indicate fresh air intake configurations (Barometric Fresh Air Damper, Blank-off Plate, Motorized Fresh Air Damper, Commercial Ventilator, Economizer, Energy Recovery Ventilator). Note: X, B, M options are without exhaust capability and may require field-supplied barometric relief.
- Coil Options (X, 1, 2, 3): Standard, Phenolic Coated Evaporator, Phenolic Coated Condenser, or both.
- Color Options (X, 1, 2, 4, 5, 6): Beige, White, Mesa Tan, Buckeye Gray, Desert Brown, Dark Bronze.
- Filter Options (X, W, P): One Inch Throwaway (standard), One Inch Washable, or Two Inch Pleated.
- Outlet Options (X, T): Front (standard) or Top Outlet (for W30A, W36A only).
- Control Modules: Refer to Specification Sheet S3397.
Shipping Damage
Upon receipt of equipment, inspect the carton for external signs of shipping damage. If damage is found, contact the carrier immediately, preferably in writing, to request an inspection by their agent.
General
This equipment is intended for installation by trained, experienced service and installation technicians. The refrigerant system is fully assembled and charged, and all internal wiring is complete. The unit is designed for use with or without duct work, with flanges provided for attaching supply and return ducts. These instructions detail the recommended installation method for the air-cooled self-contained unit and its electrical connections.
Read these instructions and any accompanying instructions for separate equipment carefully before beginning installation. Pay particular attention to the "Starting Procedure" and any tags or labels attached to the equipment.
While these instructions serve as a general guide, they do not supersede national or local codes. Consult authorities having jurisdiction before installation. Refer to Page 3 for codes and standards information.
Unit sizing should be based on heat loss calculations using methods from the Air Conditioning Contractors of America (ACCA). Air duct installation must comply with NFPA No. 90A (Other Than Residence Type) and NFPA No. 90B (Residence Type Warm Air Heating and Air Conditioning Systems). Adhere to local codes if they differ from these instructions.
Duct Work
All supply and return ductwork must be properly sized for the equipment's design airflow requirement. ACCA provides excellent guidance for proper sizing. Ductwork not within the conditioned space should be insulated (minimum one inch with a vapor barrier on the outside) to conserve energy and prevent condensation or moisture damage. Flexible joints should be used to minimize noise transmission.
Refer to Table 6 for Maximum ESP of operation for electric heat.
For models W18 & W24, zero inch clearance to the supply duct is permitted. For models W30, W36, W42, W48, and W60, a 1/4 inch clearance to combustible material is required for the first three feet of duct attached to the outlet air frame. Refer to Wall Mounting Instructions and Figures 3 and 4 for details.
Ducts passing through walls must be insulated, and all joints taped or sealed to prevent air or moisture ingress.
Some installations may not require a return air duct. In such cases, a metallic return air grille is required. The grille louvers should not exceed 5/8 inch spacing. Bard Return Air Grille Kits RG2-RG5 or RFG2-RFG5 are recommended. If a return air filter grille is used, ensure the filter is sized for a maximum velocity of 400 fpm.
If no return air duct is used, applicable installation codes may restrict installation to single-story structures.
Filters
A standard 1-inch throwaway filter is included. It is accessible from the outside via a filter access panel. Optional 1-inch washable or 2-inch pleated filters are available. The internal filter brackets can be adjusted for a 2-inch filter by bending two tabs on the support bracket.
Fresh Air Intake
Units are equipped with fresh air inlet slots on the service door. If a fresh air damper assembly is included, it is shipped attached to the unit with the damper blade locked closed. Maximum and minimum blade position stops must be installed for damper operation. See Figure 1.
Capacity, efficiency, and cost of operation information is based on the fresh air blank-off plate being in place for maximum energy efficiency. The blank-off plate can be requested from the factory as a replacement for the fresh air damper.
Condensate Drain
A plastic drain hose extends from the unit's drain pan to the base. Openings in the base allow the hose to pass through. If connected to a drain system, it must be an open or vented type to ensure proper drainage.
Figure 1: Fresh Air Damper
Diagram illustrating the fresh air damper assembly.
Installation Instructions
Wall Mounting Information
- Cut two holes in the wall for supply and return air openings as shown in Figure 3.
- Ensure wood frame walls are strong and rigid enough to support the unit's weight without transmitting vibration.
- Thoroughly inspect concrete block walls to confirm they can support the installed unit's weight.
Mounting the Unit
- Units are secured by wall mounting brackets attached to the outside wall surface on both sides. A bottom mounting bracket, attached to the skid for shipping, is provided for ease of installation but is not mandatory.
- The unit itself requires 0 inch clearance. However, the supply air duct flange and the first 3 feet of supply air duct require a minimum 1/4 inch clearance to combustible material for models W30, W36, W42, W48, and W60. A 1-inch clearance is generally recommended for easier installation and to maintain clearance to combustible material. See Figure 3 for opening size details.
- Locate and mark lag bolt locations and the bottom mounting bracket location (refer to Figure 3).
- Mount the bottom mounting bracket.
- Hook the top rain flashing (attached to the front-right of the supply flange for shipping) under the back bend of the top.
- Position the unit in the opening and secure with 5/16 lag bolts, using 7/8 inch diameter flat washers.
- Secure the rain flashing to the wall and caulk the entire length of the top. See Figure 3.
- For added mounting rigidity, drill and screw or weld the return air and supply air frames/collars to the structural wall (depending on construction). Ensure required clearance is maintained if the wall is combustible.
- For side-by-side installations, maintain a minimum of 20 inches clearance on the right side for access to the control panel and heat strips, and for proper outdoor coil airflow. Additional clearance may be needed to meet local or national codes.
Clearances Required for Service Access and Adequate Condenser Airflow
MODELS | LEFT SIDE | RIGHT SIDE |
---|---|---|
W18A, W24A, W30A, W36A | 15" | 20" |
W18L, W24L, W30L, W36L | 20" | 15" |
W42A, W48A, W60A | 20" | 20" |
W42L, W48L, W60L | 20" | 20" |
NOTE: For side-by-side installation of two (2) W**A models, maintain 20" between units. This can be reduced to 15" by using a W**L model (left side compressor and controls) for the left unit and a W**A model (right side compressor and controls) for the right unit. See W**A Specification S3397 & W**L Specification S3279.
Minimum Clearances Required to Combustible Materials
MODELS | SUPPLY AIR DUCT FIRST THREE FEET | CABINET |
---|---|---|
W18A,L / W24A, L | 0" | 0" |
W30A,L / W36A, L | 1/4" | 0" |
W42A,L / W48A,L / W60A,L | 1/4" | 0" |
Figure 2: Unit Dimensions
Table detailing nominal dimensions for architectural and installation requirements. Diagrams show front, side, and back views of W**A (Right Unit) and W**L (Left Unit) models, indicating key features like access panels, mounting brackets, and air inlets/outlets.
Figure 3A: W18A1, W18L1, W24A1, W24L1 Mounting Instructions
Diagram illustrating mounting details and dimensions for W18 and W24 series units.
Figure 3B: W30A1, W30L1, W36A1, W36L1 Mounting Instructions
Diagram illustrating mounting details and dimensions for W30 and W36 series units, including required clearances to combustible materials.
Figure 3C: W42A1, W42L1, W48A1, W48L1, W60A1, W60L1 Mounting Instructions
Diagram illustrating mounting details and dimensions for W42, W48, and W60 series units, including required clearances to combustible materials.
Figure 4: Electric Heat Clearance
Diagram showing a side section view of the supply air duct for wall-mounted units, highlighting the required 1/4 inch clearance to combustible surfaces for the first 3 feet of ducting. Includes a warning about fire hazard due to insufficient clearance.
Figure 5: Wall Mounting Instructions
Diagrams showing concrete block wall installation and wood frame wall installation, referencing Figure 3 for mounting instructions.
Figure 6: Wall Mounting Instructions
Diagram illustrating unit mounting within a wall opening, showing clearances and attachment points to wall framing. References Figure 2 for unit dimensions.
Figure 7: Common Wall Mounting Installations
Diagrams illustrating various installation scenarios: free air flow (no duct), ducted supply and return at unit, false wall installation, and closet installation.
Wiring - Main Power
Refer to the unit rating plate for wire sizing and maximum fuse or HACR type circuit breaker size. The "Minimum Circuit Ampacity" on the unit indicates the required current carrying capacity for field wiring. Depending on the electric heat KW, two field power circuits may be needed, as indicated on the serial plate. All models require copper conductors only, as marked on the unit and wiring diagrams. Adhere to the National Electrical Code (NEC) and local codes for current carrying capacity data and wiring practices.
Electrical data lists fuse and wire sizes (75°C copper) for all models, including common heater sizes, and the number of field power circuits required for models with heaters.
The unit rating plate specifies the "Maximum Time Delay Relay Fuse" or "HACR" type circuit breaker for proper circuit protection and to prevent nuisance tripping from momentary high starting current.
The disconnect access door can be locked to prevent unauthorized access. To enable locking, bend the tab in the bottom left corner of the disconnect opening outwards; it will then align with the door slot for padlock insertion.
Refer to the "Start Up" section for three-phase scroll compressor start-up information. Consult Tables 4 & 5 for Electrical Specifications.
Wiring - Low Voltage Wiring
Units with dual primary voltage transformers (230/208V, 1-phase and 3-phase) are factory wired to the 240V tap. For 208V operation, reconnect to the 208V tap. The acceptable operating voltage ranges are:
- 240V Tap: 253-216V
- 208V Tap: 220-187V
NOTE: Measure voltage at the field power connection point while the unit operates at full load (maximum amperage).
For wiring size and connections, refer to Wiring Manual 2100-507.
Start Up
THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.
GENERAL:
- Use separate service equipment to avoid cross-contamination of oil and refrigerants.
- Use recovery equipment rated for R-410A refrigerant.
- Use manifold gauges rated for R-410A (800 psi/250 psi low).
- R-410A is a binary blend of HFC-32 and HFC-125.
- R-410A is nearly azeotropic (similar to R-22 and R-12). Charge with liquid refrigerant.
- R-410A operates at 40-70% higher pressure than R-22; R-22 systems cannot withstand this pressure.
- R-410A has zero ozone depletion potential but must be reclaimed due to its global warming potential.
- R-410A compressors use polyolester oil.
- Polyol Ester oil is hygroscopic and absorbs moisture, holding it within the oil.
- A liquid line dryer is essential; deep vacuum alone cannot remove moisture from the oil.
- Limit atmospheric exposure to 15 minutes.
- If compressor removal is necessary, plug it immediately. Purge with nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred, Bard Manufacturing recommends reclaiming, evacuating, and charging to the nameplate charge. Topping off can be done without issues if performed correctly.
With R-410A, refrigerant composition changes are minimal with multiple leaks and recharges. R-410A is nearly an azeotropic blend. The remaining refrigerant can be used after leaks, and the charge can be topped off using charging charts on the inner control panel cover.
REMEMBER: When adding R-410A refrigerant, draw it as a liquid from the cylinder/tank to avoid fractionation and ensure optimal performance. Refer to cylinder instructions for the proper liquid extraction method.
SAFETY PRACTICES:
- Never mix R-410A with other refrigerants.
- Use gloves and safety glasses. Polyol Ester oils can irritate skin, and liquid refrigerant can freeze skin.
- Never use air and R-410A for leak checks, as the mixture can become flammable.
- Do not inhale R-410A. It can cause dizziness, loss of coordination, slurred speech, cardiac irregularities, unconsciousness, and potentially death.
- Do not burn R-410A, as decomposition produces hazardous vapors. Evacuate the area if exposed.
- Use only cylinders rated DOT4BA/4BW 400.
- Never fill cylinders over 80% of total capacity.
- Store cylinders in a cool area, out of direct sunlight.
- Never heat cylinders above 125°F.
- Never trap liquid R-410A in manifold sets, gauge lines, or cylinders. R-410A expands significantly with temperature increases, which can cause bursting.
Start Up (Continued)
IMPORTANT INSTALLER NOTE
For improved start-up performance, wash the indoor coil with a dishwashing detergent.
HIGH PRESSURE SWITCH
All W**A/W**L wall-mounted air conditioner series models have a remote reset for the high and low pressure switches. If tripped, reset by turning the thermostat off and then back on.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like other types, compress in one rotational direction. Single-phase compressors always start and run in the correct direction. Three-phase compressors rotate based on power phasing; reverse rotation can occur if power leads are reversed.
Verify proper rotation by observing suction pressure drop and discharge pressure rise when the compressor is energized. Reverse rotation also causes higher sound levels and substantially reduced current draw compared to tabulated values.
Verification must be done at the time of service. Correcting improper rotation immediately has no negative impact on compressor durability. However, running in reverse for over an hour can negatively impact bearings due to oil pump-out.
NOTE: If a compressor runs in reverse for several minutes, its internal protector will trip.
All three-phase ZP compressors are wired identically internally. Connecting properly phased power leads to the same Fusite terminal ensures correct rotation. Reversing any two line connections will change the direction of rotation.
PHASE MONITOR
Units with three-phase scroll compressors have a 3-phase line monitor to prevent compressor damage from phase reversal. The monitor has two LEDs: a green LED indicates correct phasing (Y signal present), while a red fault LED indicates reversed phases and inhibits compressor operation.
If a fault occurs, reverse two of the supply leads to the unit. Do not reverse factory wires, as this may cause damage.
CONDENSER FAN OPERATION
Applies to W42, W48, and W60 models. The condenser fan motor on 230/208 volt, 60 Hz units is a two-speed motor, factory wired for high speed. It can be reconnected to low speed (red wire) for lower sound levels if ambient conditions permit (see wiring diagram). 50 Hz models are factory wired for low speed.
SERVICE HINTS
- Advise owners to maintain clean air filters and avoid unnecessarily closing supply and return air registers, as this reduces airflow, shortens service life, and increases operating costs.
- Verify all power fuses or circuit breakers are the correct rating.
- Periodically clean the outdoor coil to ensure full and unrestricted airflow.
Sequence of Operation
COOLING
When the thermostat calls for cooling (R-Y circuit), the compressor contactor engages, starting the compressor and outdoor motor. The G circuit (indoor motor) engages automatically or via manual fan switch for constant air circulation. For heating, R-W1 engages the heat contactor and blower. R-W2 engages the second stage heat contactor if equipped.
COMPRESSOR CONTROL MODULE
The standard compressor control module is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Adjustable Delay On Make And Break Timer
On initial power-up or after power interruption, a delay-on-make period begins (2 minutes + 10% of delay-on-break setting). Once this delay expires and pressure switches are closed, the compressor contactor energizes. Upon shutdown, a delay-on-break timer prevents restart until both delay periods have passed. During normal operation without power interruptions, the compressor runs on demand with no delay.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor contactor de-energizes immediately. The unit enters a soft lockout state until the high pressure switch closes and the delay-on-break time expires. If the switch opens again in the same cycle, the unit enters manual lockout, and the alarm relay circuit energizes. Recycling the wall thermostat resets manual lockout.
Low Pressure Switch, Bypass, and Lockout Sequence
If the low pressure switch opens for over 120 seconds, the compressor contactor de-energizes into a soft lockout. The contactor will re-energize after the delay-on-make time expires, regardless of the low pressure switch state. If the switch remains open or opens again for over 120 seconds, the unit enters manual lockout, and the alarm relay circuit energizes. Recycling the wall thermostat resets manual lockout.
Alarm Relay Output
The alarm terminal provides an output connection for applications using an alarm relay. This terminal is powered when the compressor is locked out due to HPC or LPC sequences.
NOTE: High and low pressure switch controls are automatic reset devices. Cut-in/cut-out settings are fixed by model. Soft and manual lockout features are part of the Compressor Control Module.
ADJUSTMENTS
Adjustable Delay on Make and Delay on Break Timer
A potentiometer sets the Delay on Break (DOB) time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after interruptions equals 2 minutes + 10% of DOB:
- 0.5 min (30s) DOB = 123s DOM
- 1.0 min (60s) DOB = 126s DOM
- 2.0 min (120s) DOB = 132s DOM
- 3.0 min (180s) DOB = 138s DOM
- 4.0 min (240s) DOB = 144s DOM
- 5.0 min (300s) DOB = 150s DOM
During routine operation, the compressor runs on demand with no delay.
Typical Settings for Dual Unit Installation:
- Unit 1: DOB set at 2 minutes, DOM is 132 seconds.
- Unit 2: DOB set at 4 minutes, DOM is 144 seconds.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units for observing system operating pressures. A pressure table is provided later in the manual, which must be matched to the unit by model number. See Table 3.
Troubleshooting
FAN BLADE SETTING DIMENSIONS
Figure 8 shows the correct fan blade setting for proper outdoor coil air delivery. Refer to Table 1 for specific unit dimensions. Any service work on the fan or motor area requires checking these dimensions and adjusting the blade position on the motor shaft accordingly.
Figure 8: Fan Blade Setting
Diagram illustrating fan blade setting and dimension 'A'.
TABLE 1: FAN BLADE DIMENSION
Model | Dimension A |
---|---|
W18A1 / W18L1 W24A1 / W24L1 | 1.00" |
W30A1 / W30L1 W36A1 / W36L1 | 1.25" |
W42A1 / W42L1 W48A1 / W48L1 W60A1 / W60L1 | 1.75" |
REFRIGERANT CHARGE
The correct R-410A system charge is indicated on the unit rating plate. Optimal performance is achieved with a charge resulting in the suction line temperature (6" from compressor) shown in Table 2. If charge quantity is uncertain, reclaim the unit and recharge to the factory nameplate quantity.
TABLE 2: REFRIGERANT CHARGE
Model | Rated Airflow | 95°F OD Temperature | 82°F OD Temperature |
---|---|---|---|
W18A1 / W18L1 | 600 | 61-65 | 62-66 |
W24A1 / W24L1 | 800 | 56-60 | 56-60 |
W30A1 / W30L1 | 1000 | 57-61 | 57-61 |
W36A1 / W36L1 | 1100 | 56-60 | 57-61 |
W42A1 / W42L1 | 1400 | 58-62 | 60-64 |
W48A1 / W48L1 | 1550 | 63-67 | 65-69 |
W60A1 / W60L1 | 1650 | 63-67 | 64-68 |
Suction line temperatures in Table 2 are based on 80°F dry bulb / 67°F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling.
REMOVAL OF FAN SHROUD
- Disconnect all power to the unit.
- Remove screws holding both grilles (one on each side) and remove the grilles.
- Remove screws holding the fan shroud to the condenser and bottom (nine screws total).
- Unwire the condenser fan motor.
- Slide the motor, fan blade, and shroud assembly out the left side of the unit.
- Service the motor/fan as needed.
- Reverse steps to reinstall.
TABLE 3: COOLING PRESSURE TABLE
Provides cooling pressure readings based on Air Temperature Entering Outdoor Coil (°F) and Return Air Temperature (DB/WB).
Model | Return Air Temperature | Air Temperature Entering Outdoor Coil °F | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | 120 | |||
W18A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 127 295 | 129 316 | 131 337 | 133 360 | 135 383 | 137 407 | 138 432 | 140 457 | 141 484 | 143 511 |
80 deg. DB 67 deg. WB | Low Side High Side | 136 303 | 138 324 | 140 346 | 142 369 | 144 393 | 146 417 | 148 443 | 150 469 | 151 496 | 153 524 | |
85 deg. DB 72 deg. WB | Low Side High Side | 141 314 | 143 335 | 145 358 | 147 382 | 149 407 | 151 432 | 153 459 | 155 485 | 156 513 | 158 542 | |
W24A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 121 326 | 123 350 | 125 375 | 127 401 | 130 426 | 132 450 | 134 477 | 135 502 | 137 527 | 138 553 |
80 deg. DB 67 deg. WB | Low Side High Side | 129 334 | 132 359 | 134 385 | 136 411 | 139 437 | 141 462 | 143 489 | 144 515 | 146 541 | 148 567 | |
85 deg. DB 72 deg. WB | Low Side High Side | 134 346 | 137 372 | 139 398 | 141 425 | 144 452 | 146 478 | 148 506 | 149 533 | 151 560 | 153 587 | |
W30A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 121 335 | 122 357 | 125 380 | 127 404 | 130 429 | 132 454 | 134 481 | 136 509 | 137 537 | 138 566 |
80 deg. DB 67 deg. WB | Low Side High Side | 129 344 | 131 366 | 134 390 | 136 414 | 139 440 | 141 466 | 143 493 | 145 522 | 146 551 | 148 581 | |
85 deg. DB 72 deg. WB | Low Side High Side | 134 356 | 136 379 | 139 404 | 141 428 | 144 455 | 146 482 | 148 510 | 150 540 | 151 570 | 153 601 | |
W36A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 123 350 | 125 372 | 127 396 | 129 420 | 131 445 | 133 470 | 136 496 | 138 524 | 140 552 | 143 581 |
80 deg. DB 67 deg. WB | Low Side High Side | 132 359 | 134 382 | 136 406 | 138 431 | 140 456 | 142 482 | 145 509 | 148 537 | 150 566 | 153 596 | |
85 deg. DB 72 deg. WB | Low Side High Side | 137 372 | 139 395 | 141 420 | 143 446 | 145 472 | 147 499 | 150 527 | 153 556 | 155 586 | 158 617 | |
W42A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 128 341 | 130 362 | 132 383 | 133 406 | 135 429 | 137 453 | 138 480 | 140 506 | 142 534 | 144 564 |
80 deg. DB 67 deg. WB | Low Side High Side | 137 350 | 139 371 | 141 393 | 142 416 | 144 440 | 146 465 | 148 492 | 150 519 | 152 548 | 154 578 | |
85 deg. DB 72 deg. WB | Low Side High Side | 142 362 | 144 384 | 146 407 | 147 431 | 149 455 | 151 481 | 153 509 | 155 537 | 157 567 | 159 598 | |
W48A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 125 349 | 127 370 | 129 391 | 131 415 | 133 440 | 136 467 | 137 495 | 140 526 | 143 557 | 146 590 |
80 deg. DB 67 deg. WB | Low Side High Side | 134 358 | 136 379 | 138 401 | 140 426 | 142 451 | 145 479 | 147 508 | 150 539 | 153 571 | 156 605 | |
85 deg. DB 72 deg. WB | Low Side High Side | 139 371 | 141 392 | 143 415 | 145 441 | 147 467 | 150 496 | 152 526 | 155 558 | 158 591 | 161 626 | |
W60A1/L1 | 75 deg. DB 62 deg. WB | Low Side High Side | 126 352 | 128 373 | 130 396 | 132 418 | 133 442 | 135 466 | 137 491 | 137 517 | 139 544 | 141 571 |
80 deg. DB 67 deg. WB | Low Side High Side | 135 361 | 137 383 | 139 406 | 141 429 | 142 453 | 144 478 | 146 504 | 147 530 | 149 558 | 151 586 | |
85 deg. DB 72 deg. WB | Low Side High Side | 140 374 | 142 396 | 144 420 | 146 444 | 147 469 | 149 495 | 151 522 | 152 549 | 154 578 | 156 607 |
Low side pressure: ± 2 PSIG
High side pressure: ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated, check condenser fan wiring. See "Condenser Fan Operation".
TABLE 4: Electrical Specifications -- W**A Series
Details electrical specifications for W**A series models, including rated voltage/phase, number of field power circuits, minimum circuit ampacity, maximum fuse/breaker size, field power wire size, and ground wire size for single and dual circuits.
TABLE 5: Electrical Specifications -- W**L Series
Details electrical specifications for W**L series models, including rated voltage/phase, number of field power circuits, minimum circuit ampacity, maximum fuse/breaker size, field power wire size, and ground wire size for single and dual circuits.
TABLE 6: RECOMMENDED AIRFLOW
Model | Rated CFM * | Rated ESP * | Recommended Airflow Range | Factory Speed Connection |
---|---|---|---|---|
W18A, W18L | 550 | .40 | 575-725 | High |
W24A, W24L | 800 | .20 | 700-950 | High |
W30A, W30L | 1000 | .40 | 930-1300 | High |
W36A, W36L | 1100 | .30 | 930-1350 | High |
W42A, W42L | 1400 | .30 | 1600-1150 | High |
W48A, W48L | 1550 | .20 | 1750-1285 | High |
W60A, W60L | 1650 | .30 | 1950-1375 | High |
* Rated CFM and ESP on high speed tap.
TABLE 7: INDOOR BLOWER PERFORMANCE
Provides indoor blower performance data (CFM) for various E.S.P. (Inches H2O) and speed settings for different model series.
E.S.P. In H÷O | W18A/L, W24A/L | W30A/L, W36A/L | W42A/L, W48A/L | W60A/L | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
High Speed | Low Speed | High Speed | Low Speed | High Speed | Low Speed | High Speed | Low Speed | |||||||||
Dry Coil | Wet Coil | Dry Coil | Wet Coil | Dry Coil | Wet Coil | Dry Coil | Wet Coil | Dry Coil | Wet Coil | Dry Coil | Wet Coil | Dry Coil | Wet Coil | Dry Coil | Wet Coil | |
.0 | 1020 | 975 | 1395 | 1315 | 950 | 935 | 1885 | 1800 | 1650 | 1600 | 2200 | 2000 | 1600 | 1450 | ||
.1 | 960 | 905 | 1340 | 1270 | 930 | 915 | 1770 | 1665 | 1550 | 1500 | 2100 | 1900 | 1525 | 1375 | ||
.2 | 865 | 800 | 1285 | 1190 | 910 | 885 | 1635 | 1540 | 1450 | 1400 | 2000 | 1800 | - | - | ||
.3 | 820 | 735 | 1205 | 1100 | 855 | 830 | 1500 | 1400 | 1350 | 1300 | 1875 | 1700 | - | - | ||
.4 | 735 | 650 | 1110 | 1000 | 800 | 755 | 1370 | 1285 | 1300 | 1175 | 1775 | 1600 | - | - | ||
.5 | 615 | 535 | 1005 | 870 | - | - | 1250 | 1150 | - | - | 1650 | 1475 | - | - |
TABLE 8: MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY
Details maximum ESP values for electric heat operation across different models and speeds.
Model | W18A/L, W24A/L | W30A/L, W36A/L | W42A/L, W48A/L | W60A/L | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Outlet | FRONT | FRONT | TOP | FRONT | FRONT | |||||||
Speed | Single | High | Low | High | Low | High | Low | High | Low | |||
-A0Z | .50 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | |||
-A04 | .50 | .45 | ||||||||||
-A05 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | |||
-A08 | .50 | .50 | .50 | |||||||||
-A10 | .50 | .45 | .50 | .35 | .50 | .50 | .50 | .50 | .50 | |||
-A15 | .40 | .35 | .50 | .50 | .50 | .50 | ||||||
-A20 | .50 | .45 | .50 | .40 | ||||||||
-B0Z | .50 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | .50 | |||
-B06 | .50 | .50 | .40 | |||||||||
-B09 | .50 | .50 | .45 | .40 | .50 | .50 | .50 | .50 | .50 | |||
-B15 | .45 | .30 | .50 | .50 | .50 | .50 | ||||||
-B18 | .50 | .50 | .50 | .50 | ||||||||
-C0Z | .50 | .50 | .50 | .50 | ||||||||
-C06 | .50 | .50 | ||||||||||
-C09 | .50 | .40 | .45 | .40 | .50 | .50 | .50 | .50 | .50 | |||
-C15 | .45 | .35 | .50 | .50 | .50 | .50 |
Values are for units with standard 1-inch throwaway or 1-inch washable filters. Derate ESP by .15 for 2-inch pleated filters.
TABLE 9: ELECTRIC HEAT
Provides electric heat specifications (KW, Amps, BTUH) for various voltage and phase configurations.
Models | 240V-1 | 208V-1 | 240V-3 | 208V-3 | 460V-3 | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
KW | Amps | BTUH | Amps | BTUH | Amps | BTUH | Amps | BTUH | Amps | BTUH | |
4 | 16.7 | 13650 | 14.4 | 10240 | |||||||
5 | 20.8 | 17065 | 18.1 | 12800 | |||||||
6 | 14.4 | 20500 | 12.5 | 15360 | 7.2 | 20500 | |||||
8 | 33.3 | 27300 | 28.8 | 20475 | |||||||
9 | 21.7 | 30600 | 18.7 | 23030 | 10.8 | 30700 | |||||
10 | 41.6 | 34130 | 36.2 | 25600 | |||||||
12 | 14.4 | 40950 | |||||||||
15 | 62.5 | 51250 | 54.0 | 38400 | 36.2 | 51200 | 31.2 | 38400 | 18.0 | 51200 | |
18 | 43.3 | 61430 | 37.5 | 46100 | |||||||
20 | 83.2 | 68260 | 72.1 | 51200 |
TABLE 10: OPTIONAL ACCESSORIES
Lists optional accessories, including Heater Kits and Circuit Breakers/Pull Disconnects, with part numbers and applicable model series.
TABLE 11: VENT & CONTROL OPTIONS
Lists available vent and control options with part numbers, descriptions, and applicable model series (W18, W24; W30, W36; W42, W48, W60).