BLAUBERG Box-I Centrifugal Fans

Centrifugal fans in sound-insulated casing for rectangular ducts

Use

Supply and exhaust ventilation systems installed in various premises. Compatible with 400x200 up to 600x350 mm rectangular air ducts.

? Air flow: up to 3515 m³/h (976 l/s)

⚡ Power: from 136 W

? Noise level: from 45 dBA

✅ ErP 2018 compliant

Design

  • Atmospheric resistant galvanized steel casing and impeller.
  • The casing is heat- and sound-insulated with 50 mm mineral wool.
  • The fan is rated for continuous operation.
  • Fitted with standard 20 mm connecting flanges for connection to rectangular air ducts.
  • Access cover on the casing for inspection and maintenance operations.
  • Equipped with a built-in terminal box with a leaded outside sealed electrical lead-in for connection to power mains.

Motor

  • Two- or four-pole asynchronous motor with external rotor and centrifugal impeller with backward curved blades.
  • Single-phase (E) or three-phase (D) motor modifications.
  • Equipped with ball bearings for longer service life.
  • Dynamically balanced impeller.
  • Overheating protection by built-in thermal switches with automatic restart or with leaded outside terminals for connection to external protecting controls.
  • Thermal switch terminal leads are designed for connection to respective circuit of the contacter, overload relay, or autotransformer/thyristor speed controller terminals.

Speed Control

Smooth speed control with an external thyristor controller or step speed control with an external auto transformer (both available upon separate order).

Mounting

  • Designed for mounting inside rectangular air ducts and can be installed in any position.
  • Fan flanges connect to air ducts via bolts inserted into flange holes.
  • Suitable for mounting into round duct at intake flange with a round reducer (available upon separate order).
  • If vibration-absorbing flexible connectors are used, ensure their fixation to mounting structures with supports or brackets.
  • Provide adequate space for accessing the cover for service operations during mounting.

Designation Key

SeriesFlange Size (width x height) [cm]Motor PolesPhaseAccessories
Box-I40x20; 50x25; 50x30; 60x30; 60x352; 4E: single-phase
D: three-phase
Silencers (SD), Filter boxes (KFBK), Electric heaters (KFBT), Water heaters (EKH), Air dampers (WKH), Gravity dampers (SL), Flexible antivibration connectors (VG), Speed controllers (CDTE E... TP, CDR5E D... M)

Dimensions

Diagram Description: A diagram shows a fan unit with dimensions labeled B, B1, B2, B3, H, H1, H2, H3, and L.

TypeBB1B2B3HH1H2H3LWeight [kg]
Box-I 40x20 2E40042044050020022024036050024.5
Box-I 50x25 2E50052054060025027029041064027.6
Box-I 50x30 4E50052054060030032034046068037.2
Box-I 50x30 4D50052054060030032034046068037.2
Box-I 60x30 4E60062064070030032034046068043.5
Box-I 60x30 4D60062064070030032034046068043.5
Box-I 60x35 4E60062064070035037039053073556.2
Box-I 60x35 4D60062064070035037039053073556.2

Technical Data

ParametersBox-I 40x20 2EBox-I 50x25 2EBox-I 50x30 4EBox-I 50x30 4DBox-I 60x30 4EBox-I 60x30 4DBox-I 60x35 4EBox-I 60x35 4D
Voltage [V]1~2301~2301~2303~4001~2303~4001~2303~400
Frequency [Hz]50 / 6050 / 6050 / 6050 / 6050 / 6050 / 6050 / 6050 / 60
Power [W]138 / 200305 / 380140 / 175136 / 165220 / 235230 / 310470 / 700510 / 750
Current [A]0.6 / 0.881.32 / 1.650.57 / 0.730.34 / 0.530.9 / 1.380.52 / 0.732.37 / 3.151.41 / 1.44
Maximum air flow [m³/h (l/s)]930 (258) / 1070 (297)1720 (478) / 1850 (514)1700 (472) / 1855 (515)1380 (383) / 1620 (450)2470 (686) / 2530 (697)2530 (703) / 2630 (731)2950 (820) / 3515 (976)2970 (825) / 3410 (947)
RPM [min⁻¹]2600 / 28502550 / 28301390 / 15301360 / 16001400 / 14501360 / 16001370 / 14601415 / 1610
Sound pressure at 3 m [dBA]45 / 4747 / 5248 / 5047 / 5046 / 4746 / 4547 / 4746 / 46
Transported air temperature [°C]-25...+45-25...+45-25...+45 / -25...+50-25...+65-25...+45-25...+40 / -25...+70-40...+80-40...+55 / -40...+60
IP ratingIPX4IPX4IPX4IPX4IPX4IPX4IPX4IPX4
Motor IP ratingIP44IP44IP44IP44IP44IP44IP44IP44
ErP20182018201820182018201820182018

Performance Data

Sound Power Levels

Detailed sound power level data, categorized by octave frequency bands and overall levels (LpA at 3m and 1m), are provided in the tables below for each model series.

BOX-I 40x20 2E

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]64707066616158517564
LwA to outlet [dBA]66707372696968617968
LwA to environment [dBA]42546160615147376655

BOX-I 50x25 2E

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]62697160636764597565
LwA to outlet [dBA]63687170747171657969
LwA to environment [dBA]40556767645953447261

BOX-I 50x30 4E

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]60687062747268627868
LwA to outlet [dBA]57687272777775708372
LwA to environment [dBA]46586461616056516958

BOX-I 50x30 4D

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]59676961737167617766
LwA to outlet [dBA]56677171757574698171
LwA to environment [dBA]46576360605955506857

BOX-I 60x30 4E

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]70777772666664558171
LwA to outlet [dBA]72778079757574668575
LwA to environment [dBA]43556261625348386756

BOX-I 60x30 4D

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]69757571656563548069
LwA to outlet [dBA]71757877747473658473
LwA to environment [dBA]43546160615248386655

BOX-I 60x35 4E

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]73777370717068588171
LwA to outlet [dBA]72727374787774628373
LwA to environment [dBA]40556163625754466857

BOX-I 60x35 4D

Sound power level, A-weightedOctave frequency bands [Hz]Total
631252505001000200040008000LpA 3mLpA 1m
LwA to inlet [dBA]73767369706968578070
LwA to outlet [dBA]71717374777674628372
LwA to environment [dBA]40546062615653466756

Performance Curves Description

Pressure vs. Airflow: For all models, the performance curves consistently show a decrease in static pressure as airflow increases. Performance varies slightly between 50 Hz and 60 Hz operation, with 60 Hz often providing higher pressure at lower airflows. The curves illustrate the fan's operating range.

Power vs. Airflow: The power consumption curves demonstrate a general increase in power required as airflow increases. Similar to pressure curves, 60 Hz operation typically requires more power than 50 Hz operation for a given airflow rate.

PDF preview unavailable. Download the PDF instead.

bl box i leaflet 2025 07 en Adobe PDF Library 15.0 Adobe InDesign 14.0 (Windows)

Related Documents

Preview Blauberg Box-I Centrifugal Fans for Rectangular Ducts - Technical Specifications
Comprehensive technical specifications, dimensions, performance data, and features for Blauberg Box-I series centrifugal fans designed for sound-insulated operation in rectangular air ducts. Includes detailed information on design, motor, speed control, mounting, accessories, and performance curves.
Preview Blauberg Box-I Centrifugal Fans for Rectangular Ducts - Technical Specifications
Detailed technical specifications, dimensions, and performance curves for Blauberg Box-I series sound-insulated centrifugal fans designed for rectangular duct ventilation systems. Suitable for commercial and industrial HVAC applications.
Preview Blauberg Box-FI Centrifugal Fans: Technical Specifications and Performance Data
Detailed information on Blauberg Box-FI series centrifugal fans for rectangular ducts, including technical specifications, dimensions, sound data, and performance curves. Suitable for industrial ventilation applications.
Preview BLAUBERG Box-F Centrifugal Fans for Rectangular Ducts | Technical Data
Discover the BLAUBERG Box-F series of centrifugal fans, designed for efficient air supply and extraction in rectangular duct systems. This document provides detailed technical specifications, dimensions, and performance curves for HVAC applications.
Preview Blauberg Box-I EC Inline Centrifugal Fan User Manual
User manual for the Blauberg Box-I EC inline centrifugal fan in a sound-insulated casing. Covers safety requirements, purpose, technical data, installation, connection, maintenance, troubleshooting, and manufacturer's warranty.
Preview Blauberg Box Centrifugal Fans for Rectangular Ducts
Technical specifications, dimensions, and performance data for Blauberg Box centrifugal fans designed for rectangular air ducts. Includes application details, construction, motor information, and installation guidelines.
Preview Blauberg Box-I EC Centrifugal Fans: Technical Datasheet
Comprehensive technical specifications, dimensions, and performance data for the Blauberg Box-I EC series of centrifugal fans. These fans feature sound-insulated casings and EC motors, designed for efficient and controllable industrial ventilation systems.
Preview Blauberg Centrifugal Rectangular Duct Fan User Manual
User's manual for Blauberg Centrifugal Rectangular Duct Fans (Box, Box-I, Box-F, Box-FI) covering safety, purpose, delivery set, technical data, mounting, connection, maintenance, troubleshooting, and warranty.