Eaton PT Module Instruction Leaflet

Instruction Leaflet IL01301074E

Supersedes July 2016, Effective January 2019

PT module

Instructions apply to:

WARNING

  1. Only qualified electrical personnel should be permitted to work on the equipment.
  2. Always de-energize primary and secondary circuits if a circuit breaker cannot be removed to a safe work location.
  3. Drawout circuit breakers should be levered (racked) out to the disconnect position.
  4. All circuit breakers should be switched to the off position and mechanism springs discharged.

Failure to follow these steps for all procedures described in this instruction leaflet could result in death, bodily injury, or property damage.

WARNING

The instructions contained in this IL and on product labels have to be followed. Observe the five safety rules:

Disconnect the equipment from the supply. Use only authorized spare parts in the repair of the equipment. The specified maintenance intervals as well as the instructions for repair and exchange must be strictly adhered to prevent injury to personnel and damage to the switchboard.

Power Defense™

FAT-N

Powering Business Worldwide

Section 1. Description

Note: The content of this IL applies to both PXR and Digitrip equipped breakers. Appearance of product may vary.

The Potential Transformer (PT) module is a device used to supply a three phase voltage signal to NF-frame or RF-frame circuit breakers equipped with Digitrip 1150 or PXR programmable trip units.

Specifications:

The output of the module is directly proportional to the input voltage according to the ratio given below (Table 1).

Table 1. Voltage ratios.
INPUT OUTPUT (NORMAL)
208V L-L 1.95V L-N
240V L-L 2.25V L-N
415V L-L 3.89V L-N
440V L-L 4.13V L-N
480V L-L 4.50V L-N
600V L-L 5.63V L-N
690V L-L 6.47V L-N

WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. ALWAYS FOLLOW SAFETY PROCEDURES. EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.

WARNING

OBSERVE ALL RECOMMENDATIONS, NOTES, CAUTIONS, AND WARNINGS RELATING TO THE SAFETY OF PERSONNEL AND EQUIPMENT. OBSERVE AND COMPLY WITH ALL GENERAL AND LOCAL HEALTH AND SAFETY LAWS, CODES, AND PROCEDURES.

Note: The recommendations and information contained herein are based on experience and judgment, but should not be considered to be all-inclusive or to cover every application or circumstance that may arise.

Section 2. Installation

The PT module is to be mounted on a standard 35mm EN DIN rail and connects to the breaker as shown. Figures 2 and 3 show a 3-pole, 3-wire configuration. Figures 4 through 7 show connections for a 3-pole breaker and a 4-pole breaker with an external neutral sensor.

Figure 2. Breakers with Digitrip 1150 trip units - 3-pole, 3-wire.

Figure 3. Breakers with PXR trip units - 3-pole, 3-wire.

Figure 4. Breakers with Digitrip 1150 trip unit - 3-pole, 4-wire.

Figure 5. Breakers with PXR trip units - 3-pole, 4- wire.

Figure 6. Breakers with Digitrip 1150 trip units - 4-pole, 4-wire.

Section 3. Operation

Switches are provided to disconnect each phase from the mains (Figure 9). All three switches must be in the off ("O") position before performing dielectric testing of a system where the PT module is connected. When the test is complete, all switches must be in the on ("I") position for the module to function as intended.

CAUTION

DIELECTRIC TESTING OF A SYSTEM CONTAINING A PT MODULE WITH THE PHASE CONNECTED WILL DAMAGE THE PT MODULE. DISCONNECT ALL OF THE PHASES FROM THE MAINS (BY SELECTING "0") BEFORE TESTING. AFTER TESTING, RETURN ALL PHASE SWITCHES TO THE "I" POSITION.

Figure 7. Breakers with PXR trip units - 4-pole, 4-wire.

The PT module secondary may connect up to 16 breakers using 18 AWG wire for each phase in a daisy-chain configuration and may extend to the furthest breaker in the the chain, to a maximum of 250 feet (Figure 8).

Figure 8. Daisy chain breaker connection of up to 16 breakers.

Figure 9. Line phase switches.

Notes:

Disclaimer of warranties and limitation of liability

The information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation's ("Eaton") experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.

Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.

THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein.

The information contained in this manual is subject to change without notice.

Eaton

Electrical Group

1000 Eaton Boulevard

Cleveland, OH 44122

United States

877-ETN-CARE (877-386-2273)

Eaton.com

2019 Eaton

All Rights Reserved

Printed in USA

Publication No. IL01301074E/LNT26

Part Number: IL01301074EH03

January 2019

Eaton is a registered Trademark

All other Trademarks are property of their respective owners.

PDF preview unavailable. Download the PDF instead.

IL01301074E Adobe PDF Library 15.0

Related Documents

Preview Eaton PXR 20/25 Trip Unit User Manual for Series NRX Circuit Breakers
User manual for the Eaton PXR 20/25 Trip Unit, detailing its protection features, settings, communication capabilities, and maintenance for Series NRX circuit breakers (NF and RF frames).
Preview Eaton Power Defense Molded Case Circuit Breakers: Technical Selection Guide (PT012018EN)
Explore Eaton's Power Defense molded case circuit breakers (MCCBs) with this technical selection guide. Covers specifications, PXR electronic trip units, thermal-magnetic options, certifications (UL, CSA, CCC, IEC), and model selection for diverse electrical applications. Features publication PT012018EN.
Preview Eaton Molded Case Circuit Breakers: Power Defense, Series G, and Series C
Explore Eaton's comprehensive range of Molded Case Circuit Breakers, including the Power Defense, Series G, and Series C lines. This catalog details product specifications, applications, and ordering information for advanced electrical protection solutions.
Preview Installation Instructions for Eaton Series NRX Breaker and Trip Unit Remote Mount CAM Module Adapter
This document provides installation instructions for the Eaton Series NRX Breaker and Trip Unit Remote Mount CAM Module Adapter (IL019001EN). It details kit contents, connection procedures to the NRX circuit breaker and CAM module, and includes descriptions of diagrams illustrating the setup. Essential for proper remote mounting of CAM modules with Series NRX breakers.
Preview Eaton Series NRX Type NF Bus Extension Kit for 65 kA Fixed Front Connect Breaker Installation Instructions
Detailed installation instructions for the Eaton Series NRX Type NF bus extension kit, designed for 65 kA fixed front connect circuit breakers. It includes essential safety warnings, general information about the product, step-by-step assembly procedures, and technical specifications for cable terminals and kits. The instructions cover the proper attachment of bus conductor extensions and cable terminals to the breaker bus adapters, emphasizing correct torque values and safety precautions.
Preview Eaton Series NRX Drawout Cassette Interphase Barrier Installation and Removal Instructions
Comprehensive installation and removal instructions for Eaton Series NRX drawout cassette interphase barriers (Type RF Frame IEC, IZMX40). Includes essential safety warnings and step-by-step procedures for proper installation and maintenance.
Preview Eaton Power Defense Molded Case Circuit Breakers Frame Size 3 (45-600 A) - Product Aid
Detailed product information for Eaton's Power Defense molded case circuit breakers, frame size 3. Includes interrupting ratings, dimensions, weights, terminal specifications, and trip unit options for various applications.
Preview Eaton Magnum LV-Air Circuit Breaker User Manual (1812.900A)
Comprehensive user manual for the Eaton Magnum LV-Air Circuit Breaker (model 1812.900A), detailing installation, operation, maintenance, troubleshooting, and renewal parts. Covers fixed and drawout configurations with electronic tripping systems.