Molded Case Circuit Breakers
Power Defense molded case circuit breakers
Frame size 3 (45-600 A)
Catalog number/product selection
Interrupting ratings
Catalog designator | F kA rms | G kA rms | K kA rms | M kA rms | N kA rms | P kA rms | ||||||
UL/CSA | ||||||||||||
240 Vac | 35 | 65 | 85 | 100 | 150 | 200 | ||||||
480 Vac | 25 | 35 | 50 | 65 | 85 | 100 | ||||||
600 Vac | 14 | 18 | 25 | 35 | 50 | 65 | ||||||
250 Vdc 23 | 10/22 | 10/22 | 10/22 | 22/42 | 22/42 | 22/42 | ||||||
IEC | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics |
240 Vac | 35 | 35 | 55 | 55 | 85 | 85 | 100 | 100 | 150 | 100 | 200 | 150 |
380-415 Vac | 25 | 25 | 36 | 36 | 50 | 50 | 70 | 53 | 70 | 70 | 100 | 70 |
440 Vac | 25 | 20 | 30 | 22.5 | 35 | 35 | 50 | 40 | 70 | 50 | 100 | 50 |
480 Vac | 20 | 20 | 25 | 20 | 35 | 22.5 | 50 | 30 | 65 | 40 | 85 | 40 |
525 Vac | 18 | 5 | 20 | 7.5 | 25 | 10 | 30 | 15 | 35 | 25 | 40 | 25 |
660-690 Vac | 8 | 4 | 10 | 5 | 15 | 7.5 | 20 | 10 | 20 | 10 | 20 | 10 |
250 Vdc 23 | 10/22 | 10/22 | 10/22 | 10/22 | 10/22 | 10/22 | 22/42 | 22/42 | 22/42 | 22/42 | 22/42 | 22/42 |
• UL current limiting. M interrupting rating only current limiting for the 400 A construction breakers.
2 DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using two poles in series.
First rating listed is for 400 A frame, second rating is for 600 A frame.
Dimensions and weights
Approximate dimensions in inches (mm)
Number of poles | Width | Height | Depth |
2 | 5.47 (138.9) | 10.13 (257.1) | 4.30 (109.1) |
3 | 5.47 (138.9) | 10.13 (257.1) | 4.30 (109.1) |
4 | 7.22 (182.9) | 10.13 (257.1) | 4.30 (109.1) |
Approximate shipping weight in lb (kg)
Breaker type | 2-Pole | 3-Pole | 4-Pole |
PDG3 400 A | 8.05 (3.65) | 11.02 (5.00) | 13.77 (6.25) |
PDG3 600 A | 10.43 (4.73) | 12.36 (5.61) | 16.27 (7.39) |
Trip unit ratings
Poles | Continuous current rating | Trip units |
2-, 3-, 4-pole Thermal-magnetic | 100, 125, 150, 175, 200, 225, 250, 300, 350, 400, 500, 600 | TFA, VFA |
3-, 4-pole Electronic | 125, 250, H250, 400, H400, 600, D##, P## adjustable range (45-600) | B2N, E##, D##, P## |
H As the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame.
2 All #s refer to protection and options. Refer to the MCCB catalog or Power Defense™ poster for more information. Direct links are below.
For additional information, visit the resources section available at Eaton.com/PDmccb.
Terminals
Maximum breaker amperes | Breaker frame | Terminal body type | Wire type | Wire class per phase | Number of conductors | AWG/kcmil conductor range | Metric conductor range (mm²) | 3-Pole catalog number |
Standard terminals | ||||||||
300 | 400 | Aluminum Cu/Al | B, C | 1 | 3-350 | 26.7-177 | PDG3X3TA3002 | |
350 | 400 | Aluminum Cu/Al | B, C | 1 | 250-500 | 127-253 | PDG3X3TA3502 | |
400 | 400 | Aluminum Cu/Al | B, C | 2 | 3/0-250 | 85-127 | PDG3X3TA4002 | |
400 | 600 | Aluminum Cu/Al | B, C | 1 | 500-750 | 253-380 | PDG3X3TA401H2 | |
630 | 600 | Aluminum Cu/Al | B, C | 2 | 2-500 | 33.6-253 | PDG3X3TA6302 |
1 No accessories included.
2 Terminal shield included.
Trip units
Description | Specification |
Trip unit | |
Interchangeable trip units | Yes |
Thermal-magnetic (T) | Fixed thermal-adjustable magnetic |
Molded case switch (K) | Fixed magnetic |
Motor circuit protector (M) | Adjustable magnetic only (3-pole) |
Electronic | |
PXR 10 (B) adjustable LSI | LSI, MLSI |
PXR 20 (E) current metering / comm opt. | LSI, LSIG, ALSI, ALSIG |
PXR 25 (P) power metering / comm std. | LSI, LSIG, ALSI, ALSIG, MLSI, MLSIG |
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2024 Eaton
All Rights Reserved
Printed in USA
Publication No. MZ012019EN / Z29833
June 2025
Follow us on social media to get the latest product and support information.
Eaton is a registered trademark.
All other trademarks are property of their respective owners.