Phocos Any-Grid™ series
Compatible Lithium Battery Models: Leoch LFeLi-48100TB, LFeLi-48150TB & LFeLi-48100S
Applicable Any-Grid™ Models: PSW-H-5kW-230/48V, PSW-H-5kW-120/48V, PSW-H-6.5kW-120/48V, PSW-H-8kW-120/48V
Recommended battery settings guide
The document includes images of the Phocos Any-Grid PSW-H Hybrid Inverter Charger and a Leoch LFeLi-48100S (48V 100Ah 4800W) battery module.
1.0 Introduction
This guide provides recommended settings and establishes communication for operating Phocos Any-Grid™ PSW-H series hybrid inverter chargers with Leoch LFeLi-48100TB, LFeLi-48150TB, and LFeLi-48100S battery modules in a 48 Vdc configuration.
When using this guide, charge/discharge settings are automatically negotiated with the battery. For manual settings, a communication cable is not required, but the battery type in the PSW-H settings menu 05 must be set to "User defined" (USE). Users are responsible for selecting settings within battery specifications to preserve warranty.
Installation must follow the Any-Grid "User and Installation Manual" and the Leoch installation manual. Refer to chapter "5.0 Battery Settings and Communication Cable Installation" for connection details.
WARNING: Read and respect all warnings in the installation manuals of the Any-Grid, battery modules, and connected equipment. Installation must be performed by a trained professional.
2.0 Requirements
To proceed with this guide, the following are required:
- Any-Grid PSW-H-5KW-230/48V, PSW-H-5KW-120/48V, PSW-H-6.5KW-120/48V, or PSW-H-8kW-230/48V. Minimum display unit firmware version U2 must be 06.18 or later, with the corresponding U1 firmware for your Any-Grid PSW-H.
- Leoch LFeLi-48100TB, LFeLi-48150TB models:
- Battery communication cable: PSW-H-BAT-CABLE-PYLON-2 (available from Phocos dealers).
- If a dealer cable is unavailable, the PSW-H-BAT-CABLE-PYLON-2 is made of two male RJ45 plugs with the following pin connections:
Any-Grid PSW-H Side | Leoch Battery Side |
---|---|
Pin 8 | 1 |
Pin 7 | 2 |
Pin 6 | 3 |
Pin 5 | 4 |
Pin 4 | 5 |
Pin 3 | 6 |
Pin 2 | 7 |
Pin 1 | 8 |
Ensure the cable is correctly oriented between the battery and PSW-H unit.
WARNING: Do not use the inverter cable included with Leoch batteries. Wiring your own cable according to the pinout is at your own risk. Damage due to incorrect wiring, orientation, or cable is not covered by warranty.
2.0 Requirements (Continued)
- LFeLi-48100S model:
- Battery communication cable: Supplied with the battery, requires the battery side terminal block connection as shown below.
Any-Grid PSW-H Side | Leoch Battery Side (48100S) |
---|---|
Pin 8 | A |
Pin 7 | |
Pin 6 | |
Pin 5 | B |
Pin 4 | |
Pin 3 | |
Pin 2 | C |
Pin 1 |
Ensure the cable is correctly oriented between the battery and PSW-H unit.
WARNING: Do not use the inverter cable included with Leoch batteries. Wiring your own cable according to the pinout is at your own risk. Damage due to incorrect wiring, orientation, or cable is not covered by warranty.
- One of the battery modules defined in "1.0 Introduction".
3.0 System Overview
The system overview diagram illustrates the components: optional PV Panels, Leoch batteries, a Phocos Any-Grid Hybrid Inverter Charger, AC Loads, and optional Public Grid or Generator inputs.
4.0 Battery Sizing
To maintain the full battery warranty, each battery module should not exceed 100 Adc continuous current (refer to Leoch manual). It is recommended to use at least 2 battery modules in parallel for sufficient continuous and peak current for a single PSW-H-5KW at full power. For multiple Any-Grid units, increase the number of batteries accordingly. Using too few batteries may void your Leoch battery warranty.
Batteries must be wired in parallel to form a single large battery bank for multiple Any-Grids, with a nominal voltage of 48 Vdc. All Any-Grids must connect to a single battery array.
5.0 Battery Settings and Communication Cable Installation
CAUTION: Before connecting battery modules to the Any-Grid(s), follow these installation instructions step-by-step. Keep the battery, AC input source, AC output loads, and PV input disconnected until instructed.
Any battery settings will be overwritten if the communication cable is used. Manual settings are at your own risk.
- Make the battery communication cable as described in chapter 2. This cable is specifically designed for connecting the Any-Grid PSW-H to Leoch batteries.
- Ensure all battery modules are turned off.
- Set the battery DIP switches as described in the battery manual, based on the number and arrangement of batteries.
- Ensure battery modules are still off. Connect the Any-Grid(s) to the battery power terminals (positive and negative) with correct polarity.
CAUTION: Incorrect battery polarity can damage the Any-Grid and battery, which is not covered by warranty.
LFeLi-48100TB, LFeLi-48150TB models: Connect the battery communication cable to the master battery's RS-485A port and the Any-Grid's BMS port. Ensure correct cable ends are connected.
LFeLi-48100S model: Connect the battery communication cable to the master battery's RS-485A port and the Any-Grid's BMS port. Ensure correct cable ends are connected.
The document shows images illustrating the connection ports on the Any-Grid (RS232, RS485-A, RS485-B, RESET, DRY CONTACT) and the Master Battery (RS-232, RS485-A, RS485-B, RS485-C, CAN).
- Ensure battery modules are wired as per the Leoch battery manual. Turn on batteries, using pre-charge to avoid sudden inrush current.
- Ensure the Any-Grid's "ON/OFF" load power button is in the ON position (depressed), with no loads connected.
An image shows the Any-Grid front panel with the ON/OFF load power button.
The Any-Grid(s) should now be running, with displays on.
- Apply the following settings on the Any-Grid connected to the Leoch battery bank via the communication cable. Refer to the Any-Grid manual, chapter Operation → Device Operation Settings → Settings menus.
- Battery type: Menu 05: User-defined battery (“USE”)
- Maximum total battery charging current: Menu 02: 80A or 0.5 x total battery bank capacity (whichever value is lower)
- Voltage set-point to switch from Off-Grid mode to Grid mode (when "SBU priority" or "Solar / PV first" is selected in settings menu 01): Menu 12: 47 Vdc or higher
- Voltage set-point to switch from Grid mode to Off-Grid mode (when "SBU priority" or "Solar / PV first" is selected in settings menu 01): Menu 13: 52 Vdc or lower
- Boost battery charging voltage: Menu 26: 52.7 Vdc
- Floating battery charging voltage: Menu 27: 51.5 Vdc
- Low voltage disconnect: Menu 29: 46.0 Vdc
- Boost battery charging duration: Menu 32: 120 min
- Battery equalization: Menu 33: Disabled
- Maximum discharging current: Menu 41: Disabled
- Once settings are applied, exit the settings menu by pressing the 'X' symbol to return to the main view.
- Activate circuit breakers or insert fuses to energize inputs and outputs on the Any-Grid in the following order (skip any not connected):
- a) AC input
- b) PV input
- c) AC output
- If using more than one Any-Grid, this procedure ensures the unit connected to the Leoch battery communicates with the Leoch battery BMS. Other connected Any-Grid units will automatically have their battery type set to “User-defined”, which is normal.
The commissioning and programming of battery-related settings for the Any-Grid is now complete.