B6BV Series Air Handler
13/14 SEER Residential System | 18,000 - 60,000 Btuh (Heat Pump & Air Conditioner)
Product Overview
The B6BV series of air handlers, when combined with Nortek Global HVAC's heat pump or air conditioner, offer a full line of quality, split system heating and cooling equipment.
Features and Benefits
- Durable, Attractive Cabinet: Designed using galvanized steel with a polyester urethane finish that endures 950 hours of salt spray per ASTM Std. B117. The plastic drain pan is corrosion-resistant.
- Multi-Speed: Provides flexibility of installation.
- Ease-of-Service: Features plug-in wire connections and a built-in filter rack for easy servicing.
- Circuit Board: Incorporates a blower time delay relay, low voltage terminal strip, and heat-strip sequencing.
- Air Handler Control Board: Manages time-sequencing of heat stages with field-selectable sequence timing.
- Breaker Accessibility: Breaker is accessible from the front of the unit when a heater is applied.
- No Fasteners on Sides or Back: Smooth surfaces facilitate ease of installation.
- Cabinet Insulation: 1" insulation with an R-value of 4.2 contributes to quiet operation and prevents cabinet sweating in demanding applications.
- Designed to meet the requirements 610.2.A.2: Meets Florida building code requirements for air leakage.
Model Identification Code
The model identification code follows a specific format to denote various features:
Indoor Air Handler | Design Series | Motor (B = 3, 4 or 5-speed) | Configuration (V = Vertical) | Metering Device (0 = Piston, T = R-22 TXV, X = R-410A TXV) | Cabinet Identifier (A = 14 1/4" Width, B = 19 3/4" Width, C = 22 1/2" Width) | Electrical Code (K = 208/230-60-1)
Electrical Data
Provides electrical specifications for different cabinet sizes and voltages.
Model | Cabinet | Capacity | Voltage 240 - Min. Circuit Amp. | Voltage 240 - Max. Over-current Rating | Voltage 208 - Min. Circuit Amp. | Voltage 208 - Max. Over-Current Rating | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
A | B | C | A | B | C | A | B | C | A | B | C | ||||
B | 10 KW | 53.6 | - | - | 53.6 | 60.0 | 60.0 | 47.0 | - | - | 50.0 | 50.0 | |||
B | 15 KW | 56.6 | 25.0 | - | 60.0 | 80.0 | 30.0 | 47.0 | 21.7 | - | 68.6 | 50.0 | 25.0 | 70.0 | |
C | 20 KW | 56.3 | 50.0 | - | 78.6 | 60.0 | 30.0 | 106.3 | 50.1 | 43.3 | 93.4 | 60.0 | 45.0 | 100.0 |
Accessories
Description | Cabinet Size | |
---|---|---|
B | C | |
Downflow Plenum Connector, 6.25" | 913840 | 914969 |
Downflow Plenum Connector, 8.25" | 913841 | 914970 |
Downflow Plenum Connector, 10.25" | 913842 | 914971 |
Upflow Pedestal Mounting Stand | 913872 | 913873 |
Downflow Coil Adaptor | 919321 | 919322 *919323 |
* Use when installing B width coil in C width cabinets
Dimensions
Diagrams illustrating the dimensions of the B6BV series air handler.
Detail "D" shows specific measurements for ports and openings.
Overall Dimensions:
- Height ("H"): Varies by model (e.g., 49-5/16" for 10x8, 55-15/16" for 11x10).
- Width ("W"): Varies by model (e.g., 19-11/16" for 10x8, 22-7/16" for 11x10).
- Depth: Approximately 22".
Specifications Table:
Model Number B6BV- | -000K-B-10 | -000K-B-15 | -000K-C-20 |
---|---|---|---|
Nominal cooling capacity - Btuh ¹ | 10 x 8 | 10 x 8 | 11 x 10 |
Motor Hp-speeds-type | 1/3-4-PSC | 1/3-4-PSC | 3/4-16-ECM |
Filter Size (supplied internal filter rack) ² | 18x20x1 | 18x20x1 | 20x20x1 |
Approximate Shipping Weight, lbs | 90 | 90 | 116 |
Height, "H", in. | 49-5/16 | 49-5/16 | 55-15/16 |
Width, "W", in. | 19-11/16 | 19-11/16 | 22-7/16 |
Supply Air Outlet Dimension, in. | 12-7/8 x 18-1/4 | 12-7/8 x 18-1/4 | 12-7/8 x 21 |
¹ See current AHRI Directory for certified combinations and ratings.
² Filter is not supplied with unit.
Blower Performance Data
Provides airflow settings and performance data for various configurations.
Minimum Heating Airflow Settings (in CFM)
Cabinet | Nominal Electric Heat KW | ||
---|---|---|---|
10 | 15 | 20 | |
C | 1200 | 1400 | 1600 |
Blower Performance Table
Model | Nominal Blower Size | Nominal Motor Size | Number of Speeds | Ext. Static Pressure (in W.C.) | Low | Medium Low | Medium High | High |
---|---|---|---|---|---|---|---|---|
B6BV B - Cabinet | 10 x 8 | 1/3 hp | 4-sp | 0.1 | 800 | 1090 | 1265 | 1405 |
0.2 | 780 | 1080 | 1255 | 1395 | ||||
0.3 | 760 | 1060 | 1240 | 1375 | ||||
0.4 | 740 | 1095 | 1215 | 1350 | ||||
0.5 | 715 | 1020 | 1190 | 1310 |
NOTES:
- Airflow is shown in cfm, +/- 5%.
- All airflows are measured without filter and with dry coil. For filter velocity of 300 ft./min. subtract .08" external static pressure. For wet coil, subtract .1" external static pressure.
- See unit nameplate or installation instructions for maximum recommended external static pressure.
Cooling or Heating Airflow (CFM)
Switch Setting | Dry Coil ESP | ||||||||
---|---|---|---|---|---|---|---|---|---|
0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | ||
1/5 2/6 3/7 4/8 | |||||||||
0 0 0 0 | 710 | 580 | 395 | ||||||
1 0 0 0 | 830 | 690 | 675 | 530 | 505 | ||||
0 1 0 0 | 930 | 875 | 710 | 665 | 560 | 530 | |||
1 1 0 0 | 1065 | 1015 | 900 | 840 | 800 | 705 | 665 | 635 | |
0 0 1 0 | 1185 | 1115 | 1010 | 960 | 925 | 875 | 830 | 745 | |
1 0 1 0 | 1275 | 1220 | 1175 | 1120 | 1060 | 970 | 930 | 890 | |
B6BV C - cabinet | 0 1 1 0 | 1365 | 1350 | 1255 | 1200 | 1150 | 1105 | 1060 | 1025 |
1 1 1 0 | 1480 | 1430 | 1370 | 1325 | 1265 | 1225 | 1185 | 1140 | |
0 0 0 1 | 1560 | 1535 | 1485 | 1430 | 1375 | 1335 | 1285 | 1240 | |
1 0 0 1 | 1650 | 1600 | 1545 | 1500 | 1450 | 1405 | 1360 | 1305 | |
0 1 0 1 | 1730 | 1685 | 1660 | 1610 | 1570 | 1520 | 1470 | 1420 | |
1 1 0 1 | 1785 | 1740 | 1695 | 1645 | 1615 | 1545 | 1510 | 1470 | |
0 0 1 1 | 1865 | 1820 | 1785 | 1750 | 1695 | 1655 | 1605 | 1560 | |
1 0 1 1 | 1920 | 1890 | 1850 | 1805 | 1765 | 1715 | 1675 | 1640 | |
0 1 1 1 | 2010 | 1965 | 1960 | 1900 | 1850 | 1810 | 1775 | 1730 | |
1 1 1 1 | 2065 | 2020 | 1985 | 1955 | 1915 | 1880 | 1840 | 1810 |
NOTE: 0 = OFF, 1 = ON
Certifications and Warranty
The product is certified by ETL, AHRI, and NATE. Nortek Global HVAC, LLC provides a limited warranty for parts that fail in normal use and service. For full warranty details, contact a local installer or the Nortek Global HVAC, LLC warranty department.
Important Note: Before purchasing, read important energy cost and efficiency information available from your retailer. Specifications and illustrations are subject to change without notice.