Unitronics Vision PLC+HMI Installation Guide
General Description
The Unitronics Vision PLC+HMI series are micro-PLC+HMIs, which are rugged programmable logic controllers with built-in operating panels. Detailed installation guides, including I/O wiring diagrams, technical specifications, and additional documentation, are available in the Technical Library on the Unitronics website: https://unitronicsplc.com/support-technical-library/.
Product Models and Features
Item | V130-RA22 / V130J-RA22 | V350-RA22 / V350J-RA22 | V430J-RA22 |
---|---|---|---|
On-board I/O | Model Dependent | Model Dependent | Model Dependent |
Screen | 2.4" Monochrome | 3.5" Color Touch | 4.3" Color Touch |
Keypad | Yes | None | Yes |
Function Keys | None | Yes | Yes |
Com Port, Built-in | |||
RS232/485 | Yes | Yes* | Yes* |
USB device, mini-B | None | Yes* | Yes* |
Com Ports, separate order, user-installed |
The user may install a CANbus port (V100-17-CAN), and one of the following:
|
* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
Standard Kit Contents
Item | V130-RA22 / V130J-RA22 | V350-RA22 / V350J-RA22 | V430J-RA22 |
---|---|---|---|
Controller | Yes | Yes | Yes |
Terminal Blocks | Yes | Yes | Yes |
Battery (installed) | Yes | Yes | Yes |
Slides (2 sets of key labels) | None | None | None |
Mounting Brackets | Yes (2 parts) | Yes (2 parts) | Yes (4 parts) |
Rubber Seal | Yes | Yes | Yes |
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol | Meaning | Description |
---|---|---|
! | Danger | The identified danger causes physical and property damage. |
! | Warning | The identified danger could cause physical and property damage. |
! | Caution | Use caution. |
- Before using this product, the user must read and understand this document.
- All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
- Please dispose of this product according to local and national standards and regulations.
- Only qualified service personnel should open this device or carry out repairs.
- Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
- Do not attempt to use this device with parameters that exceed permissible levels.
- To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
- Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the standards given in the product's technical specification sheet.
- Do not place in water or let water leak onto the unit.
- Do not allow debris to fall inside the unit during installation.
- Ventilation: 10mm space required between controller's top/bottom edges & enclosure walls.
- Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J
Front View: 109mm (4.29") width x 114.1mm (4.49") height
Side View: 59.6mm (2.346") depth, with a 6.3mm (0.248") bezel width.
* Note that for models V130/V350, the bezel width is up to 8.4 mm (0.33").
Dimensions: V430J
Front View: 136mm (5.35") width x 105.1mm (4.13") height
Side View: 61.3mm (2.41") depth, with a 7.3mm (0.29") bezel width.
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
- Make a panel cut-out of the appropriate size.
- Slide the controller into the cut-out, ensuring that the rubber seal is in place.
- Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
- Tighten the bracket's screws against the panel. Hold the bracket securely against the unit while tightening the screw.
- When properly mounted, the controller is squarely situated in the panel cut-out as shown in the accompanying figures.
Cut-out Dimensions:
Model | Cut-out | View area |
---|---|---|
V130/V130J | 92x92 mm (3.622"x3.622") | 58x30.5mm (2.28"x1.2") |
V350/V350J | 92x92 mm (3.622"x3.622") | 72x54.5mm (2.95"x2.14") |
V430J | 122.5x91.5 mm (4.82"x3.6") | 96.4x55.2mm (3.79"x2.17") |
DIN-rail Mounting (V130/V350/V130J/V350J)
- Snap the controller onto the DIN rail as shown in the figure to the right.
- When properly mounted, the controller is squarely situated on the DIN-rail as shown in the figure to the right.
UL Compliance
The following section is relevant to Unitronics' products that are listed with the UL.
UL Listed for Hazardous Locations
The following models are UL listed for Hazardous Locations:
- V130-33-R34, V130-J-R34, V130-T4-ZK1, V350-35-RA22, V350-J-RA22, V350-35-R34, V350-J-R34, V430-J-R34
UL Listed for Ordinary Location
The following models are UL listed for Ordinary Location:
- V130-33-B1,V130-J-B1,V130-33-TA24,V130-J-TA24,V130-33-T38,V130-J-T38
- V130-33-TR20,V130-J-TR20,V130-33-TR34,V130-J-TR34,V130-33-RA22,V130-J-RA22,
- V130-33-TRA22,V130-J-TRA22,V130-33-T2,V130-J-T2,V130-33-TR6,V130-J-TR6,V130-33-R34,
- V350-35-B1, V130-T4-ZK1, V350-J-B1,V350-35-TA24,V350-J-TA24,V350-35-T38,V350-J-T38,
- V350-35-TR20,V350-J-TR20,V350-35-TR34,V350-J-TR34,V350-35-TRA22,V350-J-TRA22,
- V350-35-T2,V350-J-T2,V350-35-TR6,V350-J-TR6,V350-S-TA24,V350-JS-TA24,V350-35-RA22,
- V350-J-RA22,V350-35-R34, V430-J-B1,V430-J-TA24,V430-J-T38, V430-J-R34,V430-J-RH2,
- V430-J-TR34,V430-J-RA22,V430-J-TRA22,V430-J-T2,V430-J-RH6
UL Ordinary Location Mounting
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface of Type 1 or 4 X enclosures.
UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class I, Division 2, Groups A, B, C and D
This note relates to all Unitronics products that bear the UL symbols used to mark products that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
- This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-hazardous locations only.
- Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction.
- WARNING—Explosion Hazard—substitution of components may impair suitability for Class I, Division 2.
- WARNING – EXPLOSION HAZARD – Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
- WARNING – Exposure to some chemicals may degrade the sealing properties of material used in Relays.
- This equipment must be installed using wiring methods as required for Class I, Division 2 as per the NEC and/or CEC.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
- Programmable controllers, Models: V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34, V350-J-R34
When these specific products are used in hazardous locations, they are rated at 3A res. Except for models V430-J-R34, V130-33-R34, V130-J-R34, V130-T4-ZK1 and V350-35-R34, V350-J-R34, when these specific products are used in non-hazardous environmental conditions, they are rated at 5A res, as given in the product's specifications.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or both, neither the SD card slot nor the USB port are intended to be permanently connected, while the USB port is intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the battery unless the power has been switched off, or the area is known to be non-hazardous.
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data when changing the battery while the power is switched off. Date and time information will also need to be reset after the procedure.
UL des zones ordinaires
Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de protection 1 ou 4X
Certification UL des automates programmables, pour une utilisation en environnement à risques, Class I, Division 2, Groups A, B, C et D
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
- Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et D, ou dans Non-dangereux endroits seulement.
- Le câblage des entrées/sorties doit être en accord avec les méthodes de câblage selon la Classe I, Division 2 et en accord avec l'autorité compétente.
- AVERTISSEMENT: Risque d'Explosion – Le remplacement de certains composants rend caduque la certification du produit selon la Classe I, Division 2.
- AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue pour être non dangereuse.
- AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés des matériaux utilisés pour l'étanchéité dans les relais.
- Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I, Division 2 NEC et/ou CEC.
Montage de l'écran
Pour les automates programmables qui peuvent aussi être monté sur l'écran, pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de type 1 ou de type 4X.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
- Automates programmables, modèles : V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34,V350-J-R34
Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent un courant de 3A charge résistive.
Excepté les modèles: V430-J-R34, V130-33-R34,V130-J-R34, V130-T4-ZK1 et V350-35-R34, V350-J-R34 lorsque ces produits spécifiques sont utilisés dans un environnement non dangereux, ils sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la programmation uniquement.
Retrait / Remplacement de la batterie
Lorsqu'un produit a été installé avec une batterie, retirez et remplacez la batterie seulement si l'alimentation est éteinte ou si l'environnement n'est pas dangereux.
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les informations sur la date et l'heure devront également être réinitialisées après la procédure
Wiring
General Wiring Precautions:
- ! Do not touch live wires.
- Install an external circuit breaker. Guard against short-circuiting in external wiring.
- Use appropriate circuit protection devices.
- Unused pins should not be connected. Ignoring this directive may damage the device.
- Double-check all wiring before turning on the power supply.
- Caution To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
- Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break.
- Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring:
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm² –3.31 mm²).
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm² – 1.31 mm²).
- Strip the wire to a length of 7±0.5mm (0.270–0.300“).
- Unscrew the terminal to its widest position before inserting a wire.
- Insert the wire completely into the terminal to ensure a proper connection.
- Tighten enough to keep the wire from pulling free.
I/Os
V130/V350/V130J/V350J/V430J-RA22 models comprise a total of 12 inputs, 8 relay outputs and 2 analog outputs.
V130/V350/V130J/V350J/V430J-TRA22 models comprise a total of 12 inputs, 4 relays outputs, 4 npn outputs and 2 analog outputs.
Input Functionality
Input functionality can be adapted as follows:
- 12 inputs may be used as digital inputs. They may be wired, in a group, and set to either npn or pnp via a single jumper.
- In addition, according to jumper settings and appropriate wiring:
- Inputs 5 and 6 can function as either digital or analog inputs.
- Input 0 can function as high-speed counter, as part of a shaft-encoder, or as normal digital input.
- Input 1 can function as either counter reset, as part of a shaft-encoder, or as normal digital input.
- If input 0 is set as high-speed counters (without reset), input 1 can function as normal digital input.
- Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; Input 11 can also serve as the CM signal for PT100.
Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O jumpers, you must open the controller according to the instructions beginning on page 13.
! Incompatible jumper settings and wiring connections may seriously damage the controller.
Digital Inputs 0-11: Set Type
Set to | JP12 (all Inputs) |
---|---|
npn (sink) | A |
pnp (source)* | B |
Inputs 7/8: Set Type - Digital or RTD/TC #1
Set to | JP1 | JP2 | JP3 |
---|---|---|---|
Digital* | A | A | A |
Thermocouple | B | B | B |
PT100 | B | A | B |
Inputs 9/10: Set Type - Digital or RTD/TC #0
Set to | JP5 | JP6 | JP7 |
---|---|---|---|
Digital* | A | A | A |
Thermocouple | B | B | B |
PT100 | B | A | B |
Input 11: Set Type - Digital or CM for PT100
Set to | JP11 |
---|---|
Digital* | A |
CM for PT100 | B |
Input 5: Set Type - Digital or Analog #3
Set to | JP4 | JP10 |
---|---|---|
Digital* | A | A |
Voltage* | B | A |
Current | B | B |
Input 6: Set Type - Digital or Analog #2
Set to | JP8 | JP9 |
---|---|---|
Digital* | A | A |
Voltage* | B | A |
Current | B | B |
Analog Output 0: Set to Voltage/Current
Set to | JP13 |
---|---|
Voltage* | A |
Current | B |
Analog Output 1: Set to Voltage/Current
Set to | JP14 |
---|---|
Voltage* | A |
Current | B |
*Default settings
I/O Wiring Diagrams
npn (sink) Input
- Input wiring: Diagram showing 24VDC, +V, OV connections to inputs 0-15, CM, PT, AN.
- HSC input wiring: Diagram showing 24VDC, +V, OV connections to inputs 0-3 for High-speed Counter with Reset.
pnp (source) Input
- Input wiring: Diagram showing 24VDC, +V, OV connections to inputs 0-15, CM, PT, AN.
- HSC input wiring: Diagram showing 24VDC, +V, OV connections to inputs 0-3 for High-speed Counter with Reset.
Shaft-encoder
- Diagram showing 24VDC, +V, OV connections to inputs 0-15, CM, PT, AN for Shaft-encoder input.
Analog Input
Analog input wiring, current (2/3 wire)
- Diagram showing 24VDC, +V, OV connections to analog inputs AN2, AN3, with connections for 2-wire and 3-wire current transmitters.
Analog input wiring, current (4-wire), and voltage
- Diagram showing 24VDC, +V, OV connections to analog inputs AN2, AN3, with connections for 4-wire current transmitters and voltage sources.
Shields should be connected at the signal's source.
The 0V signal of the analog input must be connected to the controller's 0V.
Thermocouple
Type | Temp. Range | Wire Color (ANSI - USA) | Wire Color (BS1843 - UK) |
---|---|---|---|
mV | -5 to 56mV | +Grey | +None |
B | 200 to 1820°C (300 to 3276°F) | +Red | +Violet |
E | -200 to 750°C (-328 to 1382°F) | -Red | -Blue |
J | -200 to 760°C (-328 to 1400°F) | +White | +Yellow |
K | -200 to 1250°C (-328 to 2282°F) | +Red | +Brown |
N | -200 to 1300°C (-328 to 2372°F) | -Red | -Blue |
R | 0 to 1768°C (32 to 3214°F) | +Orange | +Orange |
S | 0 to 1768°C (32 to 3214°F) | +White | +White |
T | -200 to 400°C (-328 to 752°F) | +Red | -Blue |
Notes on Thermocouple Inputs:
- Thermocouple 0: use Input 9 as negative input and 10 as positive.
- Thermocouple 1: use Input 7 as negative input and 8 as positive.
RTD Inputs
PT100 (Sensor 0): use Input 9 and 10, related to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to CM signal.
4 wire PT100 can be used by leaving one of the sensor leads unconnected.
- 2 Wire connection: Diagram for PT100 #1.
- 3 Wire connection: Diagram for PT100 #0.
- 4 Wire connection: Diagram for PT100 #1.
Analog Outputs
- Diagram showing connections for Analog Outputs A1, A0, OV.
npn Outputs (TRA22)
- Diagram showing connections for npn outputs HS, HS, HS, HS, OV, 03, 02, 01, 00.
Relay Outputs
- RA22: Diagram showing connections for relay outputs.
- TRA22: Diagram showing connections for relay outputs.
Power Supply
The controller requires an external 24VDC power supply.
- The power supply must include double insulation. Outputs must be rated as SELV/PELV/Class2/Limited Power.
- Use separate wires to connect the functional earth line (pin 3) and the 0V line (pin 2) to the system earth ground.
- Install an external circuit breaker. Guard against short-circuiting in external wiring.
- Double-check all wiring before turning on the power supply.
- Do not connect either the 'Neutral' or 'Line' signal of the 110/220VAC to the device's 0V pin.
- In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the device to a regulated power supply.
Earthing the PLC+HMI
To maximize system performance, avoid electromagnetic interference by:
- Mounting the controller on a metal panel.
- Connect each common and ground connection directly to the earth ground of your system.
- For ground wiring uses the shortest and thickest possible wire.
Communication
Communication Ports
- Port 1: 1 channel, RS232/RS485 and USB device (V430/V350/V350J only).
- Galvanic isolation: No
- Baud rate: 300 to 115200 bps
- RS232: Input voltage: ±20VDC absolute maximum. Cable length: 15m maximum (50').
- RS485: Input voltage: -7 to +12VDC differential maximum. Cable type: Shielded twisted pair, in compliance with EIA 485. Cable length: 1200m maximum (4000'). Nodes: Up to 32.
- USB device (V430/V350/V350J only): Port type: Mini-B. Specification: USB 2.0 compliant; full speed. Cable: USB 2.0 compliant; up to 3m.
- Port 2 (optional): See Note 13. Available port types: RS232/RS485 isolated/non-isolated, Ethernet, CANbus.
Notes:
- 12. This model is supplied with a serial port: RS232/RS485 (Port 1). The standard is set to either RS232 or RS485 according to jumper settings. Refer to the product's Installation Guide.
- 13. The user may order and install one or both of the following modules: An additional port (Port 2). Available port types: RS232/RS485 isolated/non-isolated, Ethernet, CANbus port. Port module documentation is available on the Unitronics website.
- 14. Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications via Port 1. When the PC is disconnected, RS232/RS485 resumes.
RS232/RS485 Port
- Caution Turn off power before making communications connections.
- Always use the appropriate port adapters.
- Signals are related to the controller's 0V; the same 0V is used by the power supply.
- Caution The serial port is not isolated. If the controller is used with a non-isolated external device, avoid potential voltage that exceeds ± 10V.
- Use RS232 to download programs from a PC, and to communicate with serial devices and applications, such as SCADA.
- Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show the PLC port signals.
RS232 Pin # | Description | RS485** Pin # | Description | Controller Port |
---|---|---|---|---|
1* | DTR signal | 1 | A signal (+) | Pin #1 |
2 | 0V reference | 2 | (RS232 signal) | |
3 | TXD signal | 3 | (RS232 signal) | |
4 | RXD signal | 4 | (RS232 signal) | |
5 | 0V reference | 5 | (RS232 signal) | |
6* | DSR signal | 6 | B signal (-) |
* Standard programming cables do not provide connection points for pins 1 and 6.
** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A, and Pin 6 (DSR) signal is used for signal B.
Note that it is possible to establish a PC to PLC connection using RS232 even when the PLC is set to RS485 (this eliminates the need to open the controller to set jumpers). To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232 programming cable. Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard case).
Setting RS232/RS485 Communication Parameters, V130/V350/V130J/V350J
This port may be set to either RS232 or RS485 via jumper. The accompanying figure shows the jumper factory default settings.
These jumpers may be used to:
- Set communications to RS485, by setting both COMM jumpers to '485’.
- Set RS485 termination, by setting both TERM jumpers to 'OFF'.
To access the jumpers, you must open the controller according to the instructions on page 13.
Setting RS232/RS485 Communication Parameters, V430J
This port may be set to either RS232 or RS485 via DIP switches: The table shows the DIP switches factory default settings. Use the table to adapt the settings.
Switch Settings | 1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|---|
RS232* | ON | OFF | OFF | ON | OFF | OFF |
RS485 | OFF | ON | ON | OFF | OFF | OFF |
RS485 with termination** | OFF | ON | ON | OFF | ON | ON |
* Default factory setting
** Causes the unit to function as an end unit in an RS485 network
USB Port
- The USB port is not isolated.
- Caution Make sure that the PC and the controller are grounded to same potential.
- The USB port may be used for programming, OS download, and PC access.
Opening the Controller
- ! Before performing these actions, touch a grounded object to discharge any electrostatic charge.
- Avoid touching the PCB board directly. Hold the PCB board by its connectors.
- Turn off the power supply, disconnect, and dismount the controller.
- The back cover of the controller comprises 4 screws, located in the corners. Remove the screws, and pull off the back cover.
Changing I/O Settings
After opening the controller and exposing the I/O board, you can change the jumper settings according to the table shown above.
Changing Communication Settings (V130/V350/V130J/V350J Only)
- To access the communication jumpers, hold the I/O PCB board by its top and bottom connectors and steadily pull the board off.
- Locate the jumpers, and then change the settings as required, according to the jumpers' settings shown on page 12.
Closing the Controller
- Gently replace the board. Make certain that the pins fit correctly into their matching receptacle. Do not force the board into place; doing so may damage the controller.
- Replace the back cover of the controller and fasten the corner screws.
Note that you must replace the back cover securely before powering up the controller.
Technical Specifications
Order Information
Item | V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 |
---|---|---|---|
PLC with Classic panel, Monochrome display | 2.4" | 2.4" | - |
PLC with Flat panel, Monochrome display | 2.4" | 2.4" | - |
PLC with Classic panel, Color touch display | - | 3.5" | - |
PLC with Flat panel, Color touch display | - | 3.5" | 4.3" |
You can find additional information, such as wiring diagrams, in the product's installation guide located in the Technical Library at www.unitronics.com.
Power Supply
Item | V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 |
---|---|---|---|
Input voltage | 24VDC | 24VDC | 24VDC |
Permissible range | 20.4VDC to 28.8VDC with less than 10% ripple | 20.4VDC to 28.8VDC with less than 10% ripple | 20.4VDC to 28.8VDC with less than 10% ripple |
Max. current consumption | See note 1 | See note 1 | See note 1 |
npn inputs | 245mA@24VDC | 270mA@24VDC | 270mA@24VDC |
pnp inputs | 200mA@24VDC | 230mA@24VDC | 230mA@24VDC |
Notes:
- To calculate the actual power consumption, subtract the current for each unused element from the maximum current consumption value according to the values below:
V130/J | V350/J/V430J | |
---|---|---|
Backlight | 10mA | 20mA |
Ethernet card | 35mA | 35mA |
Relay Outputs (per output) | 5mA | 5mA |
All Analog Outputs, voltage/current | 48mA/30mA* | 48mA/30mA* |
*If the analog outputs are not configured, then subtract the higher value.
Digital Inputs
- Number of inputs: 12. See note 2
- Input type: None (Galvanic isolation)
- Nominal input voltage: 24VDC
- Input Voltage:
- pnp (source): 0-5VDC for Logic '0'; 17-28.8VDC for Logic '1'
- npn (sink): 17-28.8VDC for Logic '0'; 0-5VDC for Logic '1'
- Input Current: 10, 11: 5.4mA@24VDC; 12-111: 3.7mA@24VDC
- Input impedance: 10, 11: 4.5KΩ; 12-111: 6.5KΩ
- Response Time: 10ms typical, when used as normal digital input
- Input Cable length: Up to 100 meters
- Normal digital Input
- High Speed Input: See Note 3
- Frequency, HSC: Specifications below apply when wired as HSC/shaft-encoder.
Driver type | pnp/npn | Push-pull | |
---|---|---|---|
Cable length (max.) | 10m | 95kHz maximum | 200kHz maximum |
25m | 50kHz maximum | 200kHz maximum | |
50m | 25kHz maximum | 200kHz maximum |
Frequency, Shaft-encoder | Driver type | pnp/npn | Push-pull |
---|---|---|---|
Cable length (max.) | 10m | 35kHz maximum | 100kHz maximum |
25m | 18kHz maximum | 100kHz maximum | |
50m | 10kHz maximum | 100kHz maximum |
- Duty cycle: 40-60%
- Resolution: 32-bit
Notes:
- 2. V130/V350/V130J/V350J/V430J-TRA22 models comprise a total of 12 inputs. All 12 inputs may be used as digital inputs. They may be wired in a group via a single jumper as either npn or pnp.
- In addition, according to jumper settings and appropriate wiring:
- Inputs 5 and 6 can function as either digital or analog inputs.
- Input 0 can function as a high-speed counter, as part of a shaft-encoder, or as normal digital inputs.
- Input 1 can function as either counter reset, normal digital input, or as part of a shaft-encoder.
- If input 0 is set as a high-speed counter (without reset), input 1 can function as a normal digital input.
- Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; input 11 can also serve as the CM signal for PT100.
- 3. If you configure an input as high-speed, you can use an end-device that comprises push-pull drive type. In this case, the high-speed input voltage ratings for npn/pnp apply.
Analog Inputs
- Number of inputs: 2, according to wiring as described above in Note 2
- Input type: Multi-range inputs: 0-10V, 0-20mA, 4-20mA
- Input range: 0-20mA, 4-20mA
- Input impedance: 37Ω (for current), 0-10VDC (for voltage)
- Maximum input rating: 30mA, 1.1V
- Galvanic isolation: None
- Conversion method: Voltage to frequency
- Normal mode:
- Resolution, except 4-20mA: 14-bit (16384 units)
- Resolution, at 4-20mA: 3277 to 16383 (13107 units)
- Conversion time: 100ms minimum per channel. See Note 4
- Fast mode:
- Resolution, except 4-20mA: 12-bit (4096 units)
- Resolution, at 4-20mA: 819 to 4095 (3277 units)
- Conversion time: 30ms minimum per channel. See Note 4
- Full-scale error: ±0.4%
- Linearity error: ±0.04%
- Status indication: Yes. See Note 5
RTD Inputs
- RTD Type: PT100
- Temperature coefficient α: 0.00385/0.00392
- Input range: -200 to 600°C/-328 to 1100°F. 1 to 320Ω.
- Isolation: None
- Conversion method: Voltage to frequency
- Resolution: 0.1°C/0.1°F
- Conversion time: 300ms minimum per channel. See Note 4 above
- Input impedance: >10MΩ
- Auxiliary current for PT100: 150μA typical
- Full-scale error: ±0.4%
- Linearity error: ±0.04%
- Status indication: Yes. See Note 6
- Cable length: Up to 50 meters, shielded
Notes:
- 4. Conversion times are accumulative and depend on the total number of analog inputs configured. For example, if only one analog input (fast mode) is configured, the conversion time will be 30ms; however, if two analog (normal mode) and two RTD inputs are configured, the conversion time will be 100ms + 100ms + 300ms + 300ms = 800ms.
- 5. The analog value can indicate faults as shown below:
Value: 12-bit | Value: 14-bit | Possible Cause |
---|---|---|
-1 | -1 | Deviates slightly below the input range |
4096 | 16384 | Deviates slightly above the input range |
32767 | 32767 | Deviates greatly above or below the input range |
- 6. The analog value can indicate faults as shown below:
Value | Possible Cause |
---|---|
32767 | Sensor is not connected to input, or value exceeds permissible range |
-32767 | Sensor is short-circuited |
Thermocouple Inputs
- Input range: See Note 7
- Isolation: None
- Conversion method: Voltage to frequency
- Resolution: 0.1°C/0.1°F maximum
- Conversion time: 100ms minimum per channel. See Note 4 above
- Input impedance: >10MΩ
- Cold junction compensation: Local, automatic
- Cold junction compensation error: ±1.5°C/±2.7°F maximum
- Absolute maximum rating: ±0.6VDC
- Full-scale error: ±0.4%
- Linearity error: ±0.04%
- Warm-up time: 1/2 hour typically, ±1°C/±1.8°F repeatability
- Status indication: Yes. See Note 6 above
Notes:
- 7. The device can also measure voltage within the range of -5 to 56mV, at a resolution of 0.01mV. The device can also measure raw value frequency at a resolution of 14-bits (16384). Input ranges are shown in the following table:
Type | Temp. Range | Type | Temp. Range |
---|---|---|---|
mV | -5 to 56mV | N | -200 to 1300°C (-328 to 2372°F) |
B | 200 to 1820°C (300 to 3276°F) | R | 0 to 1768°C (32 to 3214°F) |
E | -200 to 750°C (-328 to 1382°F) | S | 0 to 1768°C (32 to 3214°F) |
J | -200 to 760°C (-328 to 1400°F) | T | -200 to 400°C (-328 to 752°F) |
K | -200 to 1250°C (-328 to 2282°F) |
Digital Outputs
- Number of outputs: 4 relay. See Note 8
- Output type: SPST-NO (Form A)
- Isolation: By relay
- Type of relay: Tyco PCN-124D3MHZ or compatible
- Output current (resistive load): 3A maximum per output, 8A maximum total per common
- Rated voltage: 250VAC / 30VDC
- Minimum load: 1mA, 5VDC
- Life expectancy: 100k operations at maximum load
- Response time: 10ms (typical)
- Contact protection: External precautions required (see Increasing Contact Life Span in the product's Installation Guide)
Notes:
- 8. Outputs 4, 5, 6, and 7 share a common signal.
Transistor Outputs
- Number of outputs: 4 npn (sink). See Note 9
- Output type: N-MOSFET, (open drain)
- Galvanic Isolation: None
- Maximum output current (resistive load): 100mA per output
- Rated voltage: 24VDC
- Maximum delay OFF to ON: 1 μs
- Maximum delay ON to OFF: 10 μs
- HSO freq. range with resistive load: 5Hz-200kHz (at maximum load resistance of 1.5kΩ)
- Maximum ON voltage drop: 1VDC
- Short-circuit protection: None
- Voltage range: 3.5V to 28.8VDC
Notes:
- 9. Outputs 0, 1, 2 and 3 share a common OV signal. The OV signal of the output must be connected to the controller's OV.
Analog Outputs
- Number of outputs: 2
- Output range: 0-10V, 4-20mA. See Note 10
- Resolution: 12-bit (4096 units)
- Conversion time: Both outputs are updated per scan
- Load impedance: 1kΩ minimum—voltage, 500Ω maximum—current
- Galvanic isolation: None
- Linearity error: ±0.1%
- Operational error limits: ±0.2%
Notes:
- 10. Note that the range of each I/O is defined by wiring, jumper settings, and within the controller's software.
Graphic Display Screen
Item | V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 |
---|---|---|---|
LCD Type | STN, LCD display | TFT, LCD display | TFT, LCD display |
Illumination backlight | White LED | White LED | White LED |
Display resolution | 128x64 pixels | 320x240 pixels | 480x272 pixels |
Viewing area | 2.4" | 3.5" | 4.3" |
Colors | Monochrome | 65,536 (16-bit) | 65,536 (16-bit) |
Screen Contrast | Via software (Store value to SI 7, values range: 0 to 100%) | Fixed | Fixed |
Touchscreen | None | Resistive, analog | Resistive, analog |
'Touch' indication | Via buzzer | Via buzzer | Via buzzer |
Screen brightness control | Via software (Store value to SI 9, 0 = Off, 1 = On) | Via software (Store value to SI 9, values range: 0 to 100%) | Via software (Store value to SI 9, values range: 0 to 100%) |
Virtual Keypad | None | Displays virtual keyboard when the application requires data entry. | Displays virtual keyboard when the application requires data entry. |
Keypad
Item | V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 |
---|---|---|---|
Number of keys | 20 keys, including 10 user-labeled keys | 5 programmable function keys | None |
Key type | Metal dome, sealed membrane switch | Metal dome, sealed membrane switch | - |
Slides | Slides may be installed in the operating panel faceplate to custom-label the keys. Refer to V130 Keypad Slides.pdf. A complete set of blank slides is available by separate order | Slides may be installed in the operating panel faceplate to custom-label the keys. Refer to V350 Keypad Slides.pdf. Two sets of slides are supplied with the controller: one set of arrow keys, and one blank set. | None |
Program and Memory
Program | V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 |
---|---|---|---|
Memory size | |||
Application Logic | 512KB | 1MB | 1MB |
Images | 128KB | 6MB | 12MB |
Fonts | 128KB | 512KB | 512KB |
Operand type | Quantity | Symbol | Value | ||
---|---|---|---|---|---|
V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 | |||
Memory Bits | 4096 | 8192 | 8192 | MB | Bit (coil) |
Memory Integers | 2048 | 4096 | 4096 | MI | 16-bit signed/unsigned |
Long Integers | 256 | 512 | 512 | ML | 32-bit signed/unsigned |
Double Word | 64 | 256 | 256 | DW | 32-bit unsigned |
Memory Floats | 24 | 64 | 64 | MF | 32-bit signed/unsigned |
Fast Bits | 1024 | 1024 | 1024 | XB | Fast Bits (coil) – not retained |
Fast Integers | 512 | 512 | 512 | XI | 16 bit signed/unsigned (fast, not retained) |
Fast Long Integers | 256 | 256 | 256 | XL | 32 bit signed/unsigned (fast, not retained) |
Fast Double Word | 64 | 64 | 64 | XDW | 32 bit unsigned (fast, not retained) |
Timers | 192 | 384 | 384 | T | Res. 10 ms; max 99h, 59 min, 59.99s |
Counters | 24 | 32 | 32 | C | 32-bit |
Data Tables | 120K dynamic data (recipe parameters, datalogs, etc.) 192K fixed data (read-only data, ingredient names, etc) Expandable via SD card. See Removable Memory below | ||||
HMI displays | Up to 1024 | ||||
Program scan time | 20µs per 1kb of typical application | 15µs per 1kb of typical application | 15µs per 1kb of typical application |
Removable Memory
- Micro SD card: Compatible with standard SD and SDHC; up to 32GB store datalogs, Alarms, Trends, Data Tables, backup Ladder, HMI, and OS. See Note 11
Notes:
- 11. User must format via Unitronics SD tools utility.
Dimensions
Item | V130-TRA22 / V130J-TRA22 | V350-TRA22 / V350J-TRA22 | V430J-TRA22 |
---|---|---|---|
Size | Vxxx: 109 x 114.1 x 68mm (4.29 x 4.49 x 2.67"). See Note 15 Vxxx-J: 109 x 114.1 x 66mm (4.92 x 4.49 x 2.59"). See Note 15 |
Vxxx: 109 x 114.1 x 68mm (4.29 x 4.49 x 2.67"). See Note 15 Vxxx-J: 109 x 114.1 x 66mm (4.92 x 4.49 x 2.59"). See Note 15 |
136 x 105.1 x 61.3mm (5.35 x 4.13 x 2.41"). See Note 15 |
Weight | 300g (10.58 oz) | 325g (11.46 oz) | 355g (12.52 oz) |
Notes:
- 15. For exact dimensions, refer to the product's installation guide.
Environment
- Operational temperature: 0 to 50°C (32 to 122°F)
- Storage temperature: -20 to 60°C (-4 to 140°F)
- Relative Humidity (RH): 10% to 95% (non-condensing)
- Mounting method: Panel mounted (IP65/66/NEMA4X), DIN-rail mounted (IP20/NEMA1)
- Operating Altitude: 2000m (6562 ft)
- Shock: IEC 60068-2-27, 15G, 11ms duration
- Vibration: IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
UG_V130_350_430-RA22 11/22
File Info : application/pdf, 23 Pages, 1,017.99KB
DocumentDocumentReferences
Home - Unitronics
Home - Unitronics
Technical library- about PLC Controllers, HMI panels, automation & control
Related Documents
![]() |
Unitronics Vision PLC+HMI User Guide and Technical Specifications Comprehensive user guide and technical specifications for Unitronics Vision PLC+HMI series, including V130, V350, and V430 models. Covers installation, wiring, power supply, communication, and environmental considerations. |
![]() |
Unitronics Vision PLC+HMI Installation Guide Comprehensive installation guide for Unitronics Vision PLC+HMI series, covering models V130, V350, and V430. Details mounting, wiring, power supply, and communication setup for industrial automation. |
![]() |
Unitronics Vision PLC+HMI Installation Guide: V130, V350, V430 Series Comprehensive installation guide for Unitronics Vision PLC+HMI series, covering models V130, V350, and V430. Details general description, standard kit contents, mounting instructions (panel and DIN-rail), wiring procedures, power supply, and communication settings (RS232/RS485, USB). |
![]() |
VisiLogic Software: Version Changes and Features Explore the evolution of Unitronics' VisiLogic software, detailing new features, hardware support, and improvements across various versions from 9.8.91 down to 7.00. Discover updates in I/O configuration, motion control, communication protocols, and HMI capabilities. |
![]() |
Unitronics Samba™ PLC+HMI Installation and User Guide Comprehensive guide for Unitronics Samba™ PLC+HMI controllers (SM35-J-RA22, SM43-J-RA22, SM70-J-RA22), covering general descriptions, kit contents, safety warnings, UL compliance, panel mounting, wiring procedures, I/O configurations, technical specifications, communication ports, dimensions, and environmental considerations. |
![]() |
Unitronics PLC + HMI All-in-One Solutions: Vision, Samba, Jazz Explore Unitronics' powerful PLC + HMI All-in-One automation solutions. Discover the Vision, Samba, and Jazz series, featuring intuitive software, expert support, and a complete range of PLCs for diverse industrial applications. |
![]() |
Unitronics PLC + HMI All-in-One Controllers and Software Overview Explore the comprehensive range of Unitronics' PLC+HMI All-in-One automation solutions, including UniStream, Vision, Samba, and Jazz series, alongside the powerful UniLogic programming software. Discover features, specifications, and applications for industrial automation. |
![]() |
Unitronics Vision V120 & M91 PLC User Guide Comprehensive user guide for Unitronics Vision V120 and M91 series PLC controllers, covering installation, wiring, technical specifications, and safety guidelines for hazardous and ordinary locations. |