Vision™ PLC+HMI Installation Guide

Models Covered: V130-33-B1/V130-J-B1, V350-35-B1/V350-J-B1, V430-J-B1

General Description

All of the controllers covered in this guide are micro-PLC+HMIs, rugged programmable logic controllers that comprise built-in operating panels.

Item V130-B1 / V130J-B1 V350-B1 / V350J-B1 V430J-B1
Screen 2.4" 3.5" Color Touch 4.3" Color Touch
Keypad Yes None None
Function Keys None Yes Yes
Com Port, Built-in RS232/485: Yes RS232/485: Yes* RS232/485: Yes*
USB device, mini-B None Yes* Yes*
Com Ports, separate order, user-installed The user may install a CANbus port (V100-17-CAN), and one of the following: RS232/RS485 port (V100-17-RS4/V100-17-RS4X), Ethernet (V100-17-ET2), Profibus Slave (V100-17-PB1).

* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.

Standard Kit Contents

Item V130-B1 / V130J-B1 V350-B1 / V350J-B1 V430J-B1
Controller Yes Yes Yes
Terminal Blocks Yes Yes Yes
Battery (installed) Yes Yes Yes
Slides (2 sets of key labels) None Yes None
Mounting Brackets Yes (2 parts) Yes Yes (4 parts)
Rubber Seal Yes Yes Yes

Alert Symbols and General Restrictions

When any of the following symbols appear, read the associated information carefully.

Symbol Meaning Description
Danger The identified danger causes physical and property damage.
⚠️ Warning The identified danger could cause physical and property damage.
? Caution Use caution.

General Cautions and Guidelines:

Environmental Considerations

Mounting

Note that figures are for illustrative purposes only.

Dimensions: V130/V350/V130J/V350J

Overall Dimensions: 109mm (4.29") width, 114.1mm (4.49") height.

Panel Cut-out Dimensions: 92mm x 92mm (3.622" x 3.622").

Depth: 90.2mm (3.55") total depth. Specific port and connector dimensions are detailed in the original diagrams.

For models V130J/V350J, the bezel width is 6.7 mm (0.26”).

Dimensions: V430J

Overall Dimensions: 136mm (5.35") width, 105.1mm (4.13") height.

Side View Depth: 90.9mm (3.58") total depth. Specific port and connector dimensions are detailed in the original diagrams.

Panel Mounting

Before you begin, note that the mounting panel cannot be more than 5 mm thick.

UL Listed Models: To meet the UL508 standard, panel-mount the device on the flat surface of a Type 1 enclosure.

  1. Make a panel cut-out of the appropriate size:
    • V130/V350/V130J/V350J: 92x92 mm (3.622"x3.622").
    • V430J: 122.5x91.5 mm (4.82"x3.6").
  2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
  3. Push the mounting brackets into their slots on the sides of the panel.
  4. Tighten the bracket's screws against the panel. Hold the bracket securely against the unit while tightening the screw.
  5. When properly mounted, the controller is squarely situated in the panel cut-out.

Diagram Description (V130/V350/V130J/V350J): Illustrates panel cut-out, rubber seal, mounting bracket, and controller placement. Shows ports like CANbus, USB, RS232/RS485, and additional communication ports.

Diagram Description (V430J): Illustrates panel cut-out, rubber seal, mounting bracket, and controller placement. Shows ports like CANbus, PORT 1, USB, PORT 2, and DIP Switch.

DIN-rail Mounting (V130/V350/V130J/V350J)

  1. Snap the controller onto the DIN rail as shown in the figure.
  2. When properly mounted, the controller is squarely situated on the DIN-rail.

Diagram Description: Shows controller being snapped onto a DIN rail.

Wiring

? Caution:

Wiring Procedure

Use crimp terminals for wiring; use 3.31 mm² –0.13 mm² wire (12-16 AWG):

  1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
  2. Unscrew the terminal to its widest position before inserting a wire.
  3. Insert the wire completely into the terminal to ensure a proper connection.
  4. Tighten enough to keep the wire from pulling free.

Additional wiring notes:

Power Supply

The picture is for illustration only.

The controller requires an external 12VDC or 24VDC power supply.

Requirements: The power supply must include double insulation. Outputs must be rated as SELV/PELV/Class2/Limited Power.

Diagram Description: Shows two connection diagrams for power supply: one for 24VDC with circuit protection, and one for V130/V350 with circuit protection.

Earthing the PLC+HMI

To maximize system performance, avoid electromagnetic interference by:

Communication

V130/V130J: These models comprise a built-in RS232/RS485 serial port (Port 1).

V430J/V350/V350J: These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1).

Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications via Port 1. When the PC is disconnected, RS232/RS485 resumes.

RS232/RS485 Port

Usage:

Pinouts

The pinouts below show the PLC port signals.

RS232 Pin # RS232 Description RS485** Pin # RS485 Description Controller Port
1* DTR signal 1 A signal (+) Pin #1
2 0V reference 2 (RS232 signal)
3 TXD signal 3 (RS232 signal)
4 RXD signal 4 (RS232 signal)
5 0V reference 5 (RS232 signal)
6* DSR signal 6 B signal (-)

* Standard programming cables do not provide connection points for pins 1 and 6.

** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A, and Pin 6 (DSR) signal is used for signal B.

It is possible to establish a PC to PLC connection using RS232 even when the PLC is set to RS485 (this eliminates the need to open the controller to set jumpers). To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232 programming cable. This is possible only if DTR and DSR signals of RS232 are not used.

Setting RS232/RS485 Communication Parameters, V130/V350/V130J/V350J

This port may be set to either RS232 or RS485 via jumper. The accompanying figure shows the jumper factory default settings.

Jumpers:

To access the jumpers, you must open the controller according to the instructions on page 8.

Diagram Description: Shows jumper configuration for RS232/RS485 Select (COMM jumpers) and RS485 Termination (TERM jumpers).

Setting RS232/RS485 Communication Parameters, V430J

This port may be set to either RS232 or RS485 via DIP switches. The table shows the DIP switches factory default settings. Use the table to adapt the settings.

Switch Settings 1 2 3 4 5 6
RS232* ON OFF OFF ON OFF OFF
RS485 OFF ON ON OFF OFF OFF
RS485 with termination** OFF ON ON OFF ON ON

* Default factory setting.

** Causes the unit to function as an end unit in an RS485 network.

USB Port

? Caution: The USB port is not isolated. Make sure that the PC and the controller are grounded to the same potential.

The USB port may be used for programming, OS download, and PC access.

Opening the Controller (V130/V350/V130J/V350J Only)

Before performing these actions, touch a grounded object to discharge any electrostatic charge. Avoid touching the PCB board directly. Hold the PCB board by its connectors.

  1. Turn off the power supply, disconnect, and dismount the controller.
  2. The back cover of the controller comprises 4 screws, located in the corners. Remove the screws, and pull off the back cover.

Changing Communication Settings (V130/V350/V130J/V350J Only)

  1. To access the communication jumpers, hold the Power supply PCB board by its edges and steadily pull the board off.
  2. Locate the jumpers, and then change the settings as required, according to the jumpers' settings shown on page 7.

Closing the Controller (V130/V350/V130J/V350J Only)

  1. Gently replace the board. Make certain that the pins fit correctly into their matching receptacle. Do not force the board into place; doing so may damage the controller.
  2. Replace the back cover of the controller and fasten the corner screws.

Note that you must replace the back cover securely before powering up the controller.

Legal Disclaimer

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.

All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.

The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.

Document identifier: DOC13033-D4 07/18

PDF preview unavailable. Download the PDF instead.

Manual-QIG V130-B1 V350-B1 V430-B1 Microsoft Word 2010

Related Documents

Preview Unitronics Vision PLC+HMI Installation Guide
Comprehensive installation guide for Unitronics Vision PLC+HMI series, covering models V130, V350, and V430. Details mounting, wiring, power supply, and communication setup for industrial automation.
Preview Unitronics Vision PLC+HMI User Guide and Technical Specifications
Comprehensive user guide and technical specifications for Unitronics Vision PLC+HMI series, including V130, V350, and V430 models. Covers installation, wiring, power supply, communication, and environmental considerations.
Preview Unitronics: Integrated Control and Automation Solutions
Explore Unitronics' comprehensive range of PLC+HMI controllers and Variable Frequency Drives (VFDs). Offering integrated solutions for industrial automation, Industry 4.0, and efficient control with user-friendly software and outstanding support.
Preview Unitronics Vision PLC+HMI Installation Guide
This guide provides detailed information on the installation, wiring, and specifications of Unitronics Vision PLC+HMI series controllers, including models V130, V350, and V430.
Preview Unitronics PLC + HMI All-in-One Solutions: Vision, Samba, Jazz
Explore Unitronics' powerful PLC + HMI All-in-One automation solutions. Discover the Vision, Samba, and Jazz series, featuring intuitive software, expert support, and a complete range of PLCs for diverse industrial applications.
Preview Unitronics PLC + HMI All-in-One Controllers and Software Overview
Explore the comprehensive range of Unitronics' PLC+HMI All-in-One automation solutions, including UniStream, Vision, Samba, and Jazz series, alongside the powerful UniLogic programming software. Discover features, specifications, and applications for industrial automation.
Preview Unitronics Industrial Automation Product Price List
Comprehensive price list for Unitronics industrial automation products, including PLCs, HMIs, OPLCs, GPRS modems, communication ports, expansion modules, cables, and power supplies. Features products from Jazz, M90, M91, Samba, V120, V130, V200, V350, V430, and UniStream series, with detailed model descriptions and pricing in PLN. Includes information on VAT, discounts for resellers, and current price availability on elmark.com.pl.
Preview Unitronics PLC and Accessories Catalog: Integrated Automation Solutions
Explore Unitronics' comprehensive range of PLCs, HMIs, Motion Control, UniLogic software, and UniCloud IIoT platform. Discover solutions for industrial automation, designed for efficiency, reliability, and ease of use.