Samba™ PLC+HMI User Guide

Models: SM35-J-RA22, SM43-J-RA22, SM70-J-RA22

General Description

The controllers covered in this guide are micro-PLC+HMI, rugged programmable logic controllers with built-in operating panels and on-board I/Os.

Item SM35-J-RA22 SM43-J-RA22 SM70-J-RA22
On-board I/O Model Dependent Model Dependent Model Dependent
Screen 3.5" Color Touch 4.3" Color Touch 7" Color Touch
Keypad or Function Keys None None None
Programming Com Port, Built-in RS232 None None
USB device, mini-B Yes None Yes
Com Ports, separate order, user-installed The user may install a CANbus module (V100-17-CAN), and one of the following: RS232/RS485 port (V100-17-RS4/V100-17-RS4X) or Ethernet (V100-17-ET2). The user may install a CANbus module (V100-17-CAN), and one of the following: RS232/RS485 port (V100-17-RS4/V100-17-RS4X) or Ethernet (V100-17-ET2). The user may install a CANbus module (V100-17-CAN), and one of the following: RS232/RS485 port (V100-17-RS4/V100-17-RS4X) or Ethernet (V100-17-ET2).

Standard Kit Contents

Item SM35-J-RA22 SM43-J-RA22 SM70-J-RA22
Controller Yes Yes Yes
Terminal Blocks Yes Yes Yes
Battery Yes (installed) Yes (installed) Yes (installed)
Mounting Brackets Yes (2 parts) Yes (4 parts) Yes (6 parts)
Rubber Seal Yes Yes Yes

Alert Symbols and General Restrictions

When any of the following symbols appear, read the associated information carefully.

Symbol Meaning Description
! Danger The identified danger causes physical and property damage.
! Warning The identified danger could cause physical and property damage.
! Caution Use caution.

Before using this product, the user must read and understand this document.

Failure to comply with appropriate safety guidelines can cause severe injury or property damage:

Environmental Considerations

Do not install in areas with:

UL Compliance

The following section is relevant to Unitronics' products that are listed with the UL.

UL Listed for Hazardous Locations (Class I, Division 2, Groups A, B, C and D)

The following models are UL listed for Hazardous Locations:

UL Listed for Ordinary Location

The following models are UL listed for Ordinary Location:

For models from series V130, V130-J, V430, that include “T4” or “J4” in the Model name, they are suitable for mounting on the flat surface of a Type 4X enclosure (e.g., V130-T4-R34, V130-J4-R34, V430-J4-T2, SM43-J4-R20).

UL Ordinary Location Requirements

To meet the UL ordinary location standard, panel-mount the device on the flat surface of Type 1 or Type 4X enclosures.

UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class I, Division 2, Groups A, B, C and D

This section relates to all Unitronics products bearing the UL symbols, indicating approval for use in hazardous locations (Class I, Division 2, Groups A, B, C and D).

French Sections (Translated)

UL des zones ordinaires (UL Ordinary Locations)

Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de protection 1 ou 4X.

To comply with the UL standard for ordinary locations, mount the device on a flat surface of a Type 1 or Type 4X enclosure.

Certification UL des automates programmables, pour une utilisation en environnement à risques, Class I, Division 2, Groups A, B, C et D (UL Certification for Programmable Controllers for Use in Hazardous Environments, Class I, Division 2, Groups A, B, C and D)

Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.

This note refers to all Unitronics products bearing the UL symbol – products certified for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.

! AVERTISSEMENT: Risque d'Explosion – Le remplacement de certains composants rend caduque la certification du produit selon la Classe I, Division 2.

WARNING: Explosion Hazard – Replacing certain components invalidates the product's certification according to Class I, Division 2.

! AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue pour être non dangereuse.

WARNING - EXPLOSION DANGER - Do not connect or disconnect the equipment without first switching off the power supply or ensuring the area is known to be non-hazardous.

! AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés des matériaux utilisés pour l'étanchéité dans les relais.

WARNING - Exposure to certain chemicals may degrade the properties of materials used for sealing in relays.

Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I, Division 2 NEC et/ou CEC.

This equipment must be installed using wiring methods according to Class I, Division 2 standards, NEC and/or CEC.

Panel Mounting

For programmable controllers that can be panel-mounted, to meet the UL Haz Loc standard, panel-mount the device on the flat surface of a Type 1 or Type 4X enclosure.

Mounting Panel Thickness: The mounting panel cannot be more than 5 mm thick.

UL Listed Models Panel Mounting Procedure:

  1. Make a panel cut-out of the appropriate size:
    • SM35: 92x92mm (3.622"x3.622")
    • SM43: 122.5x91.5mm (4.82"x3.6")
    • SM70: 193x125mm (7.59"x4.92")
  2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
  3. Push the mounting brackets into their slots on the sides of the panel.
  4. Tighten the bracket's screws against the panel. Hold the bracket securely against the unit while tightening the screw. The required torque is 0.35 N·m (3.1 in-lb).
  5. When properly mounted, the controller is squarely situated in the panel cut-out.

! Caution: Do not apply torque exceeding 0.35 N·m (3.1 in-lb) to tighten the bracket screws. Using excessive force can damage the product.

Dimensions

SM35

SM43

SM70

Wiring

! Do not touch live wires.

Wiring Procedure

Use crimp terminals for wiring; use 3.31 mm² – 0.13 mm² wire (12-26 AWG):

  1. Strip the wire to a length of 7±0.5mm (0.270–0.300").
  2. Unscrew the terminal to its widest position before inserting a wire.
  3. Insert the wire completely into the terminal to ensure a proper connection.
  4. Tighten enough to keep the wire from pulling free.

I/O Wiring Diagrams

npn (sink) Input

pnp (source) Input

Shaft-encoder

I/Os

The SM35/43/70-J-RA22 comprises a total of 12 inputs, 8 relays, and 2 analog outputs. Input functionality can be adapted.

Input Functionality Adaptations:

Input Jumper Settings

The following tables detail jumper settings to change input functionality. Accessing I/O jumpers requires opening the controller.

! Incompatible jumper settings and wiring connections may seriously damage the controller.

Digital Inputs 0-11: Set Type

Set to JP12 (all Inputs)
npn (sink) A
pnp (source)* B

Inputs 7/8: Set Type - Digital or RTD/TC #1

Set to JP1 JP2 JP3
Digital* A A A
Thermocouple B B B
PT100 B A B

Inputs 9/10: Set Type - Digital or RTD/TC #0

Set to JP5 JP6 JP7
Digital* A A A
Thermocouple B B B
PT100 B A B

Input 11: Set Type - Digital or CM for PT100

Set to JP11
Digital* A
CM for PT100 B

Input 5: Set Type - Digital or Analog #3

Set to JP4 JP10
Digital* A A
Voltage B A
Current B B

Input 6: Set Type - Digital or Analog #2

Set to JP8 JP9
Digital* A A
Voltage B A
Current B B

*Default settings

Analog Output 0: Set to Voltage/Current

Set to JP13
Voltage* A
Current B

Analog Output 1: Set to Voltage/Current

Set to JP14
Voltage* A
Current B

Analog Input

Analog input wiring, current (2/3 wire) and analog input wiring, current (4-wire), and voltage.

Diagram Description: Shows connections for 24VDC, +V, 0V, circuit protection device, and analog inputs AN2, AN3, with options for 2-wire, 3-wire, and 4-wire transmitters.

Shields should be connected at the signal's source.

The 0V signal of the analog input must be connected to the controller's 0V.

Thermocouple

Diagram Description: Shows connections for 24VDC, +V, 0V, circuit protection device, and inputs for Thermocouple 0 (TC0) and Thermocouple 1 (TC1).

Type Temp. Range Wire Color (ANSI USA) Wire Color (BS1843 UK)
mV -5 to 56mV +Grey +None
B 200 to 1820°C (300 to 3276°F) -Red -Blue
E -200 to 750°C (-328 to 1382°F) +Violet +Brown
J -200 to 760°C (-328 to 1400°F) +White +Yellow
K -200 to 1250°C (-328 to 2282°F) +Yellow +Brown
N -200 to 1300°C (-328 to 2372°F) +Orange +Orange
R 0 to 1768°C (32 to 3214°F) +Black +White
S 0 to 1768°C (32 to 3214°F) +Black +White
T -200 to 400°C (-328 to 752°F) +Blue +White

RTD Inputs

Diagram Description: Shows wiring for 2-wire, 3-wire, and 4-wire PT100 connections to the controller's inputs.

Analog Outputs

Diagram Description: Shows connections for Analog Output 0 (AO0) and Analog Output 1 (AO1) to load current and voltage connections.

Relay Outputs

Diagram Description: Shows connections for Relay Outputs 1-8 to external loads, with +V (24VDC), 0V, and N (110/220VAC) terminals.

Increasing Contact Life Span

To increase the life span of the relay output contacts and protect the device from potential damage by reverse EMF, connect:

Power Supply

The controller requires an external 24VDC power supply. The power supply must include double insulation and outputs must be rated as SELV/PELV/Class2/Limited Power.

Diagram Description: Shows a basic power supply connection diagram with 24VDC, +V, 0V, and circuit protection device.

Earthing the PLC+HMI

To maximize system performance and avoid electromagnetic interference:

Communication Port

Caution: Turn off power before making communications connections. Always use the appropriate port adapters.

SM43/SM70-J-RA22

This series comprises a USB port.

Caution: The USB port in SM43 Series is not isolated. Ensure that the PC and the controller are grounded to the same potential.

The USB port may be used for programming, OS download, and PC access.

SM35-J-RA22

This series comprises a built-in RS232 port.

Use RS232 to download programs from a PC and to communicate with serial devices and applications, such as SCADA.

Pinouts

The pinouts show the PLC port signals.

RS232 Pinout

Pin # Description
1 Not connected
2 0V reference
3 TXD signal
4 RXD signal
5 0V reference
6 Not connected

Opening the Controller

  1. Turn off the power supply, disconnect, and dismount the controller.
  2. The back cover of the controller has 4 screws in the corners. Remove the screws and pull off the back cover.

Closing the Controller

Replace the back cover of the controller and fasten the corner screws. Ensure the back cover is securely replaced before powering up the controller.

Technical Specifications

Power Supply

Item SM35-J-RA22 SM43-J-RA22 SM70-J-RA22
Input voltage 24VDC 24VDC 24VDC
Permissible range 20.4VDC to 28.8VDC (less than 10% ripple) 20.4VDC to 28.8VDC (less than 10% ripple) 20.4VDC to 28.8VDC (less than 10% ripple)
Max. current consumption See Note 1 See Note 1 See Note 1
npn inputs 275mA@24VDC 275mA@24VDC 330mA@24VDC
pnp inputs 235mA@24VDC 235mA@24VDC 295mA@24VDC

Notes:

  1. To calculate actual power consumption, subtract the current for each unused element from the maximum current consumption value using the values below:
  2. Backlight Ethernet card Relay Outputs (per output) All Analog Outputs, voltage/current
    SM35/SM43 20mA 35mA 5mA 48mA/30mA*
    SM70 80mA 35mA 5mA 48mA/30mA*

    *If analog outputs are not configured, subtract the higher value.

Digital Inputs

High speed inputs

Specifications apply when wired as HSC/shaft-encoder. (See Note 3)

Frequency (max) Cable length (max.) HSC Shaft-encoder pnp Shaft-encoder npn
10m 30kHz 20kHz 16kHz
25m 25kHz 12kHz 10kHz
50m 15kHz 7kHz 5kHz

Analog Inputs

Notes:

  1. Conversion times are accumulative and depend on the total number of analog inputs configured. For example, if only one analog input (fast mode) is configured, the conversion time will be 30ms; however, if two analog (normal mode) and two RTD inputs are configured, the conversion time will be 100ms + 100ms + 300ms + 300ms = 800ms.
  2. The analog value can indicate faults:
  3. Value: 12-bit Value: 14-bit Possible Cause
    -1 -1 Deviates slightly below the input range
    4096 16384 Deviates slightly above the input range
    32767 32767 Deviates greatly above or below the input range

RTD Inputs

Auxiliary current for PT100: 150µA typical. Accuracy: ±0.44%. Status indication: Yes (See Note 6). Cable length: Up to 50 meters, shielded.

Notes:

  1. The analog value can indicate faults:
  2. Value Possible Cause
    32767 Sensor is not connected to input, or value exceeds permissible range
    -32767 Sensor is short-circuited

Thermocouple Inputs

Notes:

  1. The device can also measure voltage within the range of -5 to 56mV, at a resolution of 0.01mV. The device can also measure raw value frequency at a resolution of 14-bits (16384). Input ranges are shown in the following table:
  2. Type Temp. Range Type Temp. Range
    mV -5 to 56mV N -200 to 1300°C (-328 to 2372°F)
    B 200 to 1820°C (300 to 3276°F) R 0 to 1768°C (32 to 3214°F)
    E -200 to 750°C (-328 to 1382°F) S 0 to 1768°C (32 to 3214°F)
    J -200 to 760°C (-328 to 1400°F) T -200 to 400°C (-328 to 752°F)
    K -200 to 1250°C (-328 to 2282°F)

Digital Outputs

Notes:

  1. Outputs 0, 1, 2 and 3 share a common signal. Outputs 4, 5, 6, and 7 share a common signal.

Analog Outputs

Notes:

  1. Note that the range of each I/O is defined by wiring, jumper settings, and within the controller's software.

Graphic Display

Screen SM35-J-RA22 SM43-J-RA22 SM70-J-RA22
LCD Type TFT, LCD display TFT, LCD display TFT, LCD display
Illumination backlight White LED White LED White LED
Display resolution 320x240 pixels 480x272 pixels 800x480 pixels
Viewing area 3.5" 4.3" 7"
Colors 65,536 (16-bit) 65,536 (16-bit) 65,536 (16-bit)
Touchscreen Resistive, analog Resistive, analog Resistive, analog
Screen brightness control Via software (Store value to SI 9, values range: 0 to 100%)
Virtual Keypad Displays virtual keyboard when the application requires data entry.

Program

Item SM35-J-RA22 SM43-J-RA22 SM70-J-RA22
Memory size 80K 192K 192K
Application Logic 1.5M 3M 8M
Images 320K 320K 512K
Fonts
Operand type Quantity Symbol Value
Memory Bits 512 MB Bit (coil)
Memory Integers 256 MI 16-bit signed/unsigned
Long Integers 32 ML 32-bit signed/unsigned
Double Word 32 DW 32-bit unsigned
Memory Floats 24 MF 32-bit signed/unsigned
Fast Bits 64 XB Fast Bits (coil) – not retained
Fast Integers 32 XI 16 bit signed/unsigned (fast, not retained)
Fast Long Integers 16 XL 32 bit signed/unsigned (fast, not retained)
Fast Double Word 16 XDW 32 bit unsigned (fast, not retained)
Timers 32 T Res. 10 ms; max 99h, 59 min, 59.99s
Counters 16 C 32-bit

Communication Ports

Notes:

10. The user may order and install one or both of the following modules: A serial RS232/RS485 isolated/non-isolated interface module, or an Ethernet Interface module in port 2. CANbus modules documentation is available on the Unitronics website.

Miscellaneous

Environment

Disclaimer

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.

All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.

The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.

Document reference: UG_SM35_43_70_RA22.pdf 10/22

Models: SM35-J-RA22 3.5 Inch Programmable Logic Controller, SM35-J-RA22, 3.5 Inch Programmable Logic Controller, Logic Controller, Controller

File Info : application/pdf, 20 Pages, 1,006.71KB

PDF preview unavailable. Download the PDF instead.

UG SM35 43 70 RA22 Microsoft Word for Microsoft 365

Related Documents

Preview Unitronics Vision V120 & M91 PLC User Guide
Comprehensive user guide for Unitronics Vision V120 and M91 series PLC controllers, covering installation, wiring, technical specifications, and safety guidelines for hazardous and ordinary locations.
Preview Unitronics V200-18-E6B Snap-in I/O Module: Features, Specifications, and Wiring
Detailed technical specifications, features, safety guidelines, and wiring instructions for the Unitronics V200-18-E6B Snap-in I/O Module. Covers digital and analog inputs/outputs, relay and transistor outputs, and UL compliance.
Preview Unitronics Vision PLC+HMI User Guide and Technical Specifications
Comprehensive user guide and technical specifications for Unitronics Vision PLC+HMI series, including V130, V350, and V430 models. Covers installation, wiring, power supply, communication, and environmental considerations.
Preview Unitronics V570-57-T34 OPLC User Guide
Comprehensive user guide for the Unitronics V570-57-T34 OPLC, covering general description, communications, I/O options, wiring, power supply, and technical specifications.
Preview Unitronics Product Catalog and Specifications | YURSAT
Explore the comprehensive range of Unitronics automation products, including PLCs, HMIs, and I/O modules, available through YURSAT. Find detailed product listings, model numbers, and specifications for industrial automation solutions.
Preview Unitronics: Integrated Control and Automation Solutions
Explore Unitronics' comprehensive range of PLC+HMI controllers and Variable Frequency Drives (VFDs). Offering integrated solutions for industrial automation, Industry 4.0, and efficient control with user-friendly software and outstanding support.
Preview Unitronics Vision PLC+HMI Installation Guide
This guide provides detailed information on the installation, wiring, and specifications of Unitronics Vision PLC+HMI series controllers, including models V130, V350, and V430.
Preview Unitronics Vision PLC+HMI Installation Guide
Comprehensive installation guide for Unitronics Vision PLC+HMI series, covering models V130, V350, and V430. Details mounting, wiring, power supply, and communication setup for industrial automation.