Schneider Electric Modicon M221 Logic Controller, 40 IO, Relay (TM221C40R)
Product Data Sheet
Specifications
Product or Component Type: Modicon M221 Logic controller
Range of Product: Modicon M221
[Us] rated supply voltage: 100...240 V AC
Discrete input number: 24, discrete input IEC 61131-2 Type 1
Analogue input number: 2
Analogue input voltage: 0...10 V
Discrete output type: Relay normally open
Discrete output number: 16 relay
Discrete output voltage: 5...125 V DC / 5...250 V AC
Discrete output current: 2 A
Complementary
Discrete I/O number: 40
Maximum number of I/O expansion module: 7 (local I/O-Architecture), 14 (remote I/O-Architecture)
Supply voltage limits: 85...264 V
Network Frequency: 50/60 Hz
Inrush current: 40 A
Maximum power consumption in VA: 67 VA (100...240 V with max number of I/O expansion module), 37 VA (100...240 V without I/O expansion module)
Power supply output current: 0.52 A (5 V expansion bus), 0.24 A (24 V expansion bus)
Discrete input logic: Sink or source (positive/negative)
Discrete input voltage: 24 V DC
Discrete input voltage type: DC
Analogue input resolution: 10 bits
LSB value: 10 mV
Conversion time: 1 ms per channel + 1 controller cycle time analog input
Permitted overload on inputs: +/- 30 V DC (5 min maximum) analog input, +/- 13 V DC (permanent) analog input
Voltage state 1 guaranteed: >= 15 V input
Voltage state 0 guaranteed: <= 5 V input
Discrete input current: 7 mA (discrete input), 5 mA (fast input)
Input impedance: 3.4 kOhm (discrete input), 100 kOhm (analog input), 4.9 kOhm (fast input)
Response time: 35 µs turn-off, 12...15 µs input; 10 ms turn-on output; 10 ms turn-off output; 5 µs turn-on (10, 11, 16, 17 fast input), 35 µs turn-on (other terminals input); 5 µs turn-off (10, 11, 16, 17 fast input), 100 µs turn-off (other terminals input)
Configurable filtering time: 0 ms input, 3 ms input, 12 ms input
Output voltage limits: 125 V DC, 277 V AC
Maximum current per output common: 7 A
Absolute accuracy error: +/-1% of full scale analog input
Electrical durability: 100,000 cycles AC-12 (120 V, 240 VA, resistive), 100,000 cycles AC-12 (240 V, 480 VA, resistive), 300,000 cycles AC-12 (120 V, 80 VA, resistive), 300,000 cycles AC-12 (240 V, 160 VA, resistive), 100,000 cycles AC-15 (cos phi = 0.35, 120 V, 60 VA, inductive), 100,000 cycles AC-15 (cos phi = 0.35, 240 V, 120 VA, inductive), 300,000 cycles AC-15 (cos phi = 0.35, 120 V, 18 VA, inductive), 300,000 cycles AC-15 (cos phi = 0.35, 240 V, 36 VA, inductive), 100,000 cycles AC-14 (cos phi = 0.7, 120 V, 120 VA, inductive), 100,000 cycles AC-14 (cos phi = 0.7, 240 V, 240 VA, inductive), 300,000 cycles AC-14 (cos phi = 0.7, 120 V, 36 VA, inductive), 300,000 cycles AC-14 (cos phi = 0.7, 240 V, 72 VA, inductive), 100,000 cycles DC-12 (24 V, 48 W, resistive), 300,000 cycles DC-12 (24 V, 16 W, resistive), 100,000 cycles DC-13 (24 V, 24 W, inductive (L/R = 7 ms)), 300,000 cycles DC-13 (24 V, 7.2 W, inductive (L/R = 7 ms))
Switching frequency: 20 switching operations/minute with maximum load
Mechanical durability: 20,000,000 cycles relay output
Minimum load: 1 mA (5 V DC relay output)
Protection type: Without protection (5 A)
Reset time: 1 s
Memory capacity: 256 kB user application and data RAM, 10000 instructions; 256 kB internal variables RAM; 256 kB built-in flash memory backup of application and data
Data backed up: 256 kB built-in flash memory backup of application and data
Data storage equipment: 2 GB SD card (optional)
Battery type: BR2032 or CR2032X lithium non-rechargeable
Backup time: 1 year (at 77 °F (25 °C) by interruption of power supply)
Execution time for 1 KInstruction: 0.3 ms (event and periodic task)
Execution time per instruction: 0.2 µs (Boolean)
Exct time for event task: 60 µs (response time)
Maximum size of object areas: 512 %M memory bits, 512 %KW constant words, 8000 %MW memory words, 255 %C counters, 255 %TM timers
Realtime clock: With
Clock drift: <= 30 s/month (at 77 °F (25 °C))
Regulation loop: Adjustable PID regulator up to 14 simultaneous loops
Counting input number: 4 fast input (HSC mode) 100 kHz 32 bits
Connections and Schema
Integrated connection type: USB port mini B USB 2.0, Non-isolated serial link serial 1 RJ45 RS485, Non-isolated serial link serial 2 RJ45 RS232/RS485
Supply: Serial link supply 5 V, <200 mA
Transmission rate: 1.2...115.2 kbit/s (115.2 kbit/s by default) (49.2 ft (15 m) RS485), 1.2...115.2 kbit/s (115.2 kbit/s by default) (9.8 ft (3 m) RS232), 480 Mbit/s USB
Communication port protocol: USB port USB - SoMachine-Network, Non-isolated serial link Modbus master/slave - RTU/ASCII or SoMachine-Network
Local signalling: 1 LED (green) for PWR, 1 LED (green) for RUN, 1 LED (red) for module error (ERR), 1 LED (green) for SD card access (SD), 1 LED (red) for BAT, 1 LED (green) for SL1, 1 LED (green) for SL2, 1 LED per channel (green) for I/O state
Electrical connection: Removable screw terminal block for inputs, Removable screw terminal block for outputs, Terminal block (3 for connecting the 24 V DC power supply), Connector (4 for analogue inputs), Mini B USB 2.0 connector for a programming terminal
Maximum cable distance between devices: Shielded cable <32.8 ft (10 m) fast input, Unshielded cable <98.4 ft (30 m) output, Unshielded cable <98.4 ft (30 m) digital input, Unshielded cable <3.3 ft (1 m) analog input
Insulation: Between input and internal logic 500 V AC, Non-insulated between analogue input and internal logic, Non-insulated between analogue inputs, Between supply and ground 1500 V AC, Between sensor power supply and ground 500 V AC, Between input and ground 500 V AC, Between output and ground 1500 V AC, Between supply and internal logic 2300 V AC, Between sensor power supply and internal logic 500 V AC, Between output and internal logic 2300 V AC, Between Ethernet terminal and internal logic 500 V AC, Between supply and sensor power supply 2300 V AC
Marking: CE, cULus, EAC, UKCA, cULus HazLoc
Sensor power supply: 24 V DC 250 mA supplied by the controller
Mounting support: Top hat type TH35-15 rail IEC 60715, Top hat type TH35-7.5 rail IEC 60715, Plate or panel with fixing kit
Height: 3.5 in (90 mm)
Depth: 2.8 in (70 mm)
Width: 6.3 in (160 mm)
Product Weight: 1.005 lb(US) (0.456 kg)
Environment
Standards: IEC 61131-2, UL 508, CAN/CSA C22.2 No. 213, IACS E10, ANSI/ISA 12-12-01
Environmental characteristic: Ordinary and hazardous location
Resistance to electrostatic discharge: 8 kV in air IEC 61000-4-2, 4 kV on contact IEC 61000-4-2
Resistance to electromagnetic fields: 9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3, 2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3, 0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3
Resistance to magnetic fields: 98.4 A/m (30 A/m) 50/60 Hz IEC 61000-4-8
Resistance to fast transients: 2 kV IEC 61000-4-4 (power lines), 2 kV IEC 61000-4-4 (relay output), 1 kV IEC 61000-4-4 (I/O), 1 kV IEC 61000-4-4 (Ethernet line), 1 kV IEC 61000-4-4 (serial link)
Surge withstand: 2 kV power lines (AC) common mode IEC 61000-4-5, 2 kV relay output common mode IEC 61000-4-5, 1 kV I/O common mode IEC 61000-4-5, 1 kV shielded cable common mode IEC 61000-4-5, 0.5 kV power lines (DC) differential mode IEC 61000-4-5, 1 kV power lines (AC) differential mode IEC 61000-4-5, 1 kV relay output differential mode IEC 61000-4-5, 0.5 kV power lines (DC) common mode IEC 61000-4-5
Resistance to conducted disturbances: 10 V (0.15...80 MHz) IEC 61000-4-6, 3 V (0.1...80 MHz) Marine specification (LR, ABS, DNV, GL), 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission: Conducted emissions 79 dBμV/m QP/66 dBμV/m AV power lines (AC) 0.15...0.5 MHz IEC 55011, Conducted emissions 73 dBμV/m QP/60 dBuV/m AV power lines (AC) 0.5...300 MHz IEC 55011, Conducted emissions 120...69 dBμV/m QP power lines 10...150 kHz IEC 55011, Conducted emissions 63 dBμV/m QP power lines 1.5...30 MHz IEC 55011, Radiated emissions 40 dBμV/m QP class A 10 m 30...230 MHz IEC 55011, Conducted emissions 79...63 dBμV/m QP power lines 150...1500 kHz IEC 55011, Radiated emissions 47 dBμV/m QP class A 10 m 200...1000 MHz IEC 55011
Immunity to microbreaks: 10 ms
Ambient air temperature for operation: 14...131 °F (-10...55 °C) horizontal installation, 14...95 °F (-10...35 °C) vertical installation
Ambient Air Temperature for Storage: -13...158 °F (-25...70 °C)
Relative humidity: 10...95%, without condensation in operation, 10...95%, without condensation in storage
IP degree of protection: IP20 with protective cover in place
Pollution degree: 2
Operating altitude: 0...6561.68 ft (0...2000 m)
Storage altitude: 0...9842.5 ft (0...3000 m)
Vibration resistance: 3.5 mm 5...8.4 Hz symmetrical rail, 3.5 mm 5...8.4 Hz panel mounting, 1 gn 8.4...150 Hz symmetrical rail, 1 gn 8.4...150 Hz panel mounting
Shock resistance: 98 m/s² 11 ms
Product Certifications
RCM, LR, cULus, DNV-GL, ABS, EAC, CE, UKCA, cULus HazLoc
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.30 in (10.92 cm)
Package 1 Width: 5.70 in (14.48 cm)
Package 1 Length: 8.30 in (21.08 cm)
Package 1 Weight: 30.0 oz (850 g)
Unit Type of Package 2: CAR
Number of Units in Package 2: 12
Package 2 Height: 11.57 in (29.4 cm)
Package 2 Width: 15.55 in (39.5 cm)
Package 2 Length: 21.93 in (55.7 cm)
Package 2 Weight: 24.297 lb(US) (11.021 kg)
Unit Type of Package 3: P12
Number of Units in Package 3: 144
Package 3 Height: 41.34 in (105.0 cm)
Package 3 Width: 47.24 in (120.0 cm)
Package 3 Length: 31.50 in (80.0 cm)
Package 3 Weight: 321.9 lb(US) (146 kg)
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.
Environmental footprint: Carbon footprint (kg CO2 eq, Total Life cycle): 115
Materials and Substances: Packaging made with recycled cardboard: Yes, Packaging without single use plastic: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
REACH Regulation: REACH Declaration
California proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
PVC free: Yes
Repack and remanufacture: End of Life Information
Take-back: No
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Dimensions Drawings
Dimensions:
mm: 75.9 (2.99), 163 (6.42), 103.6 (4.08)
in.: 75.9 (2.99), 163 (6.42), 103.6 (4.08)
Mounting and Clearance
Mounting on a Rail
Correct Mounting Position: [Image of correct mounting position]
Acceptable Mounting Position: [Image of acceptable mounting position]
Incorrect Mounting Position: [Image of incorrect mounting position]
Direct Mounting on a Panel Surface
(1) Install a mounting strip
[Image of direct mounting on a panel surface]
Mounting Hole Layout
Dimensions: M4 x 6/8 mm (0.24/0.31 in.)
Layout: [Diagram showing mounting hole layout with dimensions]
Clearance
[Diagram showing required clearance around the unit]
Connections and Schema
Digital Inputs
Wiring Diagram (Positive Logic): [Diagram of positive logic wiring for digital inputs]
(*) Type T fuse
Wiring Diagram (Negative Logic): [Diagram of negative logic wiring for digital inputs]
(*) Type T fuse
Connection of the Fast Inputs: [Diagram showing connection of fast inputs]
Inputs: 10, 11, 16, 17
Relay Outputs
Negative Logic (Sink): [Diagram of negative logic (sink) relay outputs]
(1) The COMO, COM1, COM2 and COM3 terminals are not connected internally.
(2) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load.
Sink wiring (negative logic): [Diagram illustrating sink wiring]
Positive Logic (Source): [Diagram of positive logic (source) relay outputs]
(1) The COMO, COM1, COM2 and COM3 terminals are not connected internally.
(2) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load.
Source wiring (positive logic): [Diagram illustrating source wiring]
Analog Inputs
[Image showing analog input connection]
Input Terminals: 0 V AN1, 0 V AND
Voltage: 0...10 V
The (-) poles are connected internally.
Pinout:
Pin | Wire Color |
---|---|
0 V | Black |
AN1 | Red |
0 V | Black |
ANO | Red |
USB Mini-B Connection
[Diagram showing USB Mini-B connection with cables and lengths]
Cable 1: TCSXCNAMUM3P (3 m/9.8 ft)
Cable 2: BMXXCAUSBH018 (1.8 m/5.9 ft)
SL1 Connection
[Diagram of SL1 RJ45 connector pinout]
N° | RS 232 | RS 485 |
---|---|---|
1 | RxD | N.C. |
2 | TxD | N.C. |
3 | RTS | N.C. |
4 | N.C. | D1 |
5 | N.C. | D0 |
6 | CTS | N.C. |
7 | N.C.* | 5 Vdc |
8 | Common | Common |
N.C.: not connected
*: 5 Vdc delivered by the controller. Do not connect.
[Diagram showing SL1 connection to DCE and DTE devices via RJ45 and SUB D 9 pin connectors]
SL2 Connection
[Diagram of SL2 RJ45 connector pinout]
N° | RS 485 |
---|---|
1 | N.C. |
2 | N.C. |
3 | N.C. |
4 | D1 |
5 | D0 |
6 | N.C. |
7 | N.C. |
8 | Common |
N.C.: not connected
Performance Curves
Derating Curves
Embedded Digital Inputs (No Cartridge)
[Graph showing derating curve for embedded digital inputs without cartridge]
X: Ambient temperature
Y: Input simultaneous ON ratio
Embedded Digital Inputs (with Cartridge)
[Graph showing derating curve for embedded digital inputs with cartridge]
X: Ambient temperature
Y: Input simultaneous ON ratio
Related Documents
![]() |
Schneider Electric Modicon M221 TM221C24R Logic Controller Data Sheet Detailed technical specifications, features, environmental data, and ordering information for the Schneider Electric Modicon M221 TM221C24R logic controller. |
![]() |
Schneider Electric Modicon M221, 16 IO, Relay (TM221M16R) Product Data Sheet Detailed product data sheet for the Schneider Electric Modicon M221, 16 IO, Relay (TM221M16R). Includes specifications, electrical characteristics, environmental data, and connection diagrams. |
![]() |
Schneider Electric Modicon M221 TM221ME16R Logic Controller Data Sheet Detailed technical specifications for the Schneider Electric Modicon M221 TM221ME16R logic controller, including main and complementary features, environmental data, ordering information, and connection diagrams. |
![]() |
Schneider Electric Modicon M221 Data Sheet Comprehensive data sheet for the Schneider Electric Modicon M221 logic controller, detailing specifications, features, and environmental data. Includes information on I/O, power, communication, and mounting. |
![]() |
Modicon M221 Logic Controller, 40 IO, Relay, Ethernet - Product Data Sheet Detailed product data sheet for the Schneider Electric Modicon M221 logic controller. This document provides comprehensive specifications, electrical and environmental data, ordering and shipping details, and connection diagrams for the TM221CE40R model. |
![]() |
Schneider Electric Modicon M221 Logic Controller Datasheet Detailed technical specifications, features, and environmental data for the Schneider Electric Modicon M221 logic controller, model TM221C24T, a 24 IO transistor PNP controller. |
![]() |
Schneider Electric Modicon M221 TM221C16T Logic Controller Data Sheet Detailed technical specifications and data for the Schneider Electric Modicon M221 TM221C16T logic controller, including main features, complementary specifications, environmental data, dimensions, mounting instructions, and performance curves. |
![]() |
Schneider Electric SR2A101FU Zelio Logic Compact Smart Relay Data Sheet Technical data sheet for the Schneider Electric SR2A101FU Zelio Logic compact smart relay, detailing specifications, characteristics, environmental conditions, electrical durability, dimensions, and connection schematics for automation applications. |