3M™ Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

With High-K Stress Relief

For Tape Shielded, Wire Shielded and UniShield® Cable

Model: 7620-S-2

Type: Instructions

Standards: IEEE Std. No. 48, Class 1 Termination, 5/8 kV Class, 95 kV BIL

⚠️ CAUTION: Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product.

May 2013 | Document ID: 78-8117-0508-2 Rev D

1.0 Kit Contents

? NOTE: Do Not use knives to open plastic bags.

Kit Selection Table

? NOTE: Final Determination Factor is cable insulation diameter.

Table 1: Kit Selection
Kit Number Primary Insulation O.D. Range Jacket O.D. Range Conductor Size Range (AWG)
5 kV 100% 133% 8 kV 100% 133%
7620-S-2 0.32"–0.59" (8,1 – 15,0 mm) 0.52" – 0.78" (13,3 – 19,9 mm) 8 – 4 8 – 6

Instructions For Tape Shielded Cable

2.0 Prepare Cable

  1. Check to be sure cable size fits within kit range as shown in Table 1.
  2. Prepare cable using dimensions shown in Figure 1. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M™ EMI Copper Foil Shielding Tape 1181.

? NOTE: Provide additional 1/4" (6 mm) exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors.

? NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

Figure 1: Cable Preparation Diagram
Shows cable jacket removal. Dimensions indicated are: Jacket Removal Length (1" / 25 mm), Depth Of Terminal Lug + Growth Allowance (6 3/4" / 171 mm), and a section of 2" (51 mm) for the semi-con layer. The diagram illustrates the cable jacket, semi-con layer, and tape shield.

3.0 Install Ground Braid

  1. Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a SINGLE WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 2). Cut off excess.
Figure 2: Mastic Application Diagram
Illustrates applying a single wrap of mastic strip 1/4" (6 mm) from the cut edge of the cable jacket. Shows cable jacket, semi-con, tape shield, and the mastic strip.
  1. Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 3). Secure ground braid to cable jacket 3 1/2" (89 mm) from cable semi-con edge using vinyl tape (Figure 3).

? NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

Figure 3: Ground Braid Positioning Diagram
Shows the pre-formed ground braid positioned with a short tail over the tape shield and a long tail extending over the cable jacket, secured by vinyl tape. Includes labels for: Semi-Con Edge, Tape Shield, Ground Braid, Cable Jacket Edge, Solder Block, 1ST Scotch® Mastic Strip 2230, and Vinyl Tape Marker. The dimension 3 1/2" (89 mm) is indicated.
  1. Wrap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 4). Cinch (tighten) the spring after wrapping the final winding.
  2. Select second Scotch® Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 4). Cut off excess.
Figure 4: Mastic and Spring Application Diagram
Illustrates applying a second mastic strip over the solder block and ground braid, followed by securing with a constant force spring. Shows components: Constant Force Spring, Tape Shield, Ground Braid, 1ST Scotch® Mastic Strip 2230, Solder Block, 2nd Scotch® Mastic Strip 2230, Ground Braid Leg, and Trim indication for Cable Tape Shield.
  1. Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed tape shield (Figure 5).

? NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 3/4" (19 mm) must be exposed.

SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELD: In cables with cloth or paper semi-conductive shields it is recommended the shield be over wrapped with one half-lapped layer of highly stretched semi-conductive rubber tape such as Scotch® Electrical Semi-Conducting Tape 13.

Figure 5: Vinyl Tape Wrapping Diagram
Shows two half-lapped layers of electrical grade vinyl tape wrapped over the mastic seal and constant force spring. Includes labels for: Semi-Con, Tape Shield, Constant Force Spring, Two Half-Lapped Layers of Electrical Grade Vinyl Tape, Scotch® Mastic Strip 2230, and Vinyl Tape Marker.

4.0 Install Lug or Connector

  1. Check to insure 3M™ Cold Shrink QT–III Silicone Rubber Termination assembly fits over the selected lug or connector. If lug or connector (Figure 6) will not fit through the termination core, clean the insulation (per Step 5.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.
Figure 6: Lug/Connector Fit Diagram
Illustrates a cable termination assembly with a lug or connector, indicating the 'Clearance' required. Shows the termination assembly and the connector/lug.

? NOTE: Refer to pages 18 – 20 for 3M Connector and Lug crimping information.

? NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into lug or connector barrel as far as it will go.

  1. Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping.

5.0 Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice

  1. Wipe the cable insulation with one of the solvent saturated pads from the 3M™ Cable Cleaning Preparation Kit CC-2. DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD!
  2. If abrasive must be used:
    1. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD!
    2. Use only aluminum oxide abrasive; grit 120 or finer, included in the 3M™ Cable Cleaning Preparation Kit CC-2.
    3. Be careful not to reduce the cable insulation diameter below that allowed by the kit.

6.0 Install Termination

Important Packaging Notice

In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste. ♻️

  1. Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 7). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 7).

? NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE.

Figure 7: Termination Installation Diagram
Shows the process of sliding the termination body onto the cable and removing the core by pulling counter-clockwise. Includes a 'Vinyl Tape Marker' as a reference point. A note indicates that the removed material is mixed polymers and can be recycled.
  1. Connect ground braid to system ground according to standard practice.

Correct Installation of Termination on Tape Shielded Cable

Diagram: Correct Termination Installation (Tape Shielded)
A cross-section view showing the correctly installed termination. Key components labeled include: Vinyl Tape Marker, Ridge at End of Stress Controlling Compound, Ridge at End of Cable Insulation Shield (Semi-Con), Semi-Con Insulation Shield, Stress Controlling Compound, Cable Insulation, Conductor, Silicone Rubber Tube, and Environmental Top Seal.

Instructions for Wire Shielded Cable

7.0 Prepare Cable

  1. Check to be sure cable size fits within kit range as shown in Table 1.
  2. Prepare cable using dimensions shown in Figure 8 and Figure 9. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG.

? NOTE: Provide additional 1/4" (6 mm) exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors.

? NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

Figure 8: Cable Preparation Diagram (Wire Shielded)
Shows cable jacket removal for wire shielded cable. Dimensions indicated are: Jacket Removal Length (1" / 25 mm), Depth Of Terminal Lug + Growth Allowance (6 3/4" / 171 mm), and a section of 2" (51 mm) for the semi-con layer. The diagram illustrates the cable jacket, semi-con layer, and shield wires.
  1. Bend leading 1" (25 mm) of exposed shield wires back upon themselves to jacket edge (Figure 9).
Figure 9: Shield Wire Bending Diagram
Illustrates bending the exposed shield wires back to the jacket edge. Shows cable jacket, semi-con, and shield wires. Dimensions indicated are 1" (25 mm) for bent wires and 2" (51 mm) for semi-con.

8.0 Install Ground Braid

  1. Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a SINGLE WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess. ✂️
Figure 10: Mastic Application Diagram (Wire Shielded)
Illustrates applying a single wrap of mastic strip 1/4" (6 mm) from the cut edge of the cable jacket. Shows cable jacket, semi-con, and the mastic strip.
  1. Position pre-formed ground braid with short tail over wire shield directly adjacent to cable jacket cut edge. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 11). Secure ground braid to cable jacket 3 1/2" (89 mm) from cable semi-con edge using vinyl tape (Figure 11).

? NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

Figure 11: Ground Braid Positioning Diagram (Wire Shielded)
Shows the pre-formed ground braid positioned with a short tail over the wire shield and a long tail extending over the cable jacket, secured by vinyl tape. Includes labels for: Semi-Con Edge, Shield Wires, Ground Braid, Cable Jacket Edge, Solder Block, 1ST Scotch® Mastic Strip 2230, and Vinyl Tape Marker. The dimension 3 1/2" (89 mm) is indicated.
  1. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 12). Cinch (tighten) ⚙️ the spring after wrapping the final winding.
  2. Select second Scotch® Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 12). Cut off excess. ✂️
Figure 12: Mastic and Spring Application Diagram (Wire Shielded)
Illustrates applying a second mastic strip over the solder block and ground braid, followed by securing with a constant force spring. Shows components: Constant Force Spring, Shield Wires, Ground Braid, 1ST Scotch® Mastic Strip 2230, Solder Block, 2nd Scotch® Mastic Strip 2230, Ground Braid Leg, and Trim indication for Cable Wire Shield.
  1. Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 13).

? NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 3/4" (19 mm) must be exposed.

SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATED SHIELD: In cables with cloth or paper semi-conductive shields, it is recommended the shield be over wrapped with one half-lapped layer of highly stretched semi-conductive rubber tape such as Scotch® Electrical Semi-Conducting Tape 13.

Figure 13: Vinyl Tape Wrapping Diagram (Wire Shielded)
Shows two half-lapped layers of electrical grade vinyl tape wrapped over the mastic seal and constant force spring. Includes labels for: Semi-Con, Shield Wires, Constant Force Spring, Two Half-Lapped Layers of Electrical Grade Vinyl Tape, Scotch® Mastic Strip 2230, and Vinyl Tape Marker. The dimension 1" (25 mm) is indicated.

9.0 Install Lug or Connector

  1. Check to insure the 3M™ Cold Shrink QT–III Silicone Rubber Termination assembly fits over the selected lug or connector. If lug or connector (Figure 14) will not fit through the termination core, clean the insulation (per Step 10.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.
Figure 14: Lug/Connector Fit Diagram
Illustrates a cable termination assembly with a lug or connector, indicating the 'Clearance' required. Shows the termination assembly and the connector/lug.

? NOTE: Refer to pages 18 – 20 for 3M Connector and Lug crimping information.

  1. Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping.

10.0 Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice

  1. Wipe the cable insulation with one of the solvent saturated pads from the 3M™ Cable Cleaning Preparation Kit CC-2. DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD!
  2. If abrasive must be used:
    1. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD!
    2. Use only aluminum oxide abrasive; grit 120 or finer, included in 3M™ Cable Cleaning Preparation Kit CC-2.
    3. Be careful not to reduce the cable insulation diameter below that allowed by the kit.

11.0 Install Termination

Important Packaging Notice

In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste. ♻️

  1. Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 15). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 15).

? NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE.

Figure 15: Termination Installation Diagram (Wire Shielded)
Shows the process of sliding the termination body onto the cable and removing the core by pulling counter-clockwise. Includes a 'Vinyl Tape Marker' as a reference point. A note indicates that the removed material is mixed polymers and can be recycled.
  1. Connect ground braid to system ground according to standard practice.

Correct Installation of Termination on Wire Shielded Cable

Diagram: Correct Termination Installation (Wire Shielded)
A cross-section view showing the correctly installed termination. Key components labeled include: Vinyl Tape Marker, Ridge at End of Stress Controlling Compound, Ridge at End of Cable Insulation Shield (Semi-Con), Semi-Con Insulation Shield, Stress Controlling Compound, Cable Insulation, Conductor, Silicone Rubber Tube, and Environmental Top Seal.

Instructions for UniShield® Shielded Cable

12.0 Prepare Cable

  1. Check to be sure cable size fits within kit range as shown in Table 1.
  2. Prepare cable using dimensions shown in Figures 16, 17 and 18. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG.

? NOTE: Provide additional 1/4" (6 mm) exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors.

  1. Install constant force spring as shown in Figure 16. Pull shield wires through semi-conductive jacket to leading edge of constant force spring (Figure 16).
Figure 16: Spring Installation Diagram (UniShield®)
Shows the installation of a constant force spring and pulling shield wires through the semi-conductive jacket. Dimensions indicated are: Depth Of Terminal Lug + Growth Allowance (5 3/4" / 146 mm). Includes labels for Constant Force Spring, Shield Wires, and Semi-Conductive Jacket.
  1. Remove constant force spring. Bend shield wires back upon cable jacket 1" (25 mm). Cut excess shield wire and discard. ✂️ (Figure 17).
Figure 17: Shield Wire Bending Diagram (UniShield®)
Illustrates bending shield wires back onto the cable jacket by 1" (25 mm). Dimensions indicated are: Depth Of Terminal Lug + Growth Allowance (6 3/4" / 171 mm). Includes labels for Semi-Conductive Jacket and Fold Back Shield Wires.
  1. Remove semi-conductive jacket to dimension shown in Figure 18.

? NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring cut 80% through jacket. Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CON JACKET. Remove constant force spring.

? NOTE: It is imperative to remove all remnants of the semi-conductive jacket, even if the semi-conductive jacket comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

Figure 18: Semi-Con Jacket Removal Diagram (UniShield®)
Shows the removal of the semi-conductive jacket. Dimensions indicated are: Depth Of Terminal Lug + Growth Allowance (4 3/4" / 121 mm), 2" (51 mm), and 1" (25 mm). Includes labels for Semi-Conductive Jacket, Cut Line, Constant Force Spring, and Fold Back Shield Wires.

13.0 Install Ground Braid

  1. Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a SINGLE WRAP of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires (Figure 19). Cut off excess. ✂️
Figure 19: Mastic Application Diagram (UniShield®)
Illustrates applying a single wrap of mastic strip 1/4" (6 mm) from the shield wires onto the cable semi-conductive jacket. Shows Semi-Con, Shield Wires, and 1ST Scotch® Mastic Strip 2230.
  1. Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. Position long tail of ground braid, extending over cable semi-conductive jacket with solder block over mastic strip (Figure 20). Secure ground braid to cable semi-conductive jacket 3 1/2" (89 mm) from cable semi-con edge using vinyl tape (Figure 20).

? NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

Figure 20: Ground Braid Positioning Diagram (UniShield®)
Shows the pre-formed ground braid positioned with a short tail over the shield wires and a long tail extending over the cable semi-conductive jacket, secured by vinyl tape. Includes labels for: Semi-Con Edge, Shield Wires, Ground Braid, Solder Block, 1ST Scotch® Mastic Strip 2230, and Vinyl Tape Marker. The dimension 3 1/2" (89 mm) is indicated.
  1. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 21). Cinch (tighten) ⚙️ the spring after wrapping the final winding.
  2. Select second Scotch® Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 21). Cut off excess. ✂️
Figure 21: Mastic and Spring Application Diagram (UniShield®)
Illustrates applying a second mastic strip over the solder block and ground braid, followed by securing with a constant force spring. Shows components: Constant Force Spring, Shield Wires, Ground Braid, 1ST Scotch® Mastic Strip 2230, Solder Block, 2nd Scotch® Mastic Strip 2230, Ground Braid Leg, and Trim indication for Cable Wire Shield.
  1. Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 22).

? NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 3/4" (19 mm) must be exposed.

Figure 22: Vinyl Tape Wrapping Diagram (UniShield®)
Shows two half-lapped layers of electrical grade vinyl tape wrapped over the mastic seal and constant force spring. Includes labels for: Semi-Con, Shield Wires, Constant Force Spring, Two Half-Lapped Layers of Electrical Grade Vinyl Tape, Scotch® Mastic Strip 2230, and Vinyl Tape Marker. The dimension 1" (25 mm) is indicated.

14.0 Install Lug or Connector

  1. Check to insure the 3M™ Cold Shrink QT–III Silicone Rubber Termination assembly fits over the selected lug or connector. If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.
Figure 23: Lug/Connector Fit Diagram
Illustrates a cable termination assembly with a lug or connector, indicating the 'Clearance' required. Shows the termination assembly and the connector/lug.

? NOTE: Refer to pages 18 – 20 for 3M Connector and Lug crimping information.

  1. Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping.

15.0 Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice

  1. Wipe the cable insulation with one of the solvent saturated pads from the 3M™ Cable Cleaning Preparation Kit CC-2. DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD!
  2. If abrasive must be used:
    1. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD!
    2. Use only aluminum oxide abrasive; grit 120 or finer, included in 3M™ Cable Cleaning Preparation Kit CC-2.
    3. Be careful not to reduce the cable insulation diameter below that allowed by the kit.

16.0 Install Termination

Important Packaging Notice

In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste. ♻️

  1. Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 24). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 24).

? NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE.

Figure 24: Termination Installation Diagram (UniShield®)
Shows the process of sliding the termination body onto the cable and removing the core by pulling counter-clockwise. Includes a 'Vinyl Tape Marker' as a reference point. A note indicates that the removed material is mixed polymers and can be recycled.
  1. Connect ground braid to system ground according to standard practice.

Correct Installation of Termination on UniShield® Shielded Cable

Diagram: Correct Termination Installation (UniShield®)
A cross-section view showing the correctly installed termination. Key components labeled include: Vinyl Tape Marker, Ridge at End of Stress Controlling Compound, Ridge at End of Cable Insulation Shield (Semi-Con), Semi-Con, Stress Controlling Compound, Cable Insulation, Conductor, Silicone Rubber Tube, and Environmental Top Seal.

Tooling Index

Lug and Crimping Information for 3M™ Scotchlok™ Copper Lugs

Table 2: Lug and Crimping Information (Copper Lugs)
Cable Size AWG/ kcmil Stud Size (in.) 3M™ Scotchlok™ Copper Lug Number Burndy Corporation Thomas & Betts Corporation Square D Co. Anderson Div.
MD6 MY29 Y34A Y35, Y39, Y45*, Y46* TBM 5 TBM 8 TBM 15
610300146AWG(1)U5CRT(1)Blue(1)Blue(1)(1)
1/430015
5/1630016
41/430018
3/830019W161(1)4AWG(1)A4CR(1)U4CRT(1)Grey(1)Grey(1)(1)
3/830021
21/430022
5/1630023W162(2)2AWG(1)A2CR(1)U2CRT(2)Brown(1)Brown(1)33(1)(2)
3/830024
15/16300271AWG(1)A1CR(1)U1CRT(2)Green(1)Green(1)37(1)(2)
3/830028
1/05/1630031W163(2)1/0(1)A25R(1)U25RT(1)Pink(2)Pink(2)42H(2)(1)
3/830032
2/03/830036W241(2)2/0(1)A26R(1)U26RT(2)Black(2)Black(2)45(1)(1)
3/831036W241(3)2/0(2)A26R(2)U26RT(3)Black(3)Black(3)45(2)(2)
3/01/230041W243(2)3/0(1)A27R(1)U27RT(2)Orange(2)Orange(2)50(1)(2)
1/231041W243(3)3/0(2)A27R(2)U27RT(3)Orange(3)Orange(3)50(2)(3)
4/01/230045BG(3)4/0(1)U28RT(2)Purple(2)Purple(2)54H(2)(2)
1/231045BG(4)4/0(2)A28R(2)U28RT(3)Purple(3)Purple(3)54H(3)(3)
1/231145BG(4)4/0(2)U28RT(3)Purple(3)Purple(3)54H(3)(3)
2501/231049W166(4)250(2)A29R(2)U29RT(3)Yellow(2)Yellow(2)62(2)(2)
1/231149
3001/231053A30R(2)U30RT(3)White(3)66(3)(3)
1/231153
3501/231056A31R(2)U31RT(3)Red(4)71H(4)
1/231156
4001/231060A32R(2)U32RT(3)Blue(4)76H(4)
1/231160
5001/231066A34R(2)U34RT(3)Brown(4)87H(4)
5/831067
1/231166
6001/231068U36RT(3)Green(4)94H(4)
1/231168
7501/231172Y39, Y45, Y46 U39RT(5)106H(4)
10001/231178Y45: S44RT(6) Y46: P44RT(6)125H(4)

* Y45 and Y46 accept all Y35 dies (“U” series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.

** Anderson VC6-3 and VC6-FT require no die set.

Crimping Information for 3M™ Stem Connectors Copper/Aluminum

Table 3: Crimping Information (3M™ Stem Type Connector)
Conductor Size AWG & kcmil 3M™ Connector Number Manufacturer Recommended Crimping Tools Die (Minimum No. Crimps) Hydraulic Die (Minimum No. Crimps)
Mech. Tool Die (Minimum No. Crimps)
StrandedSolid
2, 11, 1/0SC0001BurndyMD6BG(4), W243(4)Y35, Y39, Y45*12, 20, 40, TonU25ART(2), U243(2)
42/0SC0002Kearny0–51, 0–525/8–1 (4)5/8-1(4)
1/0SC0010T & BTBM 5Tan(2)
2/0T & BTBM 8Olive(2)TBM 1550(2)
AndersonVC6(2)
2/03/0SC0020BurndyMD6W669(0) 840(5)Y35, Y39, Y45*WH-1, WH-2U28ART(2)
3/04/0SC0030Kearny0–51, 0–52840(5)840(2)
4/0SC0040T & BTBM 8White(4)TBM 1566H(3)
AndersonVC6(2)

* Y45 and Y46 accept all Y35 dies ("U" series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.

** Anderson VC6 is dieless and does not require a die set.

Important Notice

All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M.

Warranty; Limited Remedy; Limited Liability.

This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted.

PDF preview unavailable. Download the PDF instead.

f5e27c03d7a3126e6ca14deb4b310088c835f8d4 GPL Ghostscript 9.23 Adobe InDesign CS6 (Windows)

Related Documents

Preview 3M™ Cold Shrink QS-III Splicing Kit 5776A-MT Installation Instructions
Detailed installation instructions for the 3M™ Cold Shrink QS-III Splicing Kit 5776A-MT, a three-conductor splice kit for use on armor and non-armor cables, including cable preparation, component placement, and splice installation procedures.
Preview 3M™ No Polish LC JG1 Connector for 1.6-2 mm Cable: Installation Instructions
Detailed instructions for terminating 1.6-2 mm fiber optic cables using 3M™ No Polish LC JG1 Connectors (Models 8832-JG1, 6832-50/OM2-JG1, 6832-50/OM4-JG1). Includes safety precautions, overview, materials, step-by-step termination process, duplexing, and re-opening procedures.
Preview 3M Dynatel 2210 Cable Locator Operator's Manual
Operator's manual for the 3M Dynatel 2210 Cable Locator, providing instructions for setup, operation, and technical specifications.
Preview 3M MDR Connector Selection Guide: High Density I/O Solutions
Comprehensive selection guide for 3M™ Mini Delta Ribbon (MDR) connectors and high-speed cable assemblies. Covers features, specifications, part numbers, and applications for industrial data transmission, machine vision, and more.
Preview 3M™ Dynatel™ Locating and Marking System: Product Catalog and Features
Comprehensive guide to 3M™ Dynatel™ locating and marking systems, including markers, locators, accessories, and ordering information for underground asset management.
Preview 3M™ Micropore™ Medical Roll Plaster - Product Information
Detailed product information for 3M™ Micropore™ Medical Roll Plaster, including features, applications, and ordering details for white and beige variants. This breathable, latex-free plaster is designed for secure and gentle adhesion.
Preview 3M Respirator Selection Guide: Protecting Your World
Comprehensive guide from 3M for selecting appropriate respirators based on chemical compounds, exposure limits (OEL, IDLH), and workplace conditions. Includes detailed respirator recommendations and usage instructions.
Preview 3M Japan Group Organizational Restructuring Announcement
Announcement regarding the organizational restructuring of 3M Japan, detailing the separation of sales, marketing, and order processing functions into a wholly-owned subsidiary and the renaming of the remaining entity. Key information on operational continuity and contact details.