Finder 83.11, 83.21, 83.41 Modular Time Relays
Models: 83.11, 83.21, 83.41
Brand: Finder
Product Overview
Finder offers a range of modular time relays, including models 83.11, 83.21, and 83.41. These relays are designed for various time-delay applications in industrial and automation systems.
Key Specifications:
- Voltage Range: (24...240)V AC (50/60 Hz) / DC
- Minimum Voltage: 16.8 V AC/DC
- Maximum Voltage: 265 V AC/DC
- Power Consumption: < 1.5 VA / < 2 W
- Output Contact: 1 CO (SPDT)
- Contact Rating: 16 A, 250 V AC
- AC1 Rating: 4000 VA
- AC15 (230 V AC) Rating: 750 VA
- DC1 Rating: (24/110/220) V (16/0.3/0.12) A
- Operating Temperature: (-20...+60)°C
- IP Rating: IP20
Time Scale Selection
The relays feature a rotary selector for choosing time scales (Tmax) and a knob for adjusting the time delay (Tmin...Tmax).
Diagram 2 shows the time scale selection with options ranging from 0.05s to 10 days.
Time Scale | 0.05...1s | 0.5...10s | 0.05...1min | 0.5...10min | 0.05...1h | 0.5...10h | 0.05...1d | 0.5...10d |
---|---|---|---|---|---|---|---|---|
83.11 | √ | √ | √ | √ | √ | √ | √ | √ |
83.21 | √ | √ | √ | √ | √ | √ | √ | √ |
83.41 | √ | √ | √ | √ | √ | √ | √ | √ |
LED Indicator
An LED indicator is present to show the operational status of the relay.
LED Status | 15-16 | 15-18 |
---|---|---|
On | √ | |
Off | √ |
Connection and Functionality Diagrams
Diagram 1 illustrates the terminal layout for models 83.11, 83.21, and 83.41, showing dimensions and terminal designations.
Model 83.11 / 83.21
Terminals: A1, A2, 15, 16, 18
Model 83.41
Terminals: A1, A2, B1, 15, 16, 18
Dimensions: 86.2 mm height, 100.3 mm length, 22.5 mm width.
Diagram 3 shows connection schemes for 83.11 and 83.21. 3a illustrates start via the supply terminal (A1) with time delay on energization (83.11) or interval timing (83.21).
Diagram 4 shows connection schemes for 83.41. 4a illustrates start via the control terminal (B1) for delayed release with a control signal. 4b shows DC polarity connection to terminal B1. 4c demonstrates external start command via terminal B1 with a different voltage supply.
Additional Data (83.41):
- Minimum control pulse duration: 50 ms
- Reset time: 200 ms
- Mounting: 35 mm DIN rail (EN 60715)
Operating Conditions
In accordance with European standard EMC 2014/30/EU, these time relays offer enhanced immunity to radiated and conducted disturbances compared to EN 61812-1. However, external devices like transformers, motors, contactors, and power cables can cause interference. To mitigate this, keep connection wires short and use protective filters (RC filters, varistors, surge arresters) where necessary.