Finder 83.11, 83.21, 83.41 Modular Timer, Mono-Function
RELAYING INNOVATION
Product Overview
This document provides technical specifications and wiring information for the Finder 83.11, 83.21, and 83.41 modular mono-function timers.
Models: 83.11, 83.21, 83.41
Power Supply: (24...240)V AC (50/60 Hz) / DC
Voltage Range: Umin 16.8 V AC/DC, Umax 265 V AC/DC
Power Consumption: P(AC/DC) < 1.5 VA / < 2 W
Output Contacts: 1 CO (SPDT)
Contact Rating: 16 A 250 V AC
AC1 Rating: 4000 VA
AC15 (230 V AC) Rating: 750 VA
M (230 V AC) Rating: 0.5 kW
DC1 Rating: (24/110/220) V (16/0.3/0.12) A
Operating Temperature: (-20...+60)°C
Protection: IP20
Front View and Time Scales
1 Front View
A: Time scale rotary selector (Tmax)
B: Time setting (Tmin... Tmax)
C: LED indicator
2 Time Scales
Example: For T=10 min, set A=10m and B=T max.
Available time scales include seconds (s), minutes (min), hours (h), and days (d).
Wiring Diagrams and Functions
3 Wiring Diagram and Functions (83.11-83.21)
3a: Start via contact in supply line (A1)
- 83.11: Al On-delay
- 83.21: DI Interval
4 Wiring Diagram and Function (83.41)
Start via contact into control terminal (B1)
BE: Off-delay with control signal
4a: Possible to control an external load, such as another relay coil or timer, connected to the signal start terminal B1.
4b: With DC supply, positive polarity must be connected to B1 terminal (according to EN 60204-1).
4c: A voltage other than the supply voltage can be applied to the command Start (B1), for example:
- A1-A2 = 230 V AC
- B1-A2 = 24 V DC
Other Data (83.41)
- Minimum control impulse: 50 ms
- Recovery time: 200 ms
- Mounting: 35 mm rail mount (EN 60715)
Working Conditions
In conformity with the European Directive on EMC 2014/30/EU, the timer relay offers a high level of immunity against radiated and conducted disturbances, exceeding the requirements of EN 61812-1. However, external factors like transformers, motors, contactors, switches, and power cables can cause disturbances. To mitigate this, wiring cables should be kept as short as possible. If necessary, protect the timer with relevant RC networks, varistors, or surge voltage protectors.
Dimensions
83.11 / 83.21: 86.2 mm (height) x 100.3 mm (depth) x 22.5 mm (width)