Morris MPH-16331 Air to Water Heat Pump
Technical Data
General Information
Model(s): | MPH-16331 |
Air-to-water heat pump: | yes |
Water-to-water heat pump: | no |
Brine-to-water heat pump: | no |
Low-temperature heat pump: | no |
Equipped with a supplementary heater: | yes |
Heat pump combination heater: | no |
Declared climate condition: | average, warmer, colder |
Parameters are declared for low-temperature application. |
Technical Parameters - Heating
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit |
---|---|---|---|---|---|---|---|
Rated heat output (*) | Prated | 15 | kW | Seasonal space heating energy efficiency | ηs | 179 | % |
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj | Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj | ||||||
Tj = -7°C | Pdh | 13.4 | kW | Tj = -7°C | COP | 2.66 | - |
Tj = + 2°C | Pdh | 8.0 | kW | Tj = + 2°C | COP | 4.33 | - |
Tj = + 7°C | Pdh | 5.4 | kW | Tj = + 7°C | COP | 6.48 | - |
Tj = + 12°C | Pdh | 4.6 | kW | Tj = + 12°C | COP | 8.96 | - |
Tj = bivalent temperature | Pdh | 13.4 | kW | Tj = bivalent temperature | COP | 2.66 | - |
Tj = operation limit temperature | Pdh | 13.4 | kW | Tj = operation limit temperature | COPd | 2.46 | - |
For air-to-water heat pumps: Tj = – 15°C (if TOL < -20°C) | Pdh | N/A | kW | For air-to-water heat pumps: Tj = – 15°C (if TOL < -20°C) | COPd | N/A | - |
Bivalent temperature | Tbiv | -7 | °C | For air-to-water heat pumps: Operation limit temperature | TOL | -10 | °C |
Cycling interval capacity for heating | Pcych | N/A | kW | Cycling interval efficiency | COPcyc | N/A | - |
Degradation co-efficient (**) | Cdh | 0.9 | - | Heating water operating limit temperature | WTOL | 65 | °C |
Power consumption in modes other than active mode | Supplementary heater | Psup | 1.6 | kW | |||
Off mode | POFF | 0.014 | kW | Rated heat output (**) | |||
Thermostat-off mode | PTO | 0.024 | kW | Type of energy input | Electric | ||
Standby mode | PSB | 0.014 | kW | ||||
Crankcase heater mode | PCK | 0.000 | kW |
Other Items
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit |
---|---|---|---|---|---|---|---|
Capacity control | variable | For air-to-water heat pumps: Rated air flow rate, outdoors | 6000 | m³/h | |||
Sound power level, indoors/ outdoors | LWA | -/68 | dB | For water- or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger | - | N/A | m³/h |
Annual energy consumption | QHE | 6863 | kWh | For heat pump combination heater: | |||
For heat pump combination heater: | Declared load profile | ||||||
Declared load profile | N/A | Water heating energy efficiency | ηwh | N/A | % | ||
Daily electricity consumption | Qelec | N/A | kWh | Daily fuel consumption | Qfuel | N/A | kWh |
Annual electricity consumption | AEC | N/A | kWh | Annual fuel consumption | AFC | N/A | GJ |
Contact Details
See the back cover of the manual.
Kalliopi Karyda & Co., LP
87A, 17is Noemvriou str.
55535, Pylea, Greece
Tel. 2316 006600
www.morris.gr
Καλλιόπη Καρύδα & ΣΙΑ Ε.Ε
17ης Νοεμβρίου 87Α,
55535, Πυλαία, Ελλάδα
Τηλ. 2316 006600
www.morris.gr
Notes
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0.9.