IDNet® Analogue Addressable Devices
Features
- Supported by SIMPLEX 4100U/ES Series CIE
- CIE displays device location and status
- Individually addressable communications over a single cable pair
- Zone adaptor modules provide addressable interface to conventional circuits
- IDNet digital protocol communications
- Convenient DIP switch address selection
- Supports up to 250 addressable devices per loop
- Range of enclosures to suit, with covers incorporating an LED viewing window
General
IDNet communication is provided by the SIMPLEX 4100U/ES Control and Indicating Equipment (CIE) and is the next generation of addressable device communications, improving upon the original MAPNET II communications protocol. The IDNet protocol and hardware enhancements support up to 250 addressable devices on a single cable pair and can support additional device types and different operations.
IDNet communicating devices individually annunciate identity and accurate status to the 4100U/ES CIE. Applications include monitoring of sprinkler pressure switches, flow switches and valve monitor devices, interfacing of conventional detectors and addressable monitoring and control (voltage free) for AS 1668 applications. The majority of IDNet devices are loop powered requiring a single cable pair for operation by the CIE.
4090-9002 Relay IAM (Individual Addressable Module)
A circuit board module with multiple relays and connectors, labeled 'Simplex'.
The 4090-9002 Relay IAM allows the CIE to control a remotely located Form "C" Relay contact using IDNet addressable communications for both data and module power. Typical applications are for switching local power for control functions such as magnetic door holders, or control of HVAC components, pressurisation fans, dampers, etc. Relay contact status is also communicated to the CIE. The address is set by DIP switch under the resealable label.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Relay Contact Ratings SPDT | |
0.5A @120VAC² | |
2A@24Vdc² | |
1A@24Vdc³ | |
Current Limited Operation | 1k8/4k7 0.5W |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 93% (n/c) |
Part Number | 4090-9002 |
¹ IDNet communications ² Transient suppressed load ³ Inductive load | |
Note: Loop powered 2 wire device |
4090-9007 Signal Relay IAM (Individual Addressable Module)
A circuit board module with a large relay and various components, labeled 'Simplex'.
The 4090-9007 Signal Relay IAM provides a supervised, addressable interface to conventional warning devices such as sounders or strobes. It requires a supervised power supply or compatible signal input for powering the externally connected loads.
- Provides a single switched branch with supervision
- Contact is fused at 0.5A for 30V DC or 70V AC using standard 20 x 5mm cartridge fuse
- DC loads must be diode isolated
- Supervision cannot be disabled
- The supply side and the internal fuse are not supervised by the Signal IAM
- Signal IAM is not suitable for switching 100V audio signals
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Operating Current | 170mA |
Relay Contact Ratings SPDT | |
0.5A @120VAC² | |
2A@24Vdc² | |
1A@24Vdc³ | |
Current Limited Operation | 1k8/4k7 0.5W |
EOLR | 10k Ohm |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 93% (n/c) |
Part Number | 4090-9007 |
¹ IDNet communications ² Transient suppressed load ³ Inductive load | |
Note: Loop powered 2 wire device |
4190-9050 Analogue Monitor Zone (AMZ) Adaptor Module
A compact circuit board module with a green connector block and various electronic components.
SIMPLEX AMZs provide an accurate, multi-featured 4-20mA interface for connecting analog sensors to Simplex addressable fire detection panels. The panel monitors the sensor and annunciates whenever a selected threshold level or fault condition is observed. Typical applications include: gas, air, liquid temperature, humidity, and air velocity sensing. The maximum distance from AMZ to a sensor is 1km. Each AMZ requires an address and up to 100 AMZs can be connected per panel.
Technical Specification | |
---|---|
Operating Voltage¹ | 18 to 32Vdc |
Sensor Output | Switched input voltage |
Sensor Current | 400mA (max.) |
Basic AMZ Current | 30mA |
Sensor Loop Current | 20mA (max.) |
Fault Current | 5mA |
2098-9808 LED Annun. | 3mA |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +38°C |
Relative Humidity | 10% to 90% (n/c) |
Part Number | 4190-9050 |
¹ MAPNET II communications | |
Note: Loop powered 2 wire device |
4090-9051 Supervised IAM (Individual Addressable Module)
A small, encapsulated module with flying leads and a circuit board visible through a translucent casing.
The 4090-9051 Supervised IAM has both power and communications supplied by a two-wire IDNet circuit. It provides a single address for an initiating device (such as detector alarm contacts) or multiple devices at the same location by monitoring N/O dry contacts and the wiring to an end of line resistor. It is housed in an encapsulated housing with flying leads. This allows dual functions such as tamper switch and water-flow switch monitoring to be done by a single addressable point.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Operating Current | 170mA |
Supervision Resistor | 6k8 Ohm 0.5W |
Current Limited Oper.² | 1k8/4k7 0.5W |
Dimensions (HWD) | 40x40x14mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 93% (n/c) |
Part Number | 4090-9051 |
¹ IDNet communications ² Available only with IDNet | |
Note: Loop powered 2 wire device |
4090-9101 ZAM (Zone Adaptor Module)
A circuit board module with two large relays and connectors, labeled 'Simplex'.
The 4090-9101 Monitor ZAM allows a 2-wire circuit of conventional smoke or heat detectors to be interfaced on to the IDNet loop. Up to 20 conventional heat and smoke detectors can be monitored by a 4090-9101 Monitor ZAM. The address is set by DIP switch under the resealable label. Note the 4090-9101 requires a separate 24Vdc power supply to power the conventional circuit.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Operating Voltage | 18.9 to 32Vdc |
ZAM Current @ 24VDC² | |
Quiescent | 16mA max. |
Alarm | 72mA max. |
Supervision Resistor | 3k3 Ohm 1W |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 93% (n/c) |
Part Number | 4090-9101 |
¹ IDNet Communications ² Actual current value is determined by total device requirements | |
Note: Loop powered 2 wire device |
4090-9116 Addressable Line Isolator
A circuit board module with a large black component and several smaller electronic parts, labeled 'Simplex'.
The 4090-9116 Isolator provides IDNet communications isolation, improving installation convenience and system integrity. Circuit isolation can be selected manually, or automatically when an output short circuit is detected and the condition is reported to the CIE. If the output wiring is acceptable, the isolator will connect the rest of the circuit. If the output wiring is shorted, the isolator remains isolated.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 90% (n/c) |
Part Number | 4090-9116 |
¹ IDNet communications |
4090-9117AU Addressable Power Isolator
A circuit board module with a prominent heat sink and various electronic components.
The 4090-9117AU Power Isolator provides monitoring and short circuit protection for 24Vdc power wiring to IDNet addressable devices. In the event of a short circuit, an electronic switch isolates both power circuit conductors and reports its status to the CIE. This function can also be selected from the CIE.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Current Rating | 2A@32Vdc max. |
Input Current | 10mA@24Vdc |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 90% (n/c) |
Part Number | 4090-9117AU |
¹ IDNet communications |
4090-9118 Relay IAM with T-Sense Input
A circuit board module with multiple relays and connectors, featuring a warning label 'DISCONNECT POWER BEFORE SERVICING'.
The 4090-9118 Relay IAM with T-Sense allows a 4100U/ES IDNet communication channel to monitor two input contact closures with one point and control an output relay with the other point, yet occupy a single loop address. Power is supplied from the IDNet communications channel, eliminating the need for separate power wiring. The input circuit and relay operation are controlled independently and may be disabled separately. Applications include water flow and tamper switch monitoring and control and damper position monitoring and control.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Relay Contact Ratings SPDT | |
0.5A @120VAC² | |
0.25A@120VAC³ | |
2A@30Vdc² | |
1A@30Vdc³ | |
Input | N/O, dry contacts |
Current Limited Operation | 1k8/4k7 0.5W |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 90% (n/c) |
Part Number | 4090-9118 |
¹ IDNet communications ² Resistive Load ³ Inductive Load | |
Note: Loop powered 2 wire device |
4090-9119 Relay IAM with Unsupervised Input
A circuit board module with multiple relays and connectors, featuring a warning label 'DISCONNECT POWER'.
The 4090-9119 allows a 4100U/ES IDNet communication channel to monitor an unsupervised input contact with one point and control an output relay with the other point, yet occupy a single address. The input circuit and relay operation are controlled independently and may be disabled separately. Module power is supplied from the IDNet communications channel eliminating the need for separate power wiring. The address is set by DIP switch under the resealable label.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Relay Contact Ratings SPDT | |
non power limited | 0.5A @120VAC² |
0.25A@120VAC³ | |
power limited | 2A@30Vdc² |
1A@30Vdc³ | |
Input | N/O, dry contacts |
Dimensions (HWD) | 105x105x35mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 95% (n/c) |
Part Number | 4090-9119 |
¹ IDNet communications ² Resistive Load ³ Inductive Load | |
Note: Loop powered 2 wire device |
4090-9120 Six Point I/O Module with T-Sense Inputs & Relay Outputs Module
A circuit board module with several green connector blocks and various electronic components.
The 4090-9120 allows 4100U/ES IDNet communication channel to monitor four T-sense input circuits and control two output relays from a single module requiring a single address. Power is supplied by a separate (listed) 24Vdc power supply. The input circuits and output relay operation are controlled independently and may be disabled separately. Point association is determined at the 4100U/ES host panel. Each of the four input circuits are monitored via an end-of-line resistor and can differentiate between a short circuit contact closure and a current limited contact closure. Two input supervision resistors are required per T-sense input.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Operating Voltage | 18 to 32Vdc |
Operating Current | 30mA@24Vdc |
Contact Ratings SPDT | |
Non-power limited | 0.5A @120VAC² |
0.25A@120VAC³ | |
Power limited | 2A@30Vdc² |
1A@30Vdc³ | |
Supervision Resistor | 6k8 Ohm 0.5W |
Current Ltd Operation | 1k8/4k7 0.5W |
Input | N/O, dry contacts |
LED Output | 24Vdc (ext. PSU) |
Dimensions (HWD) | 105x105x35 mm |
Ambient Temperature | 0 to +49°C |
Relative Humidity | 10% to 90% (n/c) |
Part Number | 4090-9120 |
¹ IDNet communications with data ² Resistive Load ³ Inductive Load | |
Note: 4 wire device; requires separate 24Vdc and IDNet communication loop |
4099-9701 Manual Call Point
A red manual call point with a 'Simplex' logo and a breakable element, designed for fire alarm activation.
The 4099-9701 addressable Manual Call Point (MCP) provides a means to manually initiate a fire alarm condition to the 4100U/ES CIE via the IDNet channel. The IDNet channel provides the communication link and power between the MCP and CIE. Activation of the MCP requires the frangible element to be broken, causing microswitch contacts to close. The MCP is reset by fitting of a replacement frangible element.
Technical Specification | |
---|---|
Comms Power¹ | 24 to 40Vdc w/data |
Dimensions (HWD) | 86x87x35mm |
Ambient Temperature | -9°C to +70°C |
Relative Humidity | 10% to 95% (n/c) |
ActivFire listed | afp-1691 |
Part Numbers | |
MCP & Backbox | 4099-9701 |
Spare Backbox | SR3T-P |
Spare Glass (Pk 10) | SU0609 |
¹ IDNet communications |
Tyco Fire Protection Products
Level 3, 95 Coventry Street, Southbank VIC 3006
Tel: 1300 725 688
Fax: +61 3 9313 9709
Form No. IDNetSBRO1411
SIMPLEX is a trademark of ADT Services GmbH or its affiliates. MAPNET II, SAFELINC, TRUEALARM, TRUESTART are trademarks of ADT Services AG or its affiliates. TYCO is a trademark of Tyco International Services GmbH. Windows is a registered trademark of Microsoft Corporation in the United States and other countries. © 2014 Tyco Australia Pty Limited. A.B.N. 80008399004. Unauthorised use of trademarks is strictly prohibited. Printed November 2014