The 4090-9007 IDNet Addressable Signal Individual Adapter Module
(Signal IAM) is an IDNet-compatible peripheral that combines both Class A (Style Z) and Class B (Style Y) Notification Appliance Circuit (NAC) functionality into a single device. The Signal IAM supervises and operates 24-VDC NACs and 25-VRMS or 70.7-VRMS speakers. The Signal IAM does not support Fire Fighter Phones.
Powered from an IDNet-compatible (addressable loop) channel, the Signal IAM provides a supervised, addressable interface between conventional notification appliances and the host FACP. The Signal IAM requires a supervised power supply or compatible signal input for driving the externally connected NAC appliances.
General | |
---|---|
Operating Temperature | 0 to 49 ℃ (32 to 120 ℉) |
Operating Humidity | Up to 93% relative humidity (non-condensing) |
Mounting | |
Dimensions | Width = 4.13 in (10.5 cm)Height = 4 in (10.2 cm)Depth = 1.38 in (3.5 cm) |
Back Box | 4 in (10.2 cm) square box |
Addressable Loop Power | |
Nominal Terminal Input | 35 VDC |
Unit Load | |
Device consumes 2 device loads on the addressable loop. |
Note: The IDNet channel (4007ES
, 4010
, 4010ES
, 4100U
, and 4100ES
) supports address codes 1 through 250. The 4008
supports address codes 1 through 200. The MAPNET II
channel (4100
, 4120
, or 4020 FACP
) supports address codes 1 through 127.
Each Signal IAM has a unique address. The address of the IAM is set via an eight position DIP switch. DIP switch position 1 is the least significant bit (LSB) and position 8 is the most significant bit (MSB). Set the IAM's address using the reference table. Use a small screwdriver or pen to set the switches. The device address for the Supervised IAM should be written on the resealable label; this information provides an aid in troubleshooting the system.
Note: DIP switch in "1" position is "ON" while DIP switch in "0" position is "OFF".
Figure: Representation of an 8-position DIP switch with LSB and MSB indicated, showing ON (1) and OFF (0) states. An example setting for address 7 is depicted.
DIP Switches 5 thru 8 (MSB) | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
0000 | 1000 | 0100 | 1100 | 0010 | 1010 | 0110 | 1110 | 0001 | 1001 | 0101 | 1101 | 0011 | 1011 | 0111 | 1111 | ||
DIP Switches 1 thru 4 (LSB) | 0000 | 0 | 16 | 32 | 48 | 64 | 80 | 96 | 112 | 128 | 144 | 160 | 176 | 192 | 208 | 224 | 240 |
1000 | 1 | 17 | 33 | 49 | 65 | 81 | 97 | 113 | 129 | 145 | 161 | 177 | 193 | 209 | 225 | 241 | |
0100 | 2 | 18 | 34 | 50 | 66 | 82 | 98 | 114 | 130 | 146 | 162 | 178 | 194 | 210 | 226 | 242 | |
1100 | 3 | 19 | 35 | 51 | 67 | 83 | 99 | 115 | 131 | 147 | 163 | 179 | 195 | 211 | 227 | 243 | |
0010 | 4 | 20 | 36 | 52 | 68 | 84 | 100 | 116 | 132 | 148 | 164 | 180 | 196 | 212 | 228 | 244 | |
1010 | 5 | 21 | 37 | 53 | 69 | 85 | 101 | 117 | 133 | 149 | 165 | 181 | 197 | 213 | 229 | 245 | |
0110 | 6 | 22 | 38 | 54 | 70 | 86 | 102 | 118 | 134 | 150 | 166 | 182 | 198 | 214 | 230 | 246 | |
1110 | 7 | 23 | 39 | 55 | 71 | 87 | 103 | 119 | 135 | 151 | 167 | 183 | 199 | 215 | 231 | 247 | |
0001 | 8 | 24 | 40 | 56 | 72 | 88 | 104 | 120 | 136 | 152 | 168 | 184 | 200 | 216 | 232 | 248 | |
1001 | 9 | 25 | 41 | 57 | 73 | 89 | 105 | 121 | 137 | 153 | 169 | 185 | 201 | 217 | 233 | 249 | |
0101 | 10 | 26 | 42 | 58 | 74 | 90 | 106 | 122 | 138 | 154 | 170 | 186 | 202 | 218 | 234 | 250 | |
1101 | 11 | 27 | 43 | 59 | 75 | 91 | 107 | 123 | 139 | 155 | 171 | 187 | 203 | 219 | 235 | 251 | |
0011 | 12 | 28 | 44 | 60 | 76 | 92 | 108 | 124 | 140 | 156 | 172 | 188 | 204 | 220 | 236 | 252 | |
1011 | 13 | 29 | 45 | 61 | 77 | 93 | 109 | 125 | 141 | 157 | 173 | 189 | 205 | 221 | 237 | 253 | |
0111 | 14 | 30 | 46 | 62 | 78 | 94 | 110 | 126 | 142 | 158 | 174 | 190 | 206 | 222 | 238 | 254 | |
1111 | 15 | 31 | 47 | 63 | 79 | 95 | 111 | 127 | 143 | 159 | 175 | 191 | 207 | 223 | 239 | 255 |
Note: MAPNET II
supports address codes 1 through 127 only.
Note: Ensure that cable shields will not ground when closing the box. Use shrink tubing or high grade electrical tape to cover bare shield.
The Signal IAM provides two terminal blocks, which are described in Tables 1 and 2, below. All terminal blocks accept 12-18 AWG wire.
Position | Label | Description |
---|---|---|
TB1-1 | +ADDR LOOP | +IDNet input (pass-through, if required) |
TB1-2 | -ADDR LOOP | -IDNet input (pass-through, if required) |
TB1-3 | ADDR LOOP SHIELD | IDNet shield |
TB1-4 | -SIGNAL IN | -Signal IN for audio or 0 V input for Strobes, Horns, etc. |
TB1-5 | +SIGNAL IN | +Signal IN for audio or +24 V input for Strobes, Horns, etc. |
TB1-6 | SIGNAL IN SHIELD | Input signal shield for audio applications |
Position | Label | Description |
---|---|---|
TB2-1 | SIGNAL SHIELD | SIGNAL OUT/RETURN shield for audio applications |
TB2-2 | +SIGNAL OUT | + SIGNAL OUT -- Class B operation |
TB2-3 | -SIGNAL OUT | - SIGNAL OUT -- Class B operation |
TB2-4 | +SIGNAL RETURN | + SIGNAL RETURN -- Class A operation |
TB2-5 | -SIGNAL RETURN | - SIGNAL RETURN -- Class A operation |
Use the following two pages to wire the Signal IAM.
The document provides detailed wiring diagrams for the IDNet Signal IAM
, illustrating typical wiring methods for addressable loops and Notification Appliance Circuits (NACs). These diagrams cover both Class A (Style Z) and Class B (Style Y) configurations for 25 VRMS and 70.7 VRMS speakers, as well as audible/visual appliances.
70.7 VRMS Power | Maximum Distance in Feet (w/ max loss of 3 DB at last speaker) | ||||
---|---|---|---|---|---|
18 AWG | 16 AWG | 14 AWG | 12 AWG | ||
Applied | Actual | ||||
35 W | 6.25 W | 1000 | 1000 | 1000 | 1000 |
Applied | Actual | ||||
30 W | 15 W | 2000 | 2000 | 2000 | 2000 |
25 VRMS Power | Maximum Distance in Feet (w/ max loss of 3 DB at last speaker) | ||||
---|---|---|---|---|---|
18 AWG | 16 AWG | 14 AWG | 12 AWG | ||
Applied | Actual | ||||
10 W | 5 W | 800 | 1000 | 1000 | 1000 |
Applied | Actual | ||||
10 W | 5 W | 1600 | 2000 | 2000 | 2000 |
Note: Wiring distances are restricted due to DC supervision limitations.
4008 Front Panel Installing, Operating, and Programming Instructions (579-716)
for more field wiring information as needed.NAC wiring distances, Class A | Maximum Distance in Feet | Line Resistance (Ohms) | ||||
---|---|---|---|---|---|---|
18 AWG | 16 AWG | 14 AWG | 12 AWG | |||
Alarm Current (Amps) | ||||||
0.25 | 400 | 650 | 1000 | 1000 | 12 | |
0.50 | 200 | 325 | 500 | 800 | 6 |
NAC wiring distances, Class B | Maximum Distance in Feet | Line Resistance (Ohms) | ||||
---|---|---|---|---|---|---|
18 AWG | 16 AWG | 14 AWG | 12 AWG | |||
Alarm Current (Amps) | ||||||
0.25 | 800 | 1300 | 2000 | 2000 | 12 | |
0.50 | 400 | 650 | 1000 | 1600 | 6 |
2081-9044
or 2081-9028
. A protector must be installed at each building exit/entrance. Each 2081-9044
adds 6 Ohms resistance, and significantly reduces wiring distance. Each 2081-9028
adds 0.2 Ohms of resistance. Maximum current allowed through a 2081-9044
is 200 mA.4905-9938 Sync Control Module (SCM)
, Class A operation on the SCM is not supported.4905-9938 Sync Control Module (SCM)
, the Signal IAM must adhere to one of the following restrictions:4905-9938 Sync Control Module
, Signal IAM and interconnecting wire must be in the same single enclosure.TrueAlert Addressable Notification Appliances
are not supported.4008 Front Panel Installing, Operating, and Programming Instructions (579-716)
for more field wiring information as needed.Note: The Signal IAM is not compatible with or intended to be used with standard NAC circuits (SPS, XPS, etc.) that are configured for Smart Sync operation.
For partial evacuation (selective signaling) systems, the NAC Riser must be installed in accordance with survivability from attack by fire requirements in NFPA 2002 ED. Section 6.9.4, using one or more of the following:
To mount the Signal IAM:
Figure: Illustration of Signal IAM mounting options, including flush-mount cover (optional 4090-9801
), surface-mount cover (optional 4090-9802
), optional extension ring (1 1/4 in / 32 mm RACO 201
or equal), and back box (2 1/8 in / 54 mm deep, 4 in / 102 mm square RACO 230
or equal). Shows assembly with 4 #6 screws.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED. Upon unpacking your product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD: Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier.
STATIC HAZARD: Static electricity can damage components. Handle as follows:
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
![]() | Simplex 4090-9007 IDNet Signal IAM: Addressable Module for Fire Alarm Systems Detailed technical specifications and features for the Simplex 4090-9007 IDNet Signal Individual Addressable Module (IAM), designed for enhanced selective signaling and audio control in Simplex 4100ES, 4010ES, 4100U, and 4008 Series fire alarm control panels. Includes wiring, operation, and mounting information. |
![]() | Módulo Direccionable Individual Simplex 4090-9007 IAM de Señal para Paneles de Alarma de Incendios Descubra el Módulo Direccionable Individual (IAM) de Señal Simplex 4090-9007, un periférico IDNet para paneles de control de alarma de incendios 4007ES, 4008, 4010ES, 4100ES y 4100U. Proporciona señalización selectiva, supervisión de NAC, control de audio y cumple con UL, ULC, CSFM y FM. |
![]() | Módulo Endereçável Individual Simplex 4090-9007 IDNet para Sinalização de Alarme de Incêndio Este documento técnico detalha o Módulo Endereçável Individual (IAM) Simplex 4090-9007 IDNet, projetado para fornecer sinalização adicional em painéis de controle de alarme de incêndio Simplex séries 4007ES, 4008, 4010ES, 4100ES e 4100U. Inclui características, recursos de supervisão, detalhes de operação, especificações elétricas e mecânicas, requisitos de fiação e informações de montagem para otimização de sistemas de alarme de incêndio. |
![]() | Simplex Addressable Manual Stations: IDNet/MAPNET II Peripherals Explore Simplex addressable manual fire alarm stations, detailing their features, single/double action types, NO GRIP options, and compatibility with IDNet/MAPNET II systems. Includes mounting and specification information. |
![]() | Simplex IDNet Analogue Addressable Devices Product Overview Explore Simplex IDNet Analogue Addressable Devices, a comprehensive range of fire alarm system components designed for enhanced communication, monitoring, and control. Learn about features, technical specifications, and applications for modules like Relay IAMs, Zone Adaptors, Line Isolators, and Manual Call Points, all integrated with SIMPLEX 4100U/ES Control and Indicating Equipment for robust building safety solutions. |
![]() | Simplex 4090-9116 Aislador de Comunicaciones IDNet Direccionable - Especificaciones Técnicas Documento técnico detallado sobre el Aislador de Comunicaciones IDNet Direccionable Simplex 4090-9116, cubriendo sus características, operación, ejemplos de instalación, especificaciones eléctricas y mecánicas para sistemas de alarma contra incendios. |
![]() | Simplex 4090-9101, 4090-9106 Monitor ZAM Installation Instructions Installation instructions for Simplex 4090-9101 and 4090-9106 Monitor Zone Adapter Modules (ZAMs). Covers mechanical installation, address setting via DIP switches, and electrical connections for IDNet and MAPNET II systems. |
![]() | Simplex 4010ES Fire Control Units: Addressable Fire Detection System Datasheet Comprehensive datasheet for Simplex 4010ES Fire Control Units, detailing addressable fire detection capabilities, IDNAC technology, system features, operator interfaces, and model specifications for advanced fire alarm solutions. |