The TP 7000 is a programmable room thermostat that combines clock and thermostat functions in a sleek, user-friendly design. It allows users to set temperatures according to their lifestyle, offering flexibility for different periods of the day and week.
Key Features
- Programming Flexibility: Supports true 7-day programming or 5/2-day programming (weekdays and weekends), allowing different temperature settings for each day or group of days.
- Temperature Periods: Up to six programmable temperature periods per day, with an additional option for a holiday/off mode.
- Wired and Wireless Options: Available in wired versions or as a simple wireless RF (Radio Frequency) version.
- Installer-Set Features:
- Optimal Start Control: This intelligent feature uses the room's temperature to calculate the time required for the heating system to reach the desired temperature. This ensures the room is comfortably warm by the programmed time, optimizing energy usage.
- Time Proportional Control: This function determines the boiler's cycle and on/off times, contributing to user comfort and increasing boiler efficiency, particularly beneficial for condensing boilers.
- RF Model Functionality: The RF model includes a digital FM radio transmitter that sends a unique identification code. This code is recognized by one-, two-, or three-channel RX receivers, which can be located up to 30 meters away. These receivers are used to control boilers, pumps, or control valves.
- Power Options: Available in battery-powered or mains-powered versions, with either built-in or remote sensors.
- Additional Modes: Includes "Holiday" mode and thermostatic mode with frost protection.
Installer Settings (Microswitches)
Various settings can be configured via microswitches, depending on the model and desired functionality:
Setting | Description |
---|---|
Sw1 | 5/2 day programming |
7-day programming | |
Sw2 | Optimal Start Control enabled |
Optimal Start Control disabled | |
Sw3 | Time Proportional Control |
2-point Control | |
Sw4 (for TP7000, A, B, AB, M, MA, RF & A-RF models with 3/6 cycles per hour) | Time Proportional, 6 cycles/hour |
Time Proportional, 3 cycles/hour | |
Sw4 (for TP7000C, CA, CM, CMA, C-RF & CA-RF models with 6/12 cycles per hour) | Time Proportional, 12 cycles/hour |
Time Proportional, 6 cycles/hour |
Note: Sw4 is only active if Sw3 is set to Time Proportional Control.
Installer Settings (Optimal Start Control)
When the microswitch SW2 is set to enable Optimal Start Control, specific settings must be configured in the user programming mode. The table below shows calculated start times based on the difference between the room temperature and the programmed temperature for the first daily event. Possible settings for the optimization period are 0:00 (OSC disabled), 0:30, 1:00, 1:30, or 2:00.
Desired Temp. for Event 1 | Temperature Difference Below Target for Optimal Start | |||
---|---|---|---|---|
-1°C | -2°C | -3°C | -4°C | |
Event 1 Start Time | 120 min. | 90 min. | 60 min. | 30 min. |
Possible Optimization Periods | (Example: With a -2°C difference and a 30-minute curve selected, the boiler will turn on 15 minutes before Event 1.) |
Technical Data - Thermostats
Feature | TP7000-RF | TP7000 | TP7000M | TP7000A / TP7000MA | TP7000-RF / TP7000A-RF |
---|---|---|---|---|---|
Part Numbers (Built-in sensor) | 087N741000 | 087N741400 | 087N740000 | 087N740400 | 087N740800 |
Part Numbers (Remote sensor, Series A) | 087N741100 | 087N741500 | 087N740100 | 087N740500 | 087N740900 |
Control Mode (2-point or Time Proportional, 3/6 cycles/hr) | ✓ | ✓ | ✓ | ||
Control Mode (2-point or Time Proportional, 6/12 cycles/hr - C models) | ✓ | ✓ | |||
RF Wireless Thermostat | ✓ | ✓ | |||
Wired Thermostat | ✓ | ✓ | ✓ | ||
Clock Type | 24-hour (user adjustable to AM/PM) | ||||
Programming Options | Choice of 7-day or 5/2-day operation | ||||
Number of Events per Day | Up to 6 | ||||
Temperature Range | Off, 5-30°C (user adjustable to °Fahrenheit) | ||||
Switching Differential (2-point control) | < 1.0°C | ||||
Factory Default Program | Yes | ||||
Holiday Program | Yes, up to 99 days | ||||
Optimal Start Control Setting | Yes, Off, 30, 60, 90 or 120 min. early start at -4K temp. difference | ||||
Thermostatic Mode & Frost Protection | Yes, set to 1.0°C, adjustable 5-30°C | ||||
Power Supply | 2 x AA Alkaline Batteries (included) | 230 V, 50 Hz | 230 V, 50 Hz | 2 x AA Alkaline Batteries (included) | 2 x AA Alkaline Batteries (included) |
Memory Power Supply | Capacitor (1 min during battery change) | Rechargeable cell (see note 1) | Rechargeable cell (see note 1) | Capacitor (1 min during battery change) | Capacitor (1 min during battery change) |
Switch Function | Single-pole changeover | - | - | Single-pole changeover | - |
Relay Load (Voltage & Current) | 3(1) A, 230 V | - | - | 3(1) A, 230 V | - |
RF Transmitter Frequency | 433.92 MHz | - | - | - | 433.92 MHz |
RF Transmitter Range | Max. 30 m | - | - | - | Max. 30 m |
Dimensions (W x H x D) mm | 138 x 88 x 28 | 138 x 88 x 28 | 138 x 88 x 28 | 138 x 88 x 28 | 138 x 88 x 28 |
Environmental Class | Class 2 | Class 2 | Class 2 | Class 2 | Class 2 |
Impulse Voltage | 2.5kV | - | - | - | - |
Pressure Temperature Test | 75°C | - | - | - | - |
Note 1: The device must be connected to the mains for at least 6 days for the cell to be fully charged.
Technical Data - Receivers (RF Models Only)
Feature | RX1 | RX2 | RX3 |
---|---|---|---|
Part Numbers | 087N747600 | 087N747700 | 087N747800 |
Receiver Module Type | 1-channel receiver module, operates with one thermostat | 2-channel receiver module, operates with two thermostats | 3-channel receiver module, operates with three thermostats |
Automatic Code Recognition | ✓ | ✓ | ✓ |
Receiver Frequency | 433.92 MHz | ||
Supply Voltage | 220/240 Vac, 50 Hz | ||
Allowed Relay Load | 3 (1) A | ||
Relay Type (Internal connection) | 1x single-pole changeover | 1x single-pole changeover | 1x single-pole changeover |
Additional Relay Types | 1x single-pole changeover, 2x single-pole changeover | ||
Memory Retention | Electronic memory retention on power loss | ||
Dimensions (W x H x D) mm | 138 x 88 x 32 | 138 x 88 x 32 | 138 x 88 x 32 |
Wiring Diagrams
The following diagrams illustrate typical wiring configurations for the TP 7000 thermostats and their associated RX receivers.
TP7000/TP7000A with RX1 & RX2 Receivers
This setup involves a TP7000 or TP7000A thermostat connected to an RX1 (single-channel) or RX2 (dual-channel) receiver. Connections are shown for the main power (L, N), thermostat sensor (remote sensor terminal), remote start terminal, load connection, and the electronic unit. The diagrams indicate specific terminals for 'COM', 'ON', 'OFF', 'REMOTE START', 'REMOTE SENSOR', and 'LOAD', with specific terminals used for models with remote sensor ('A' models) and remote start ('B' models).
TP7000M/TP7000MA with RX1 & RX2 Receivers
Similar to the TP7000/TP7000A, this configuration uses TP7000M or TP7000MA thermostats with RX1 or RX2 receivers. The wiring principles for power, sensor, start, and load connections are consistent, with terminals labeled for 'COM', 'ON', 'OFF', 'REMOTE START', 'REMOTE SENSOR', and 'LOAD'.
TP7000-RF/TP7000A-RF with RX3 Receiver
This diagram shows the wireless RF models (TP7000-RF, TP7000A-RF) connected to an RX3 (three-channel) receiver. The wiring includes connections for the main power supply (230Vac L, N) to the receiver's electronics. The receiver has terminals for 'COM', 'ON', 'OFF', and 'REMOTE SENSOR'. The RX3 receiver is designed to control up to three zones (Zone 1, Zone 2, Zone 3), with specific terminals for each zone's load connection.
Disclaimer
Danfoss Randall assumes no responsibility for potential errors in catalogs, brochures, and other documentation. Danfoss reserves the right to change its products without prior notice. This right also applies to products already ordered, provided that the technical characteristics of the product are not altered.
Danfoss d.o.o.
Ulica Jožeta Jame 16
1210 Ljubljana-Šentvid
Slovenia
Phone: +386 1 519 85 10, +386 1 519 24 55, +386 1 519 85 65
Fax: +386 1 519 23 61
Website: www.danfoss.si
Email: danfoss.si@danfoss.com
Part No. 602 Iss 1 07/03