Trumeter APM Gateway Quickstart Guide

Innovation by design

Device Diagram

1. POWER SUPPLY: 12-24 VDC/VAC

2. APM CONNECTIONS x4

3. GATEWAY STATUS LED: Indicates cloud connection status.

4. RJ45 ETHERNET PORT: For network connectivity.

5. EARTH MOUNTING POINT: For grounding the device.

Hardware Configuration

i. Device Wiring

  1. Connect APM(s) to the APM Gateway as per wiring diagram.
  2. Plug in Ethernet cable to the RJ45 ethernet port.
  3. Configure APMs to ensure alarms are set using the APM configurator software.

ii. Powering Device

  1. Power the APM Gateway.
  2. Status LED:
    RED - Not Connected to Cloud
    GREEN - Connected to Cloud
  3. Confirm each APM connection Link LEDs are active depending on how many meters are connected to the APM Gateway.

Cloud Access

To access the Trumeter Cloud dashboard, go to cloud.trumeter.com.

Creating a New User Account

  1. Go to cloud.trumeter.com.
  2. Click 'Sign Up' to go to the registration screen.
  3. Once registered, a confirmation email will be sent to the email address used for the account.

Adding a New Gateway

  1. Login to cloud.trumeter.com.
  2. Click the (+) to add a new device.
  3. Add serial number and model.
  4. 'REFRESH' the browser.
  5. Device will be claimed and added to the list of gateways.

Wiring for APM Link

Diagram illustrating the wiring connection for APM Link.

Connection of a Relay to Open Collector Output - Using DC PSU

Diagram showing the connection of a relay to an open collector output using a DC power supply unit.

Status LEDs

APM Link LEDs: GREEN - link active, output on.

APM DOut LEDs: GREEN – SP2 connection open/active.

GATEWAY Status LED: GREEN – Cloud connection; RED - Cloud disconnected; BLUE - software update.

Specification

Power Supply:12-24 V DC/AC
Input Max Power:1.5W
Supply Frequency:DC, 50-60Hz
Inputs: APM Link20mA current link
Outputs: Open Collector (Current Sink)30V Max Applied Voltage, 500mA Max Current
Ethernet10/100 Ethernet RJ45; DHCP only

Connections

Wire Type:Copper Solid or stranded
Min Cable Temperature Rating:65°C (149°F)
Wire Strip Length:6mm to 7mm
Wire Gauge:0.8mm² to 3.3mm²

Environment

Operating Temperature:-20°C to 60°C (-4°F to 140°F)
Storage Temperature:-20°C to 70°C (-4°F to 158°F)
Altitude:2000 metres
Relative Humidity:1 to 85%
IP Rating:IP20

Mechanical Dimensions

Diagram showing the mechanical dimensions of the APM Gateway, including mounting points and port locations.

Safety Warnings

WARNING: INSTALLATION AND MAINTENANCE MUST BE CARRIED OUT BY SUITABLY QUALIFIED AND COMPETENT PERSONNEL ONLY. Install this product in accordance with local regulations, codes and instructions. An external fuse should be fitted in-line with the PSU. Recommended fuse: 500mA/250V Type T with a breaking capacity of 35A or greater.

Signal cables connected to this device must not exceed 30 metres long. If signal cables are routed outside the building, install extra surge-protection devices.

12V-24V power supply, current input, USB and all outputs: Observe maximum allowable voltages. All circuits connected to these connectors must be limited-energy and insulated by double/reinforced insulation from mains voltages.

MAINTENANCE: Before cleaning, inspection or maintenance, isolate all power sources to the unit. There are no user-serviceable parts inside this unit. Never open the case. Inspect all external wiring connections at regular intervals. Replace any damaged wiring and tighten any loose connections. To clean the unit, use a dry cloth to wipe the casing. Take great care connecting the supply. If you connect power to the wrong terminals, it may destroy the unit.

Further Information

Use of APM Link requires APM Software version 28 or above and APM Link must be enabled on the APM using the APM Configurator application.

DHCP server required for correct operation.

Product page: https://www.trumeter.com/product/apm-gateway/

Trumeter Cloud pricing plans: https://www.trumeter.com/solutions/cloud/plans/

Help: https://www.trumeter.com/help/tech-tips/

APM Software Download: https://www.trumeter.com/help/apm-software-download/

Trumeter (Europe)
Trumeter, Pilot Mill, Alfred Street, Bury, Lancashire BL9 9JR, United Kingdom
Tel: +44 161 674 0960
Email: sales.uk@trumeter.com

Trumeter (The Americas)
Trumeter, 6601 Lyons Rd, SUITE H-7, Coconut Creek, Florida, FL 33073, USA
Tel: +1 954 725 6699
Email: sales.usa@trumeter.com

Asia Pacific Distributor
Innovative Design Technologies Sdn. Bhd, Lot 5881, Lorong Iks Bukit Minyak 1 Taman Perindustrian Iks, 14000 Bukit Tengah Penang, Malaysia
Web: www.idtworld.com
Tel: + 604 5015700
Email: info@idtworld.com

www.trumeter.com

Models: APM-Gateway-QSG, APM-Gateway-QSG 3 Phase Digital Energy Meter, APM-Gateway-QSG, 3 Phase Digital Energy Meter, Digital Energy Meter, Energy Meter, Meter

File Info : application/pdf, 2 Pages, 499.03KB

PDF preview unavailable. Download the PDF instead.

APM-Gateway-QSG

References

Adobe PDF Library 17.0 Adobe InDesign 20.0 (Windows)

Related Documents

Preview Trumeter FlexAlert Quickstart Guide: Setup and Mounting Instructions
Concise guide to setting up, turning on, and mounting the Trumeter FlexAlert device using hook and loop or cable ties. Includes contact information and safety warnings.
Preview Trumeter Vista Touch Modbus Communications Guide
Comprehensive guide to Modbus RTU and TCP/IP communications for the Trumeter Vista Touch series, detailing data types, protocols, function codes, configuration, and address maps.
Preview Trumeter 7110DIN 8 Digit Totalising Counter: Specifications and Guide
Comprehensive technical specifications, connection diagrams, and mounting instructions for the Trumeter 7110DIN 8-digit totalising counter, suitable for various industrial and counting applications.
Preview Trumeter Model 3602/3603/3604 Reset Instructions
Instructions for resetting Trumeter Model 3602, 3603, and 3604 counters, emphasizing correct procedures and warnings against improper methods.
Preview Trumeter ADM Series Graphical Panel Meters - Versatile Programmable Features
Explore the Trumeter ADM Series Graphical Panel Meters, offering versatile programmable features, user-configurable alarms, and flexible metering solutions for voltage, current, and frequency measurement. Learn about specifications, dimensions, and wiring.