NOTIFIER FireVoice-25/50ZS Zoned System Voice Evacuation Control Panel
General
The NOTIFIER FireVoice-25/50 Zoned System (NFV-25/50ZS) is a state-of-the-art Emergency Voice Evacuation Panel (EVAC) capable of splitting 25 or 50 watts of audio power into up to eight speaker circuits (zones). It records five field-programmable messages (up to 60 seconds total duration) using an integral commercial-grade emergency communications microphone or an external audio source. Key enhancements include full supervision in active alarm and standby conditions, supervision of amplifier outputs, field wiring, message generator, tone generators, and the microphone. The integral power supply can charge up to 18 AH batteries housed within the cabinet.
The NFV-25/50ZS is suitable for use as an adjunct (slave or stand-alone) to most UL-Listed Fire Alarm Control Panels (FACPs). An optional 25 watt, 25 Vrms audio amplifier expands output to 50 watts or serves as a secondary amplifier. A 70.7 Vrms converter is available for retrofitting amplifiers.
The Zone Splitter Module (ACC-ZSM) divides audio amplifier output into up to eight speaker circuits. The Zone Page Module with Keypad (ACC-ZPMK) provides manual control of speaker circuits, status indication, and automatic control via the FACP's ACS serial link.
Field-programming options include five custom messages (fire, tornado, evacuation, hazmat, non-fire, multi-language), making the NFV-25/50ZS a versatile voice evacuation system. Suitable applications include schools, auditoriums, dormitories, theaters, restaurants, places of worship, lodging, office buildings, and factories.
Features
- Listed to UL Standard 864, 9th edition.
- 25 watts of audio power can be divided into eight Style Y (Class B) or four Style Z (Class A) speaker circuits (zones) using the ACC-ZSM.
- Full manual control of all audio zones via the ACC-ZPMK.
- Activation by FACP using ACS serial link and/or five Command (CMD) inputs.
- ACS serial link activation compatible with NOTIFIER FACPS such as NFW2-100, NFS-320, and NFS2-640.
- CMD activation compatible with any FACP.
- FACP automatically directs voice messages to each or all audio zones.
- Paging by zone or All-Call.
- Full status indication (normal, active, fault) for each speaker circuit.
- Fault indication via ACS serial link and/or two Form-C trouble relays (System and AC Power Loss).
- Integral 25 watt, 25 Vrms audio amplifier with single Style Z (Class A) or Style Y (Class B) speaker circuit (expandable to 50 watts with ACC-AAM25).
- Modular design for flexibility and ease of service.
- Two command input circuits field-programmable for activation by Notification Appliance Circuit (NAC) or contact closure.
- Three command input circuits activate on contact closure.
- ACS link or Command Input (CMD) control supports various message durations: one 60-second, two 30-second, three 20-second, four 15-second, or five 12-second messages.
- Microphone time-out feature.
- Nineteen system and diagnostic LEDs.
- Optional equipment: second amplifier, local playback speaker, remote microphone, paging equipment interface.
- Integral digital message generator with standard, factory-prerecorded emergency evacuation messages.
- Custom messages are field recordable via integral microphone or audio input jacks.
- Digital message repeat selection: 3, 4, 6, 8, or infinite repeats.
- Built-in alert tone generators: steady, slow whoop, high/low, or chime tones.
- Field-selectable lead-in/trailing tone selection.
- Alert tone selection programmable to conform with ANSI S3.41 Audible Emergency Evacuation Signal (Temporal Pattern), per NFPA.
- Speaker zone control via ACS serial link, CMD inputs, or keypad.
- Dual-optically-isolated trigger input circuits field-programmable for activation by polarity reversal (host FACP NAC) or dry-contact closure.
- Integral diagnostic LEDs: Power, System Trouble, Microphone Trouble, Message Generator Trouble, Tone Generator Trouble, Amplifier Fault, and others.
- ACS serial link or independent Form-C trouble relay allows FACP to monitor voice system during active alarm state.
- Integral piezo provides local audible indication for troubles.
- Fully supervised in standby and active states, including integral microphone, amplifier output, message generator, speaker wiring, and tone generators.
- Independent amplifier supervision: current limit, audio level, short circuit protection.
- All outputs are power-limited.
- Auxiliary power output provides local power for addressable control modules.
- Compatible with all NOTIFIER FACPS and other manufacturers' panels.
Optional Modules
ACC-AAM25
- 25 watt, 25 Vrms audio amplifier module.
- Field-programmable for system expansion to 50 watts or as a backup to the primary 25 watt amplifier.
- Single Class A or Class B speaker circuit.
- Plug-in terminal blocks for service and maintenance.
- Fully supervised and power-limited.
- Diagnostic LEDs: yellow "trouble" LED (cable fault, amp fault) and green "amp functional" LED.
ACC-EPM
- Provides interface to non-fire paging equipment for non-emergency paging applications.
- Plug-in terminal blocks for service and maintenance.
- Transformer-isolated, 600-ohm audio connection to paging equipment.
- Electrically-isolated, contact-closure trigger input for activation by paging equipment.
FC-XRM70
- Converts 25 Vrms audio outputs to 70.7 Vrms for retrofit applications.
- Plugs directly onto ACC-AAM25 module(s) for independent conversion.
FC-LPS
- Provides local digital message playback for user review of field-recorded custom messages.
Controls and Indicators
LED Indicators
- 1. Power On (green).
- 2. System Trouble (yellow).
- 3. Message Generator Trouble (yellow).
- 4. Tone Generator Trouble (yellow).
- 5. Microphone Trouble (yellow).
- 6. Record/Playback (green).
- 7. All-Call (green = Active).
- 8. Audio ON/OFF (green = Active, yellow = Manual Deactivation).
- 9. Status of each speaker zone (green = Active, yellow = Manual Deactivation or Fault).
Other system LEDs: Battery Trouble, Charger Trouble, Ground Fault, (ACC-AAM25) Speaker Circuit Trouble, and Amplifier Supervisory.
Product Line Information
- NFV-25/50ZS: 25 watt, 25 Vrms, Emergency Voice Evacuation Control Panel (VECP) with integral commercial microphone, digital message generator, zone splitter module (ACC-ZSM), zone page module with keypad (ACC-ZPMK).
- ACC-AAM25: Optional 25 watt, 25 Vrms Audio Amplifier Module with single Class A or Class B speaker circuit.
- ACC-EPM: Optional External Page Module.
- FC-XRM70: Optional 70.7 Vrms Converter Module (one required per amplifier, consult factory for availability).
- VEC-RM: Optional Remote Microphone, includes backbox (only one VEC-RM per system).
- FC-LPS: Optional Local Playback Speaker.
- BAT Series: Two batteries required. Consult FACP manual for specific current requirements; see data sheet DN-6933 for battery overview.
- FC-RM: Optional Remote Microphone, includes backbox (only one FC-RM per system).
- ACC-TR: Optional Trim Ring for semi-flush mounting.
System Specifications
Primary Power (AC)
- 120 VAC, 60 Hz, 1.5 A.
- Wire size: minimum #14 AWG with 600 V insulation. Nonpower-limited, supervised.
Secondary Power (Battery) Charging Circuit
- Lead-acid batteries only.
- Maximum Charging Circuit: Normal Float Charge - 27.6V @ 0.800 A.
- Maximum Charger Capacity: 18 Amp Hour battery. (NFV-25/50ZS Series cabinet holds max. 18 Amp Hour Battery.)
AC Loss Relay (TB7)
- Operation: normally energized fail-safe relay transfers on AC power loss for independent monitoring by DACT.
- AC Loss Relay can be programmed as the sole indication of an AC loss condition.
- AC Loss relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.6 amps @ 30 VAC (resistive).
Command Input Circuits (CMD1 and CMD2)
- Trigger input voltage: 10.5 – 29 VDC. (NOTE: When programmed for reverse-polarity activation.)
Trouble Contact Rating
- 2.0 A at 30 VDC (resistive), 0.6 A @ 125 VAC (resistive).
Auxiliary Power Output
- Specific application power: 24 V, 35 mA.
Cabinet Specifications
- Door: 26.174" (66.482 cm) high x 15.780" (40.081 cm) wide x 1.125" (2.858 cm) deep.
- Backbox: 26.0" (66.040 cm) high x 15.5" (39.370 cm) wide x 4.75" (12.065 cm) deep, depth includes door.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 - 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, extreme temperature ranges and humidity may adversely affect the useful life of standby batteries and electronic components. It is recommended that the system and peripherals be installed in an environment with a normal room temperature of 15 - 27°C/60 – 80°F.
Standards and Codes
The NFV-25/50ZS complies with the following standards: NFPA 72 National Fire Alarm Code; NFPA 101 Life Safety Code; UL 864 Standard for Control Units for Fire Alarm Systems (9th edition).
Agency Listings and Approvals
The listings and approvals below apply to the basic NFV-25/50ZS control panel. Consult factory for the latest listing status, as some modules may not be listed by all agencies or listing may be in process.
- UL: S635
- CSFM: 6911-0028:229
- MEA: 341-03-E Vol. 2
Product Image Description
The primary visual depicts the NOTIFIER FireVoice-25/50ZS Voice Evacuation Control Panel. It is a rectangular unit featuring a display screen, control buttons, and indicator lights, presented in a professional, industrial design.
Legal and Copyright Information
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended for installation purposes. Information is kept up-to-date and accurate, but specific applications or requirements cannot be covered. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com. Made in the U.S. A.