Dwyer Series MSX and MSX Pro Magnesense® Pressure Transmitter
Specifications - Installation and Operating Instructions
QUICK START GUIDE
- Mount transmitter with pressure ports facing down. Do not overtighten mounting screws.
- Attach wires following diagram on reverse side.
- Set Zero Calibration. Apply zero pressure to both pressure ports on transmitter at the same time you press ZERO button for 3 seconds.
- Scan QR code with smart device to open the product web page for additional resources.
WIRING INFORMATION
4-20 mA
Diagram Description: A wiring diagram shows a DC POWER SUPPLY (10-36 VDC) connected to a CURRENT RECEIVER. The transmitter has terminals labeled VAC, VDC, COM, and VOUT. The DC POWER SUPPLY positive terminal connects to the VDC terminal of the transmitter. The COM terminal of the transmitter connects to the negative terminal of the DC POWER SUPPLY. The VOUT terminal of the transmitter connects to the positive terminal of the CURRENT RECEIVER. The negative terminal of the CURRENT RECEIVER is connected to the COM terminal of the transmitter.
3-wire voltage (with DC supply)
Diagram Description: A wiring diagram shows a DC POWER SUPPLY (17-36 VDC) connected to a VOLTAGE RECEIVER. The transmitter has terminals labeled VAC, VDC, COM, and VOUT. The DC POWER SUPPLY positive terminal connects to the VDC terminal of the transmitter. The COM terminal of the transmitter connects to the negative terminal of the DC POWER SUPPLY. The VOUT terminal of the transmitter connects to the positive terminal of the VOLTAGE RECEIVER. The negative terminal of the VOLTAGE RECEIVER is connected to the COM terminal of the transmitter.
See online User Guide for AC wiring.