Dwyer Series 655A Wet/Wet Differential Pressure Transmitter

Specifications - Installation and Operating Instructions

The Series 655A Differential Pressure Transmitter converts a positive differential pressure measurement into a standard 4-20 mA output signal. Designed for use as a wet/wet differential pressure transmitter, it can be used to measure gas or liquid pressure compatible with 316L stainless steel wetted parts. With an accuracy of less than $\pm 0.25 \%$ (BFSL, RSS), the Series 655A Pressure Transmitter can measure low differential pressures, but can withstand working pressures to a maximum of 1000 psi (68.95 bar), 3000 psi (206.8 bar) burst.

INSTALLATION

Location

Select a location where the temperature of the transmitter will be between -20 to $200^{\circ} \mathrm{F}$ (-29 to $93^{\circ} \mathrm{C}$). Distance from the receiver is limited only by total loop resistance. Tubing or piping of extended lengths will increase response time slightly.

Position

The transmitter is not position sensitive. However, all standard models are originally calibrated with the unit in a vertical position and with the pressure connections at horizontal. Although they can be used at other angles, for best accuracy it is recommended that zeroing and spanning be done while unit is in the alternative position.

Pressure Connections

Pressure connections are $1/4^{\prime \prime}$ female NPT. Use a small amount of plumbers thread tape or other suitable sealant to prevent leaks. Be sure the pressure passage inside the port is not blocked.

SPECIFICATIONS

Service Compatible gasses or liquids.
Wetted Materials 316L SST.
Accuracy $\pm 0.25 \%$ BFSL, RSS (combined effect of non-linearity, hysteresis, and repeatability).
Stability $\leq \pm 0.25 \%$ FSO/yr.
Temperature Limits -20 to $200^{\circ} \mathrm{F}$ (-29 to $93^{\circ} \mathrm{C}$).
Compensated Temperature Limits 0 to $170^{\circ} \mathrm{F}$ (-17.8 to $76.7^{\circ} \mathrm{C}$).
Pressure Limits 1000 psi (68.95 bar) continuous; 3000 psi (206.8 bar) burst.
Thermal Effects $\leq \pm 1.5 \%$ F.S. oven comp. temperature range.
Power Requirements 8 to 38 Vdc.
Output Signal 4 to 20 mA.
Static Pressure Effects on zero: $\leq \pm 0.25 \%$ FSO per 1000 psi; on span: $\leq \pm 0.5 \%$ of reading per 1000 psi.
Loop Resistance 1500 ohms.
Electrical Connections Cable exit with $24^{\prime \prime}$ cable; optional 6-pin connector.
Process Connections $1/4^{\prime \prime}$ NPT female.
Enclosure Rating Designed to meet NEMA 4X (IP66).
Mounting Orientation Mount in vertical position: zero shifts up to $1^{\prime \prime} \mathrm{H}_{2} \mathrm{O}$ depending on orientation.
Response Time $<10 \mathrm{mS}$.
Weight $18 \mathrm{oz}$ (510 g).
Agency Approval CE.

Electrical Connections

Use A-232 with $6^{\prime \prime}$ pin connection models.

Diagram showing the A-232 connector end and the opposite end with six wires: RED POSITIVE, BLACK NEGATIVE, GREEN CASE GROUND.

Two (2)-Wire Operation

An external power supply delivering 8 to 38 Vdc with minimum current capability of 40 mA DC (per transmitter) is required to power the control loop. The range of appropriate receiver load resistance for the DC power supply voltage available is expressed by the formula and graph below. Shielded two wire cable is recommended for control loop wiring.

Diagram illustrating a 2-wire connection: PRESSURE TRANSMITTER connected via a BLACK WIRE to a RECEIVER, which is then connected to a POWER SUPPLY (8-38 VDC).
Graph showing Receiver Resistance (Ohms) on the Y-axis and Power Supply Voltage (VDC) on the X-axis. The graph displays an operating range defined by the formula RL MAX = (Vps - 8.0) / 20 mA DC.

Wire Length

The maximum length of wire connecting the transmitter and receiver is a function of wire size and receiver resistance. Wiring should not contribute more than $10 \%$ of the receiver resistance to total loop resistance. For extremely long runs (over 1000 feet (305 m)), choose receivers with lower resistance to minimize the size and cost of connecting leads. Where wiring length is under 100 feet (30.5 m), wire as small as 22 AWG can be used.

MAINTENANCE

Upon final installation of the Series 655A Differential Pressure Transmitter, no routine maintenance is required. A periodic check of system calibration is recommended. The Series 655A is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.

Dwyer Instruments, Inc.
P.O. BOX 373, MICHIGAN CITY, INDIANA 46361, U.S.A.
Phone: 219/879-8000 Fax: 219/872-9057
www.dwyer-inst.com e-mail: info@dwyer-inst.com

Models: 655A-XX-P, 655A Series Wet Wet Differential Pressure Transmitter, 655A Series, Wet Wet Differential Pressure Transmitter, Differential Pressure Transmitter, Pressure Transmitter, Transmitter

File Info : application/pdf, 2 Pages, 178.18KB

PDF preview unavailable. Download the PDF instead.

655A iom

References

Acrobat Distiller 8.1.0 (Macintosh)

Related Documents

Preview Dwyer Series DM-2000 Differential Pressure Transmitter - Technical Data
Explore the Dwyer Series DM-2000 Differential Pressure Transmitter, a digital device for measuring air and compatible gases. Features include easy calibration, tamper-proof settings, quick response, and a clear LCD display. This transmitter is designed for seamless integration into Building Automation Systems and offers a standard 4-20 mA output.
Preview Dwyer Series DM DigiMag Differential Pressure Transmitter: Specifications and Instructions
Comprehensive guide to the Dwyer Series DM DigiMag Differential Pressure Transmitter, covering specifications, installation, operation, and calibration. Features include digital push-button zero and span, LCD display, and 4-20 mA output.
Preview Dwyer Series 605 Magnehelic Differential Pressure Transmitter - Specifications and Instructions
Detailed specifications, installation, and operating instructions for the Dwyer Series 605 Magnehelic Differential Pressure Indicating Transmitter. Covers features, model chart, electrical and mechanical specifications, mounting, pressure connections, and output ranging.
Preview Dwyer DM-1000 DigiMag Digital Differential Pressure Gage: Specifications, Installation & Operation
Comprehensive guide to the Dwyer DM-1000 DigiMag Digital Differential Pressure Gage, covering its specifications, installation procedures, operating instructions, and maintenance. Features include field-programmable units, filter set points, and versatile power options.
Preview Dwyer Series WHT Weather-Resistant Humidity/Temperature Transmitter
Dwyer Series WHT is a weather-resistant humidity and temperature transmitter designed for applications like air handling economizers and agricultural environment monitoring. It features a compact NEMA 3S housing, a removable sintered filter, and offers 4-20 mA or 0-10 VDC output signals for both temperature and humidity.
Preview Dwyer Series MSX and MSX Pro Magnesense Pressure Transmitter Quick Start Guide
Quick start guide for Dwyer Series MSX and MSX Pro Magnesense Pressure Transmitters, covering mounting, wiring, and zero calibration.
Preview Dwyer Series A3000 Photohelic Differential Pressure Switch/Gage: Specifications and Operating Instructions
Detailed guide for the Dwyer Series A3000 Photohelic® Differential Pressure Switch/Gage, covering specifications, installation, operation, and electrical connections for industrial air and gas pressure control.
Preview Dwyer A-610 Pipe Mounting Kit Installation Instructions
Detailed installation instructions for the Dwyer A-610 Pipe Mounting Kit, compatible with Magnehelic, Capsuhelic gages, and 1950 series switches. Includes hole selection guide and mounting procedures.