Legrand DPX³ 160 Thermal Magnetic Circuit Breakers and DPX³-I 160 Trip-Free Switches

Technical Data Sheet

Introduction

The DPX³ platform offers advanced protection devices for precise current control in various installations. It provides a comprehensive solution for medium power applications, featuring high-performance breakers in compact dimensions at a competitive cost.

Product Range

DPX³ 160 Thermal Magnetic Circuit Breakers

Available in 3-pole and 4-pole configurations with breaking capacities of 16 kA and 25 kA.

DPX³-I 160 Trip-Free Switches

Available in 3-pole and 4-pole configurations with breaking capacities of 16 kA, 25 kA, 36 kA, and 50 kA.

Technical Characteristics

Electrical Characteristics (DPX³ 160)

Rated Current (In) Breaking Capacity (Icu) Breaking Capacity (kA) & Ics
16 A, 25 A, 40 A, 63 A, 80 A, 100 A, 125 A, 160 A 16 kA, 25 kA
Ue 16 kA 25 kA 36 kA 50 kA
240 V~ 25 35 50 65
415 V~ 16 25 36 50
500 V~ 8 10 12 15
690 V~ 5 5 8 10

Electrical Characteristics (DPX³-I 160)

Rated Current (In) Breaking Capacity (Icu) Breaking Capacity (kA) & Ics
160 A 16 kA, 25 kA, 36 kA, 50 kA
Ue 16 kA 25 kA 36 kA 50 kA
415 V~ 16 25 36 50
690 V~ 5 5 8 10

Key Specifications:

Mechanical Characteristics

Installation Rules

Temperature deratings are provided based on ambient temperature and installation conditions. The table indicates maximum long-time protection setting based on ambient temperature.

Derating factors for various cable types and connection methods (fixed vertical/horizontal installation) are detailed in the technical data sheet.

Altitude Derating:

Altitude (m) Ue (V) In (A) (Ta = 40 °C / 50 °C)
2000 690 1 x In
3000 590 0.98 x In
4000 520 0.93 x In
5000 460 0.9 x In

Dimensions and Weight

Dimensions (mm)

Detailed diagrams for fixed versions, front terminals, side motor operators, direct rotary handles, and vari-depth rotary handles are provided.

Weight (kg)

Configuration 3P 4P
Circuit breaker/trip-free switch 1.27 1.38
Direct rotary handle* 0.35 0.72
Vari depth rotary handle* 1.08 -
Interlock* 0.13 0.17

Connections

Various connection methods are supported, including:

Specifications for cage terminal capacity and cable cross-sections for both standard and high-capacity terminals are detailed.

DC Connections Modality

Diagrams illustrate DC connection configurations for breakers and trip-free switches (polarity can be inverted).

Equipments and Accessories

Releases

Auxiliary Contacts

Rotary Handles

Locking Accessories

Accessories for rotary handles and general purpose rotary handles are available.

Motor Operators

Mechanical Accessories

Connection Accessories

Marking

Products are labeled in conformity with IEC/EN standards and directives. Labels include manufacturer information, product denomination, standard conformity, and declared characteristics.

Product Laser Label (front face): Contains manufacturer, product type, standard conformity, declared characteristics, and Icu identification.

Product Sticker Label (on the side): Includes manufacturer, product denomination, standard conformity, directive requirements, barcode, and country of manufacture.

Packaging Sticker Label: Features manufacturer details, product denomination, standard conformity, directive requirements, barcode, and country of manufacture.

Curves

Thermal Magnetic Tripping Curve

The document includes a graph illustrating the thermal magnetic tripping curve, showing tripping time versus current (I/In) for different rated currents (In) and magnetic trip settings (li).

Pass-through Specific Energy Characteristic Curve

A graph displays the pass-through specific energy (I²t) as a function of short circuit current (Icc) for various rated currents.

Cut-off Peak Current Characteristic Curve

A graph illustrates the cut-off peak current (Ip) as a function of short circuit current (Icc) for different rated currents.

Standards and Regulations

DPX³ and DPX³-I products comply with IEC/EN standards 60947-2 and 60947-3.

They also comply with European Directives:

Other Information

XLPro Calcul: Software for creating calculation notes for installers, design offices, and maintenance operators.

XLPro³ Tool Selectivity and backup: Software for defining selectivity and backup values and obtaining tripping curves.

XLPro Panels: Software for designing electrical distribution, creating diagrams, and costing projects.

Workshop book: Available on e-catalog for mounting information, equipment, accessories, and spare parts.

PEP: Available on e-catalog.

For further technical information, contact Legrand technical support.

PDF preview unavailable. Download the PDF instead.

F01360EN 09 Adobe PDF Library 17.0 Adobe InDesign 20.4 (Windows)

Related Documents

Preview Legrand DPX³ 250 Thermal Magnetic Circuit Breakers with Earth Leakage - Technical Data
Comprehensive technical data for Legrand DPX³ 250 thermal magnetic circuit breakers and DPX³-I 250 trip-free switches with earth leakage, covering specifications, installation rules, dimensions, accessories, and tripping curves.
Preview Legrand Control Module with Netatmo (Gateway) - Technical Data Sheet
Technical specifications and installation guide for the Legrand Control Module with Netatmo (gateway), a modular Wi-Fi/RF gateway for smart home automation systems. Details electrical characteristics, dimensions, connection, configuration, and standards.
Preview Legrand DPX³ 160 Thermal Magnetic Circuit Breakers with Earth Leakage - Technical Data
Comprehensive technical data sheet for Legrand DPX³ 160 thermal magnetic circuit breakers and DPX³-I 160 trip-free switches with earth leakage, covering specifications, installation, dimensions, and performance curves.
Preview Legrand 4 120 40/4 120 41 EMDX³ Energy Meter Technical Specifications and Wiring Guide
Detailed technical specifications, installation instructions, and wiring diagrams for the Legrand 4 120 40 and 4 120 41 EMDX³ three-phase energy meters. Includes RS485 Modbus connectivity and safety guidelines.
Preview Legrand DPX³ 160 Magnetic Thermal Circuit Breakers and Free Release Miniature Circuit Breakers
Technical datasheet for Legrand DPX³ 160 magnetic thermal circuit breakers and DPX³-I 160 free release miniature circuit breakers, covering technical specifications, installation guidelines, dimensions, accessories, and standards compliance.
Preview Legrand 4 120 42/4 120 43 3-Phase CT Energy Meter Installation and Technical Guide
Comprehensive guide for Legrand 3-phase CT energy meters (models 4 120 42, 4 120 43), covering installation, wiring diagrams, RS485 Modbus communication, and EU Declaration of Conformity.
Preview Wattstopper CI-200 PIR Ceiling Occupancy Sensor Specifications
Detailed specifications for the discontinued Wattstopper CI-200 PIR Ceiling Occupancy Sensor, including features, benefits, dimensions, and technical information.
Preview Legrand DPX³ 250 Thermal-Magnetic Circuit Breakers - Technical Data
Technical data sheet for Legrand DPX³ 250 thermal-magnetic circuit breakers and DPX³-I 250 trip-free circuit breakers, covering electrical and mechanical characteristics, installation guidelines, dimensions, and accessories.