Legrand DPX³ 160 Thermal Magnetic Circuit Breakers and DPX³-I 160 Trip-Free Switches
Technical Data Sheet
Introduction
The DPX³ platform offers advanced protection devices for precise current control in various installations. It provides a comprehensive solution for medium power applications, featuring high-performance breakers in compact dimensions at a competitive cost.
Product Range
DPX³ 160 Thermal Magnetic Circuit Breakers
Available in 3-pole and 4-pole configurations with breaking capacities of 16 kA and 25 kA.
DPX³-I 160 Trip-Free Switches
Available in 3-pole and 4-pole configurations with breaking capacities of 16 kA, 25 kA, 36 kA, and 50 kA.
Technical Characteristics
Electrical Characteristics (DPX³ 160)
Rated Current (In) | Breaking Capacity (Icu) | Breaking Capacity (kA) & Ics | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
16 A, 25 A, 40 A, 63 A, 80 A, 100 A, 125 A, 160 A | 16 kA, 25 kA |
|
Electrical Characteristics (DPX³-I 160)
Rated Current (In) | Breaking Capacity (Icu) | Breaking Capacity (kA) & Ics | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
160 A | 16 kA, 25 kA, 36 kA, 50 kA |
|
Key Specifications:
- Rated Insulation Voltage (Ui): 800 V
- Rated Operating Voltage (Ue): 690 V
- Rated Impulse Withstand Current (Uimp): 8 kV
- Rated Frequency: 50 Hz - 60 Hz
- Operating Temperature: -25 °C to 70 °C
- Electrical Endurance at In: 8000 cycles
- Electrical Endurance at 0.5 x In: 10000 cycles
Mechanical Characteristics
- Mechanical Endurance: 25000 cycles
- Mechanical Endurance with Motor Control: 25000 cycles
Installation Rules
Temperature deratings are provided based on ambient temperature and installation conditions. The table indicates maximum long-time protection setting based on ambient temperature.
Derating factors for various cable types and connection methods (fixed vertical/horizontal installation) are detailed in the technical data sheet.
Altitude Derating:
Altitude (m) | Ue (V) | In (A) (Ta = 40 °C / 50 °C) |
---|---|---|
2000 | 690 | 1 x In |
3000 | 590 | 0.98 x In |
4000 | 520 | 0.93 x In |
5000 | 460 | 0.9 x In |
Dimensions and Weight
Dimensions (mm)
- 3P (W x H x D): 80 x 130 x 97
- 4P (W x H x D): 110 x 130 x 97
Detailed diagrams for fixed versions, front terminals, side motor operators, direct rotary handles, and vari-depth rotary handles are provided.
Weight (kg)
Configuration | 3P | 4P |
---|---|---|
Circuit breaker/trip-free switch | 1.27 | 1.38 |
Direct rotary handle* | 0.35 | 0.72 |
Vari depth rotary handle* | 1.08 | - |
Interlock* | 0.13 | 0.17 |
Connections
Various connection methods are supported, including:
- Busbars
- Cable lugs
- Cables
- Extended front terminals
- Cage terminals
Specifications for cage terminal capacity and cable cross-sections for both standard and high-capacity terminals are detailed.
DC Connections Modality
Diagrams illustrate DC connection configurations for breakers and trip-free switches (polarity can be inverted).
Equipments and Accessories
Releases
- Shunt releases (ST)
- Undervoltage releases (UVR)
- Time-lag undervoltage releases
Auxiliary Contacts
- Standard auxiliary contact (OC) / Fault signal (CTR)
- Set of connectors for auxiliary contacts
- Auxiliary contacts (1NC and 1 NO)
- Signal contact for plugged-in version
Rotary Handles
- Direct on DPX³ (with auxiliary option)
- Vari-depth handle IP55 (with auxiliary option)
- Direct on DPX³ (general purpose)
- Vari-depth handle IP55 (general purpose)
Locking Accessories
Accessories for rotary handles and general purpose rotary handles are available.
Motor Operators
- Side motor operator (24 - 230 V~)
Mechanical Accessories
- Padlocks for locking in "open" position
- Insulated shields (phase barriers)
- Sealable terminal shields
- Fixing plates in XL³ for transfer switches
- Fixing plates in XL³
Connection Accessories
- Front spreaders
- Rack screw and nut
- Cage terminals (standard and high capacity)
Marking
Products are labeled in conformity with IEC/EN standards and directives. Labels include manufacturer information, product denomination, standard conformity, and declared characteristics.
Product Laser Label (front face): Contains manufacturer, product type, standard conformity, declared characteristics, and Icu identification.
Product Sticker Label (on the side): Includes manufacturer, product denomination, standard conformity, directive requirements, barcode, and country of manufacture.
Packaging Sticker Label: Features manufacturer details, product denomination, standard conformity, directive requirements, barcode, and country of manufacture.
Curves
Thermal Magnetic Tripping Curve
The document includes a graph illustrating the thermal magnetic tripping curve, showing tripping time versus current (I/In) for different rated currents (In) and magnetic trip settings (li).
Pass-through Specific Energy Characteristic Curve
A graph displays the pass-through specific energy (I²t) as a function of short circuit current (Icc) for various rated currents.
Cut-off Peak Current Characteristic Curve
A graph illustrates the cut-off peak current (Ip) as a function of short circuit current (Icc) for different rated currents.
Standards and Regulations
DPX³ and DPX³-I products comply with IEC/EN standards 60947-2 and 60947-3.
They also comply with European Directives:
- RoHS: Restriction of Hazardous Substances (2011/65/EU, amended by 2015/863/EU).
- REACH: Registration, Evaluation, Authorisation and Restriction of Chemicals (Regulation (EC) No 1907/2006).
- WEEE: Waste Electrical and Electronic Equipment Directive (2012/19/EU).
- Packaging: Compliant with European Directive 94/62/CE.
Other Information
XLPro Calcul: Software for creating calculation notes for installers, design offices, and maintenance operators.
XLPro³ Tool Selectivity and backup: Software for defining selectivity and backup values and obtaining tripping curves.
XLPro Panels: Software for designing electrical distribution, creating diagrams, and costing projects.
Workshop book: Available on e-catalog for mounting information, equipment, accessories, and spare parts.
PEP: Available on e-catalog.
For further technical information, contact Legrand technical support.
Related Documents
![]() |
Legrand DPX³ 250 Thermal Magnetic Circuit Breakers with Earth Leakage - Technical Data Comprehensive technical data for Legrand DPX³ 250 thermal magnetic circuit breakers and DPX³-I 250 trip-free switches with earth leakage, covering specifications, installation rules, dimensions, accessories, and tripping curves. |
![]() |
Legrand Control Module with Netatmo (Gateway) - Technical Data Sheet Technical specifications and installation guide for the Legrand Control Module with Netatmo (gateway), a modular Wi-Fi/RF gateway for smart home automation systems. Details electrical characteristics, dimensions, connection, configuration, and standards. |
![]() |
Legrand DPX³ 160 Thermal Magnetic Circuit Breakers with Earth Leakage - Technical Data Comprehensive technical data sheet for Legrand DPX³ 160 thermal magnetic circuit breakers and DPX³-I 160 trip-free switches with earth leakage, covering specifications, installation, dimensions, and performance curves. |
![]() |
Legrand 4 120 40/4 120 41 EMDX³ Energy Meter Technical Specifications and Wiring Guide Detailed technical specifications, installation instructions, and wiring diagrams for the Legrand 4 120 40 and 4 120 41 EMDX³ three-phase energy meters. Includes RS485 Modbus connectivity and safety guidelines. |
![]() |
Legrand DPX³ 160 Magnetic Thermal Circuit Breakers and Free Release Miniature Circuit Breakers Technical datasheet for Legrand DPX³ 160 magnetic thermal circuit breakers and DPX³-I 160 free release miniature circuit breakers, covering technical specifications, installation guidelines, dimensions, accessories, and standards compliance. |
![]() |
Legrand 4 120 42/4 120 43 3-Phase CT Energy Meter Installation and Technical Guide Comprehensive guide for Legrand 3-phase CT energy meters (models 4 120 42, 4 120 43), covering installation, wiring diagrams, RS485 Modbus communication, and EU Declaration of Conformity. |
![]() |
Wattstopper CI-200 PIR Ceiling Occupancy Sensor Specifications Detailed specifications for the discontinued Wattstopper CI-200 PIR Ceiling Occupancy Sensor, including features, benefits, dimensions, and technical information. |
![]() |
Legrand DPX³ 250 Thermal-Magnetic Circuit Breakers - Technical Data Technical data sheet for Legrand DPX³ 250 thermal-magnetic circuit breakers and DPX³-I 250 trip-free circuit breakers, covering electrical and mechanical characteristics, installation guidelines, dimensions, and accessories. |