INSTALLATION INSTRUCTIONS

TITAN SERIES

MODEL ELT50, ELT50 N

CAUTION: For safety and proper operation, read and follow instructions carefully before installation.

Parts Description

Figure 1: Illustrates the emergency light unit (ELT50) with its components, including the housing, lamp heads, and a separate depiction of the battery and its connection.

IMPORTANT SAFEGUARDS

  1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
  2. Do not use outdoors.
  3. Do not let power supply cord touch hot surfaces.
  4. Do not mount near gas or electric heater.
  5. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or in eyes, flush acid with fresh water and contact a physician immediately.
  6. Equipment should be mounted in location and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  7. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
  8. Do not use this equipment for other than intended use.
  9. Before wiring to power supply, turn off electricity at fuse or circuit breaker.
  10. Consult your local building code for approved wiring.
  11. Fixture must be grounded to avoid potential electric shock.
  12. Disconnect A.C. power and unplug battery before servicing.
  13. All servicing should be performed by qualified personnel.
  14. CAUTION: Halogen cycle lamp(s) may be used in this fixture to avoid shattering, do not operate lamp in excess of rated voltage. Protect lamp against abrasions, scratches and against liquids when lamp is operating. Dispose of lamps with care. Halogen lamps operate at high temperatures. Do not store or place flammable materials near lamps.

SAVE THESE INSTRUCTIONS

BEFORE INSTALLATION

Unit should be located to assure adequate clearance for front cover and lampheads.

Do not position unit where it will be exposed to direct sunlight, radiators, or other heat sources. Prolonged exposure to high temperatures will shorten battery life and may void warranty.

CAUTION: Damage to battery will occur if battery is connected to charger board for a prolonged period of time without A.C. power provided.

MOUNTING TO WALL USING J-BOX

  1. Remove all knockouts from rear of housing. Locate center 7/8" knockout over J-box.
  2. Install fastener with a minimum pullout rating of 30 pounds in each keyhole mounting slot (④) and in lower oblong mounting slot (⑤) (see Figure 1).

MOUNTING WITH SURFACE CONDUIT

  1. Two 7/8" dia. knockouts are located on either side of housing for conduit connection. Remove keyhole mounting slot knockouts (④) and lower oblong mounting slot knockout (⑤) from rear of housing, and remove desired 7/8" knockout from side of housing.
  2. Install fastener with a minimum pullout rating of 30 pounds in each keyhole mounting slot (④) and in lower oblong mounting slot (⑤) (see Figure 1).

WIRING

(Refer to Fig. 2, 3, or 4)

  1. Connect A.C. input as follows:
    • 120V AC - Black and White leads
    • 277V AC - Brown or Orange and White leads

    NOTE: Unused lead must be properly capped with standard wirenut.

  2. Place battery (⑥) inside housing (①), and connect battery terminals. In Model ELT50 N, battery is provided with double-stick tape. Remove paper backing from double-stick tape and secure battery in place.
  3. CAUTION: Model ELT50 batteries are wired in series. Be sure to refer to wiring diagram Fig. 4 for proper connection of battery terminals.

  4. Slide ground clip (⑧) onto slot in bottom of 7/8" knockout. Press flag terminal of green ground lead (⑨) onto flange of ground clip (⑧). Connect supply ground to green ground lead (⑨) using standard wirenut. For units that are mounted with surface conduit, attach ground clip and ground lead assembly to upper flanged lip of housing (①).

Figure 2: Depicts wiring connections for remote lamps, showing connections to the terminal board, battery, charger board, and lampheads. It includes color-coded wires (Blue, Yellow, Red, Black) and labels for different components.

INSPECTION AND MAINTENANCE

NOTE: Emergency lighting systems should be tested as often as local codes require, or at least monthly, to ascertain that all components are operational.

A. NORMAL OPERATION: When unit is functioning properly, with A.C. power provided, the "READY" light will be on.

B. TO TEST: Push "TEST" button. D.C. lamps should come on and "READY" light should go out.

C. CHARGER BOARD REPLACEMENT: Disconnect wiring as shown in Fig. 3, or Fig. 4. Charger board is secured to bracket with three nylon standoffs. Depress standoff locking flanges and lift charger board from unit. Install replacement charger board and reconnect wiring as shown in Fig. 3 or Fig. 4.

D. BATTERY REPLACEMENT: Disconnect battery. Replace battery only with a manufacturer's recommended replacement. Reconnect battery as shown in Fig. 3 or Fig. 4.

E. TRANSFORMER REPLACEMENT: Disconnect wiring as shown in Fig. 3, or Fig. 4. Remove mounting screws holding transformer to housing. Replace transformer with manufacturer's recommended replacement and secure to housing using mounting screws, and clips from old transformer.

F. LAMP REPLACEMENT:

Wiring Diagrams

Figure 3: WIRING DIAGRAM: MODEL ELT50 N. Shows connections between Lamphead, Remote LP, Terminal Board, Fuse, Battery, Charger Board, Transformer, and Ground Clip for the ELT50 N model.

Figure 4: MODEL ELT50 WITH OPTIONS. Shows similar connections for the ELT50 model with options, including Load Disconnect and different wire colors (e.g., Violet for Transformer).

NOTES:

Important Battery Information

Batteries are perishable items. For best results, it is recommended that the battery receive an initial charge within the first 18 months of the manufacture date of the fixture. The mfg date can be found on the outside of the unit packaging and on the UL label as part of the Date Code/Series. Note: First two digits in the date code will represent the year and the second two digits will represent the month. Batteries beyond the initial charge recommendation time frame can often times be returned to full capacity by fully charging the battery shortly after installation. If the battery will not fully charge after the initial charge, replacing the battery with a fresh battery will resolve the issue.

Models: ELT50, ELT50 N, ELT50 N Die Formed Steel Emergency Unit, ELT50 N, Die Formed Steel Emergency Unit, Steel Emergency Unit, Emergency Unit, Unit

PDF preview unavailable. Download the PDF instead.

emcsa00590 GPL Ghostscript 9.04

Related Documents

Preview Lithonia Lighting Titan Series ELT Emergency Lighting Installation and Maintenance Guide
Comprehensive installation, wiring, and maintenance instructions for Lithonia Lighting Titan Series ELT50, ELT125, ELT180, ELT250, and ELT275 emergency lighting units.
Preview Titan Series ELT24C, ELT36C Emergency Lighting Unit Installation Guide
Installation guide for Titan Series ELT24C and ELT36C emergency lighting units by Lithonia Lighting. Covers safety, mounting, wiring, inspection, maintenance, battery information, and warranty.
Preview Lithonia Lighting ELT Series Industrial Steel Emergency Lighting - Specifications and Ordering
Detailed specifications, features, and ordering information for Lithonia Lighting's ELT16, ELT24, ELT36, and ELT50 Industrial Steel Emergency Lighting units. Includes electrical, battery, mounting details, and warranty information.
Preview Lithonia Lighting Titan Series ELT16, ELT16 N, ELT24, ELT24 N, ELT36 Installation Instructions
Comprehensive installation, wiring, and maintenance guide for Lithonia Lighting's Titan Series emergency lighting units, including models ELT16, ELT16 N, ELT24, ELT24 N, and ELT36. Covers safety precautions, parts identification, mounting procedures, electrical wiring, inspection, maintenance, and component replacement.
Preview Lithonia Lighting Precise Series ELA LCRIS Recessed Rough-In Sections Installation Guide
Detailed installation instructions for Lithonia Lighting's Precise Collection ELA LCRIS recessed standard rough-in sections, covering ceiling and wall mounting procedures, important safety safeguards, and parts identification.
Preview EXTL EXTREME Emergency Lighting Unit Installation and Maintenance Manual
This manual provides detailed instructions for the installation, testing, and maintenance of the EXTL EXTREME Emergency Lighting Unit by Lithonia Lighting. It covers safety precautions, mounting procedures, component replacement, troubleshooting, and wiring diagrams.
Preview Lithonia Lighting 2GTL Series LED Recessed Troffer - Product Specifications and Ordering
Explore the Lithonia Lighting 2GTL Series 2'x4' LED Recessed Troffer. This document details features, specifications, ordering information, performance data, and photometrics for this energy-efficient lighting solution suitable for commercial and institutional applications.
Preview Lithonia Lighting LED Combo Exit & Emergency Light Installation Instructions
Comprehensive installation, operation, and maintenance guide for Lithonia Lighting's LED Combo Exit & Emergency Light, covering safety, mounting procedures, wiring, and battery backup.