Lochinvar EcoShield High Efficiency Gas Fired Condensing Water Heater User & SMART SYSTEM Control Guide

SHW USER 0016 Issue No. 2 | September 2015

1.0 User Guide

1.1 General Requirements

This equipment must be installed by a competent person, registered with a H.S.E. approved body. All installations must conform to the relevant Gas Safety and Building regulations. Health & safety requirements must also be taken into account when installing any equipment.

Failure to follow these instructions may lead to severe injury, serious property damage or death.

A competent person must also undertake any alterations that require the gas train or flue system to be broken.

Any interference with a sealed component is forbidden.

Failure to comply with the above may lead to prosecution.

Incorrect use may result in injury and will also invalidate the warranty.

1.2 Procedure for Lighting

  1. Ensure that the gas-inlet appliance isolating valve, provided by the installer, is in the "On" position.
  2. Press the power rocker switch, positioned inside the service access front cover (see section 2), to the on position.
  3. Press the Enter/Reset button on the user control interface panel to initiate the burner.
  4. The combustion fan should ramp up to full speed to purge the combustion chamber and then drop back to half rate in order to light. The spark generator should create a spark, visible through the burner sight glass. The appliance will attempt to light 4 times (SHW35-210-SHW116-410) or once (SHW146-410). If the unit does not light, it will go to lockout. If this occurs, please contact a qualified Gas Service Engineer.
  5. Once a flame is established, the LCD display will change to display the Temperature and Setpoint.

1.3 Procedure for Shutting Down

To take the appliance out of service, the Enter/Reset button should be pressed. If the appliance is to be shut down for a long period of time, the power supply should be isolated using the rocker switch on the back and the gas supply should be isolated at the gas inlet appliance isolating valve.

1.4 Temperature Adjustment Procedure

The setpoint can be adjusted using the Up ⬆️ and Down ⬇️ buttons on the Smart System control panel. Once the desired setpoint is displayed, the Enter/Reset button should be pressed to store the value.

The setpoint should be adjusted to ensure that the water is stored at 60°C and distributed at 50°C within 1 (one) minute at all outlets. Care is needed to avoid much higher temperatures because of the risk of scalding. At 50°C, the risk of scalding is small for most people, but the risk increases rapidly with higher temperatures and for longer exposure times. The risk to young children and to those with a sensory or mobility loss will be greater. Where a significant scalding risk has been identified, the use of thermostatic mixing valves on baths and showers should be considered to reduce temperature; these need to be placed as close to the point of use as possible.

1.5 Maintenance

The Lochinvar EcoShield must be serviced by a competent engineer at a maximum interval of every 12 months. By law, location, and usage patterns, service intervals may need to be more frequent.

Details of the necessary maintenance work can be found in the Installation, Commissioning and Maintenance Instructions. If these instructions are not available, a copy should be obtained from the Lochinvar website www.lochinvar.ltd.uk or by using the contact details on the back cover of this document.

1.6 Frost Protection

If the temperature of the water at the inlet side of the heat exchanger drops below 7°C, the primary pump will be energised. If the temperature of the water at the inlet side of the heat exchanger drops further and reaches 3°C, the burner will fire. If the temperature rises above 10°C, the burner and the pump will shut down.

1.7 Air Supply

When installed as a conventionally flued appliance, the room in which the appliance is installed must be ventilated.

Blocking these air vents may lead to severe injury, serious property damage or death.

The area in which the appliance is installed should not be used to store any other materials.

1.8 Condensate Drain

The condensate drain must not be blocked or modified in any way. If fitted with a neutralisation kit, this must be replaced at least every 12 months to ensure correct operation. Due to its design, no further maintenance should be necessary.

2.0 Smart System Control

2.1 User Control Interface Panel

The user control interface panel features a display screen and several buttons for operation and settings adjustment.

Display: Shows current temperature, setpoint, operating status, and error messages.

Buttons:

(Refer to Figure 2.1 in the original document for a visual representation of the panel.)

2.2 Sequence of Operation

The following describes the typical sequence of operation upon a call for heat:

Operation Step Description Display Example
1 Upon call for heat, the control turns on the integrated pump.

48°C
50 DHW

▲ (Pump icon)

2 The control connects 230 VAC to the fan. The fan does not run at this time. (Checks for low water cut-off, manual reset high limit, and louver proving switch if applicable).

48°C
50 DHW

3 The control starts a 10-second pre-purge cycle.

48°C
50 DHW

4 Once the pre-purge cycle is complete, and safety limits are closed, the control starts a 5-second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve.

48°C
50 DHW

? (Blinking)

5 If no flame is detected by the end of the trial, a 10-second post-purge occurs. Models SHW35-116 CE perform another pre-purge and try to light again. If ignition fails after 4 trials, lockout occurs for 1 hour (then another 4 trials). SHW146 CE locks out until manually reset.

48°C
50 DHW

? (Blinking)

6 If flame is detected before trial ignition ends, the control modulates the burner to maintain the setpoint.

48°C
50 DHW

?

7 Once the call for heat is satisfied, the burner turns off. The fan remains on for a 10-second post-purge cycle. The integrated pump continues to run for its programmed delay time, then turns off.

50°C
50 DHW

?

8 The integrated pump switches off.

50°C
50 DHW

3.0 User Settings

3.1 User Adjustable Parameters Screen

To access the User Adjustable Parameters screen, press and hold the ENTER button for 5 seconds. The user code 'u01' should appear in the lower digits. Use the ⬆️ and ⬇️ buttons to scroll through the seven available parameters and the ENTER button to make a selection. After cycling through all parameters, new values are saved.

3.2 Pasteurisation Function (Using Night Set Back Facility)

3.2.1 Procedure for Weekly High Temperature (70°C) Pasteurisation

Follow these steps for a weekly high temperature pasteurisation:

  1. Access the installer menu (Down ⬇️ & Enter for 5 seconds).
  2. Set parameter p02 to 15°C (deduction from pasteurisation temperature; can be reduced to 10°C for 65°C storage).
  3. Set parameter p03 to 75°C (maximum setpoint).
  4. Exit the installer menu.
  5. Access the user menu (Enter for 5 seconds).
  6. Set parameter u02 to 75°C (pasteurisation temperature).
  7. Check that parameters u03 to u07 display the correct date and time.
  8. Exit the user menu.
  9. Access the setback function menu (Up ⬆️ & Down ⬇️ for 5 seconds).
  10. Set the trigger values as follows:
Trigger Day Time
On 1100:00
Off 1123:59
On 2200:00
Off 2223:59
On 3300:00
Off 3323:59
On 4400:00
Off 4423:59
On 5500:00
Off 5523:59
On 6600:00
Off 6623:59
On 7702:00
Off 7723:59
  1. Exit the setback function menu (Enter for 5 seconds).

This configuration causes the water heater to operate at a reduced temperature between 00:00 and 23:59 daily, except for Sunday morning when the reduced temperature becomes active at 02:00. From Saturday night 23:59 until Sunday 02:00, the setpoint will be 75°C.

3.2.2 Procedure for Daily Pasteurisation (Domestic Hot Water < 60°C)

⚠️ Systems must always comply with the requirements of L8. Running water heaters at low temperatures may encourage the growth of legionella bacteria.

  1. Access the installer menu (Down ⬇️ & Enter for 5 seconds).
  2. Set parameter p02 to the required temperature less than the standard pasteurisation setting of 65°C (e.g., if the daily set point is 50°C, set p02 to 15°C).
  3. Set parameter p03 to 65°C (this is the pasteurisation setting).
  4. Exit the installer menu.
  5. Access the user menu (Enter for 5 seconds).
  6. Set parameter u02 to 75°C (this is the pasteurisation temperature).
  7. Check that parameters u03 to u07 display the correct date and time.
  8. Exit the user menu.
  9. Access the setback function menu (Up ⬆️ & Down ⬇️ for 5 seconds).
  10. Set the trigger values as follows:
Trigger Day Time
On 1123:59
Off 1100:59
On 2223:59
Off 2200:59
On 3323:59
Off 3300:59
On 4423:59
Off 4400:59
On 5523:59
Off 5500:59
On 6623:59
Off 6600:59
On 7723:59
Off 7700:59
  1. Exit the setback function menu (Enter for 5 seconds).

This configuration causes the water heater to operate at the reduced temperature between 00:59 and 23:59 each day, with the exception of the period from 23:59 until 00:59 when the setpoint will be 65°C.

⚠️ During the pasteurisation period, any outlets without temperature limiting devices fitted will have very hot water. Suitable precautions should be taken to inform all potential users.

3.3 Night Setback Screen

To access the Night Setback screen, press and hold the ⬆️ and ⬇️ buttons simultaneously for 5 seconds. The trigger type (On/OFF) will be shown in the upper digits.

  1. Use the ⬆️ and ⬇️ buttons to display the desired trigger type (On or OFF) and press ENTER to select.
  2. The trigger number (e.g., On1, OFF1) will appear in the upper digits. On1 is the first trigger to lower the tank set point. Press ENTER.
  3. The day of the week will appear in the lower digits (1 = Monday, 2 = Tuesday, etc.). Press ⬆️ or ⬇️ to display the desired day and press ENTER to select.
  4. The time for that trigger will appear, with the hour digits flashing. Press ⬆️ or ⬇️ to display the desired hour and press ENTER to select.
  5. The minute digits will then start flashing. Press ⬆️ or ⬇️ to display the desired minutes.
  6. If all triggers are set, press and hold ENTER for 5 seconds to save. The burner will shut off and automatically re-ignite. Otherwise, press ENTER once.
  7. The lower digits will clear, and the upper digits will display the trigger type again. Repeat steps 2-5 to set all desired triggers.

3.4 Error Log Screen

The water heater automatically stores the 10 most recent errors. To access the error log screen, press and hold the ⬇️ button for 5 seconds. The upper digits display the error number (most recent is "1"). The lower digits display error details in 2-second intervals:

  1. Error Code
  2. Hour and Minute of the error
  3. Date of the error
  4. Year of the error

Press the ⬆️ button to view the next errors. Press and hold ENTER to pause the information; releasing it resumes the display. Press and hold ⬇️ for 5 seconds to exit the error log screen.

3.5 Error Codes

The user interface provides information on Error codes, which can be one of three types:

  1. Lockout codes: May require user reset and/or service engineer investigation.
  2. Blocking codes: May require investigation by a service engineer.
  3. Notification codes: The unit continues to operate, but a service engineer is required.

Lockout Codes

CodeDescriptionCodeDescription
E00Invalid lockoutE11No flame running
E01Memory lockoutE12No flame ignition
E02Fan speed faultE13Flue temperature limit
E04Flow switch faultE15Manual reset High limit
E05Flame out of sequenceE18Outlet sensor Differential
E06Auto reset Hi limitE19Flue sensor short/open
E07Wiring faultE21Outlet sensor short/open
E08Louvre proving switchE22Inlet sensor open
E09Blocked condense drainE23Inlet sensor shorted
E10Air pressure switch/HEX Limit-contacts are openE15Manual reset High limit

Blocking Codes

CodeDescription
b01Setpoint met
b02Anti-cycling
b03Outlet temperature too high
b04Delta T too high
b05Flue temperature too high
b06Low voltage

Notification Codes

CodeDescription
n01Fan limited due to no flue sensor change
n02Fan limited due to high outlet temperature
n03Fan limited due to high Delta T
n04Fan limited due to high flue temperature
n05Fan increased due to low flame current
n06Tank sensor is open
n07Inlet sensor open
n08Inlet sensor shorted

4.0 ErP Specification Data Sheet

Water Heater Type: SHW35-245 SHW46-325 SHW61-325 SHW86-410 SHW116-410 SHW146-410
Manufacturer Lochinvar Limited
Load Profile XXLXXL3XL3XL3XL3XL
Energy Efficiency 76%73%81%79%78%79%
Daily Electricity Consumption (Qelec) 0.3330.3820.5410.5170.5310.552
Daily Fuel Consumption (Qfuel) 31.39832.89356.18058.39959.23657.952
Mixed water V40 @40°C (litre) 88512135288
Emissions of Nitrogen Oxides (EN15502) (mg/kwh) 565859.759.861.663.3
Sound Power Level (EN 15036-1:2006) (LWA(db)) 565860626466

PDF preview unavailable. Download the PDF instead.

EcoShield User Instructions Microsoft Word 2010 Microsoft Word 2010

Related Documents

Preview Lochinvar EcoShield™ Gas Fired Condensing Water Heaters: Installation, Commissioning, and Maintenance Guide
This guide provides detailed instructions for the installation, commissioning, and maintenance of Lochinvar EcoShield™ Gas Fired Condensing Water Heaters, covering safety, technical specifications, and operational procedures.
Preview Lochinvar Armor Condensing Commercial Gas Water Heaters
Lochinvar's ARMOR Commercial Condensing Water Heater offers 98% thermal efficiency with advanced features like SMART TOUCH control and CON-X-US remote connectivity. Available in five models from 1.25 to 4.0M BTU/hr, it boasts a 5:1 turndown ratio and direct-vent flexibility up to 150 feet. Suitable for indoor and outdoor installations in warm climates.
Preview Lochinvar Commercial Gas Water Heaters: Condensing High Efficiency Models
An overview of Lochinvar's LCT-199 series of commercial gas tankless water heaters, detailing their condensing high efficiency technology, Ultra-Low NOx features, durable heat exchangers, performance specifications, and model details for indoor and outdoor installations.
Preview Lochinvar TTW Series: Gas Fired Condensing Water Heater Installation & Maintenance Manual
Comprehensive installation, commissioning, user, and maintenance guide for Lochinvar TTW410 and TTW580 floor-standing gas-fired condensing circulating type water heaters. Features technical data, safety guidelines, and operational procedures.
Preview Lochinvar Copper-Fin Gas Fired Commercial Water Heaters: Specifications & Features
Detailed information on Lochinvar's Copper-Fin series of gas-fired commercial water heaters, including standard features, dimensions, specifications, optional equipment, and firing controls for models CWN090PM through CWN500PM.
Preview Lochinvar EcoForce++ High Efficiency Gas Fired Condensing Water Heaters: Installation, Commissioning, and Maintenance Instructions
This document provides comprehensive installation, commissioning, and maintenance instructions for the Lochinvar EcoForce++ range of high-efficiency gas-fired condensing water heaters. It details technical specifications, safety requirements, flue system guidelines, electrical connections, troubleshooting procedures, and maintenance schedules for models EF+35/150+, EF+35/230+, and EF+55/230+.
Preview Lochinvar ARMOR Condensing Water Heater Installation & Operation Manual
Comprehensive guide for installing and operating Lochinvar ARMOR Condensing Water Heaters (Models 151-801). Covers safety precautions, system requirements, venting, piping, gas connections, startup procedures, maintenance, and troubleshooting.
Preview Lochinvar Impetus Instantaneous Gas Fired Water Heater: Installation, Commissioning, User & Maintenance Instructions
Comprehensive guide for Lochinvar Impetus Instantaneous Gas Fired Water Heaters (IM 550, IM 750, IM 1250), covering installation, commissioning, operation, maintenance, and technical specifications.