Control unit AV and AV1
CONTROL UNIT WITH EXTRACTIBLE MEMORY
1. Introduction
Control unit for an alternating current motor with torque adjuster (AV1), featuring an output contact for limit switch or Open/Close buttons, selectable. It also includes an output contact for a photo sensor, stop button, step-by-step operation, radio modular capability, expansion memory, and the possibility to install an additional card for courtesy light and electrolock (AV1). This control unit is designed for the automation of rolling shutters, shutters, and sliding doors.
2. Configuration
Card options (only with AV1):
The control unit features various jumper selections (J1-J5) and connectors (LC, ELS) for configuration. The 'LIT LIGHT = FUNCTION ENABLE' indicates that a specific indicator light signifies the function is enabled.
Function Selection Present on AV and AV1 (See page 4):
- J1: Step-by-step / open-close function selection.
- J2: Normal / deadman function selection.
- J3: Fixed code / rolling code selection.
- J4: Condominium function enable / disable selection.
- J5: Limit-switch or button use selection.
An optional torque regulator can be connected (only with AV1). If the torque regulator is used, connect the flashing light (with self-blinking card) to the output of the torque regulator.
3. Electrical connections
The unit supports connections for Antenna, photocells (power supply 24 Vac 1.5W MAX), stop button, COM, and step/passo functions. A connection is available for a blinker BRO LIGHT 220 (with self-blinking card) when the torque regulator is not used.
ATTENTION: N.C. (Normally Closed) contacts that are not used must be jumped to the common wire as shown in the following figure.
J5 jumper configuration for limit switch or button selection:
- J5 close: Limit switch selection.
- J5 open: Button selection.
LEGEND:
- P.C.: Closing button
- P.A.: Opening button
- FCC: Closing limit switch
- FCA: Opening limit switch
Note: Contacts 9 and 10 must be jumped to the common only if jumper J5 is closed and the photocells are not connected.
4. Learning
LED Indicators: FLASHING, CONSTANTLY LIT
Key Actions: PRESS KEY, TRANSMISSION
Important Note: It is not possible to enter the configuration menu while the automation is in movement. The automation MUST BE CLOSED before proceeding.
4.1 Remote control setting
Learning:
- Press the SELECTION key; the CODE LED will start flashing.
- Press the radio control key "a". The control unit will automatically memorize the second key "b" (which can be used as a pedestrian run).
The learning operation is finished when the CODE LED remains lit.
CANCEL:
- Press the SELECTION key until the CODE LED is flashing.
- Press the MODE key. All LEDs will light up, and upon completion, all learned transmitter codes will be deleted (the CODE LED will remain off).
4.2 Setting the gate
Programming work time from 1 sec to 3 min: The control box is supplied with a default work time of 3 minutes.
Work time setting:
- Ensure the GATE is CLOSED.
- Press the SELECTION key twice; the WORK TIME LED will start flashing.
- Press the MODE key. The automation will start to OPEN and continue until the MODE key is released. The WORK TIME is memorized at this point.
- The WORK TIME LED will flash for a few seconds, the gate will re-close, and then the LED will remain permanently ON.
Repeat this procedure to vary the work time. For an INFINITE WORK TIME using the limit switch, keep the MODE key pressed for less than 1 second; the signal will be given by the WORK TIME OFF LED.
ATTENTION: The working time is reloaded every time the control unit is powered on. The first step-by-step command is always OPEN, except when the OPEN LIMIT SWITCH (if present) is activated.
5. Configuration
5.1 Automatic closure
Programming of the automatic closure time from 4 seconds to 2 min: The unit is provided with an active automatic reclosure, with a default time of 30 seconds.
Setting automatic re-closing time:
- Press the SELECTION key three times; the Auto Close LED will start flashing.
- Press the MODE key. The number of flashes corresponds to the closure time in seconds. The first 3 seconds of pressing the key activate the closure; upon releasing the key, the automatic closure begins, and the AUTO CLOSE LED remains lit. Re-closure also occurs in pedestrian function if active.
The unit starts counting the reclosure as soon as it has reached a condition of complete opening, or as soon as the opening operational time is finished, or the opening control is activated. Reclosure does not occur in any other intermediate phase of automation stop.
To disable automatic closure, keep the MODE KEY PRESSED for less than 3 seconds. Upon releasing, the AUTOMATIC RE-CLOSURE LED will remain off.
5.2 Pedestrian function
The control box is supplied with the pedestrian function deactivated. To use this function, the use of the 2nd transmitter channel is indispensable (see paragraph 4).
Activation and setting:
- Press the SELECTION key four times; CODE and WORK TIME LEDs will light up.
- Press the MODE key; the CODE and WORK TIME LEDs will now flash.
- Exit the configuration menu.
- Press the step-by-step key; the automation will start to OPEN and continue until the SELECTION or MODE key is pressed. Upon release, the motor stops, and that position is memorized as the pedestrian run. The second channel learned (b) will now manage the pedestrian function.
To change the pedestrian run, repeat the procedure described above.
To disable the pedestrian function: Use the SELECTION key to disable the pedestrian feature (CODE and WORK TIME LEDs flashing). Pressing the MODE key again will disable the function, indicated by the CODE and WORK TIME LEDs lighting up for a few seconds. If disabled, each time it is re-enabled, it will be necessary to reset the time.
5.3 Electric lock (only on AV1 with optional card)
The control box is supplied with this function deactivated. To use this function, an optional additional card is necessary.
There is an auxiliary output for the use of an electric lock. The activation time is fixed at 3 SECONDS. With a closed gate, a command to open will activate the lock immediately, and the gate will have a delay of 1 second. The electric lock remains active for another two seconds after the start of movement.
To enable this function:
- Press the SELECTION key five times; the WORK TIME & AUTO CLOSE LEDs will light up.
- Pressing the MODE key once will ENABLE the ELECTRIC LOCK feature, indicated by a few FLASHES of the WORK TIME and AUTO CLOSE LEDs.
TO DISABLE IT: Use the SELECTION key on the electric lock ability (WORK TIME & AUTO CLOSE LEDs flashing). Pressing the MODE key again will disable the function, indicated by the WORK TIME and AUTO CLOSE LEDs lighting up for a few seconds. In the event that the function is activated on the AV version, a delay of 1 second will be noted in the opening phase.
5.4 Allmatic or customized variable code
The unit is fitted with the Allmatic variable decoding code.
Enable:
- Press the SELECTION key six times; the CODE and Auto.ric LEDs will light up.
- Press the MODE key; the CODE and Auto.ric LEDs will flash for a few seconds.
- Reset the control unit by pressing the SELECTION and MODE keys simultaneously.
TO ENABLE THE ALLMATIC VARIABLE CODE DECODING: Act on the SELECTION key to use the new parameter (CODE and AUT RECL. LEDs flashing). A press of the MODE key will enable the Allmatic variable code coding, signaled by the permanent lighting of the CODE and AUT RECL LEDs. Reset the control unit.
5.5 Exit from the programming
Each time parameters are altered, the control box exits the menu for that parameter. The available time to act on settings is 10 seconds. Otherwise, the control box automatically exits the programming phase. Skipping the programming phase by pressing SEL the 7th time exits programming mode.
5.6 Reset
To reset the control unit to factory settings, or to switch between fixed code or variable code reception, press the SELECTION AND MODE keys CONTEMPORARILY. All LEDs will light up, flash, and then turn off.
6. Advanced programming
FUNCTIONS SELECTION: Personalization of the automation is possible by operating on the jumpers present on the central control panel. The table below describes the working and effect of each jumper.
N.B.: DISCONNECT THE POWER SUPPLY EACH TIME THAT YOU OPERATE THE JUMPER!!!
To make the personalization phase easier, it is advisable to set the jumpers by removing the optional additional card.
Jumper Settings:
- J1:
- POS.1: The transmitter works in IMPULSE MODE. The memorized key runs these functions: OPEN...STOP...CLOSE...STOP. The second channel memorized by the transmitter manages the PEDESTRIAN mode (in this mode, the transmitter cannot carry out either the deadman function or the normal working function).
- POS.2: The OPEN/CLOSE FUNCTION manages the automation acting on 2 transmitter keys. The first commands the gate to open, the second to close. J1 in position 2 has another possibility of personalizing the central computer acting on jumper 2.
- J2:
- POS.1: Determines the NORMAL WORKING of the wall keys and the transmitter. Pressing the open key opens the gate completely; pressing the key a second time blocks the gate. To stop movement, press the key for the other direction (close key). The same applies to opening. In this J2 configuration, the intervention of photoelectric cells during closure blocks the gate and inverts the movement.
- POS.2: Determines the PERSON PRESENT function with keys on the wall and transmitter (if jumper 1 = POS.2). The automation begins to open or close for the precise time of the relative transmitter button or key. In this J2 configuration, the intervention of the photoelectric cells stops the movement until the obstacle is removed. The movement will recommence, either opening or closing as selected.
- J3:
- OPEN: The central computer allows FIXED CODE transmitter setting.
- CLOSED: The central computer allows VARIABLE CODE transmitter setting.
Important: To switch from FIXED CODE to VARIABLE CODE (and vice versa), it is necessary to RESET the control panel!
- J4:
- Condominium function: The unit is provided with a deactivated master function. The master function is activated and deactivated using jumper J4.
- J4 CLOSED = CONDOMINIUM FUNCTION ACTIVATED
- J4 OPEN = CONDOMINIUM FUNCTION DEACTIVATED
To activate the master function, switch the unit on and then...
CONDOMINIUM FUNCTION: The opening mechanism starts with an impulse command when the gate is closed. Any other impulse command is ignored. Once completely opened, reclosure is commanded only by time. If not set, the gate remains open. A preset reclosing time of 30 seconds is considered. The photocell reloads the entire reclosing time when the gate is open. If the photocell remains interrupted, the gate does not restart. During reclosure, an impulse command stops the unit and makes the automation reopen completely.
- J5: Limit-switch or button use selection. (Described in Section 3).
7. Additional card for AV1 (not supplied as standard)
The AV1 version has a connector where it is possible to insert an additional card for outputs connecting the electric lock and the sensor light. The lighting time of the sensor light is fixed at 1 minute and 30 seconds; it lights each time the motor begins.
CONNECTOR TO INSTALL TO THE AV1 CENTRAL COMPUTER:
- TERMINALS 1 & 2: Output for sensor light. Timed for 90 SEC.
- TERMINALS 3 & 4: Output for electric lock. Timed for 3 SEC.
- CLEAN CONTACTS WITHOUT VOLTAGE. Max load 220 V - 5 A.
WARNING:
- Some points on the electrical control panel carry dangerously high voltage. Installation, opening, and programming must be carried out by qualified personnel only.
- Use equipment ensuring omnipolar disconnection of the system's power supply (e.g., a switch with a minimum contact distance of 3 mm per pole, or an integrated device).
- Control the absorption of all devices connected to the control panel's outputs (pilot lights, photoelectric cells, safety devices, etc.) to stay within the technical limits. Incorrect usage may lead to malfunctioning.
- To maximize the central unit's capacity, ensure the antenna is not directed towards walls or metallic screens. The antenna's screened cable terminals must be tightly closed.
- A tuned antenna is necessary for maximum system performance; otherwise, the range may be reduced.
- The manufacturer accepts no responsibility for damage caused by ignoring these warnings.
Technical details
Parameter | Value |
---|---|
Power voltage | 230 Vac +10%-15% 50Hz |
Power accessories | 24 Vac 1.5W MAX |
Motor output | 230Vac 500W MAX |
Working temperature | -10 +60 °C |
Working time | from 1 to 180 s |
Automatic reclosure time | from 4 to 120 s |
Receiver frequency | 433.92 MHz |
Available reception | Fixed code, Rolling Code |
Impedance of antenna | 50 W (* Device not for UE market) |
Number of codes | 4096 (receipt of fixed code), 18 billion billion (Rolling Code receipt) |
Capacity | 50-150 in unlimited space (for various reception types) |
8. Guarantee
The producer's guarantee is valid in compliance with the law, from the date stamped on the product. It is limited to repair work and free replacement of pieces recognized as faulty due to quality or material issues from bad workmanship. The guarantee does not cover damage caused by foreign elements, maintenance errors, overloading, natural wear, incorrect choice, assembly faults, or other causes not controllable by the manufacturer. Products tampered with are not covered. Information provided is indicative; no responsibility is accepted for capacity reduction or malfunctions caused by environmental interferences. Producer's liability for damage from accidents caused by faulty products is exclusively as stated in Italian law.
9. Disposal of the product
This product is an integral part of the automation and must be disposed of accordingly. Dismantling operations must be performed by qualified personnel. The product is made from various materials; some can be recycled, others must be disposed of. Please consult local laws for recycling or disposal systems.
CAUTION! Some parts may contain polluting or dangerous substances that can cause serious harm to the environment and human health if dispersed. As indicated by the symbol ♻️, it is forbidden to throw this product into domestic refuse. Follow "separated collection" instructions according to local regulations, or return the product to the retailer when purchasing a new, equivalent product.