Hochiki Conventional Detectors Technical Bulletin

Subject: Maintenance, Cleaning, and Testing Instructions

Introduction

These instructions apply to all detectors listed in this Technical Bulletin for maintaining, cleaning, and testing. Failure to follow these instructions may result in the failure of the detectors to initiate an alarm condition. Hochiki America Corporation is not responsible for detectors that have been improperly maintained, cleaned, or tested.

Detectors

Features of SOC and SOE series detectors

Multi-criteria Detectors use a supplementary photoelectric sensor to scale the photoelectric smoke sensor output to reduce sensitivity to false alarms and increase sensitivity to fire conditions.

Placement of Detectors

Following the guidelines in NFPA 72, base the number and location of detectors on an engineering survey of the area to be protected. Factors to consider include:

Detector Location Spacing Guidelines:

WARNING: Heat detectors are not life safety devices. Smoke detectors are recommended where life safety is a factor.

Examples:

*Beams or other obstructions extending more than 18" below the ceiling reduce the effective range of the detectors. Such obstruction should designate a new separation point and be considered a border for a new section.

*Beams or other obstructions extending more than 8" but less than 18" require reduced spacing at the perpendicular of the obstructions.

NOTE: For information on differing styles of construction consult the NFPA 72.

WARNING: Do not install Hochiki smoke detectors in the following areas:

Maintenance

Cleaning

Use clean, dry compressed air to remove dust from a detector, or return to Hochiki America for service. Disassembly of the detector may result in the failure of the detector to initiate an alarm condition or initiation of a false alarm condition.

Testing

For a smoke detector to operate efficiently, the combustion products must enter the outer chamber. Air flow, stratification, velocity, stagnation, and migration all affect the efficiency and accuracy of the detector. Use an air flow meter to determine the movement of the air within a structure. Field testing equipment is available from Hochiki America for testing the function of the detectors. Consult local codes and ordinances for maintenance requirements. Hochiki America Corporation recommends a bi-annual functional testing and visual inspection.

Prior to testing any detector, care should be exercised to ensure proper disabling of live signals and notification circuits of the Fire Alarm Control Panel. Failure to exercise this procedure may result in false alarm signals which could place life and property in jeopardy.

Caution: Excessive aerosol smoke can contaminate a detector.

Test with Smoke Sabre aerosol cans or the Testifier 1000/1001 or 2000/2001 with TS3 smoke capsules.

Testifier usage: To insert the battery baton, hold the Testifire head unit by the handle and depress the upper spring button on the battery baton. Align the button with the location hole in the handle and push the battery baton into the handle until the button snaps into place.

  1. Insert the other end of the battery baton into the Solo access pole and depress the lower spring button. Align it with the location hole and push the battery baton further into the pole until the button snaps into place.
  2. Remove the capsule from its outer carton and Anti-Static bag.
  3. Remove the spring clip protector cap from the new capsule.
  4. Holding the capsule by spring clips with the label on the underside, carefully insert the new capsule into the capsule port. Push it into position, ensuring that the clips spring out positively on both sides of the capsule.
  5. Close the access cover securely.
  6. Program the tester to the following options available: Smoke or Heat.
  7. Raise Testifire over the detector. The detector should touch the base of the inner clear cup.
  8. Lower Testifire from the sensor after testing is complete.

Testifire's LED Indications

LED Status Indication
Blue Solid Smoke test in progress
Red Solid Heat test in progress
Green Slow Flashing Standby mode
Green Fast Flashing Operational mode
Red Flashing Battery needs charging, but still operational
Alternating Red/Green Flashing Timeout indication (after 2 minutes of continuous testing)
Red Solid Error

Detector Specifications

SOC-24V Conventional Photoelectric Smoke Detector

Parameter Value
Sensing Element Smoke
Supply Voltage 8-35VDC
Operating Voltage Range 8-35VDC
Absolute Max Voltage 42VDC
Maximum Voltage Ripple Filtered DC, 15% Ripple (Max)
Maximum Input Capacitance 0.01uF
Standby Current 59μΑ
Minimum Allowable Alarm Current 6mA
Maximum Allowable Alarm Current 150mA
Startup Current 160μΑ (Max)
Smoke Density Range 1.36-3.12%/ft Open Area and 300 – 4000FPM in duct
Detector Compatibility ID HD3
Compatible Bases NS4-100, NS6-100, NS4-220, NS6-220, NS4-221, NS6-221, NS4-224, NS6-224, HSC-220R, HSC-221R, HSC-224R, HSC-4R, HSC-4R12
Operating Temperature Range 14°F ~ 122°F
UL Listed Ambient Temperature 32°F ~ 100°F
Storage Temperature Range -22°F ~ +140°F
Dimensions 3.94" diameter x 1.77" tall
Color (SOC-24V) Ivory, (SOC-24VW) White
Weight 3.0 oz.

SOE-24V Conventional Photoelectric Smoke Detector

Parameter Value
Sensing Element Smoke
Supply Voltage 8-35VDC
Operating Voltage Range 8-35VDC
Absolute Max Voltage 42VDC
Maximum Voltage Ripple 8200mVAC
Maximum Input Capacitance 0.01uF
Standby Current 59μΑ
Minimum Allowable Alarm Current 5mA
Maximum Allowable Alarm Current 150mA
Startup Current 160μΑ (Max)
Reset Time 100ms (Min)
Reset Voltage 2.5V (Max)
Smoke Density Range 1.82-3.16%/ft @ Open area
1.82-4.55%/ft @300FPM in Duct
1.82-3.96%/ft @1000FPM in Duct
1.82-4.19%/ft @2000FPM in Duct
1.82-4.07%/ft @3000FPM in Duct
1.82-4.20%/ft @4000FPM in Duct
Detector Compatibility ID HD3
Compatible Bases NS4-100, NS6-100, NS4-220, NS6-220, NS4-221, NS6-221, NS4-224, NS6-224, HSC-220R, HSC-221R, HSC-224R, HSC-4R, HSC-4R12
Operating Temperature Range 32°F ~ 120°F
UL Listed Ambient Temperature 32°F ~ 100°F
Storage Temperature Range -22°F ~ +140°F
Operating Humidity Limit <95%RH at 104°F, <80%RH at 120°F
Dimensions 3.94" diameter x 1.77" tall
Color SOE-24V – Ivory, SOE-24V (WHT) – White
Weight 3.4 oz.

SOE-24H Conventional Photoelectric Smoke and Heat Detector

Parameter Value
Sensing Element Heat, Smoke, Thermistor
Supply Voltage 8-35VDC
Operating Voltage Range 8-35VDC
Absolute Max Voltage 42VDC
Maximum Voltage Ripple 8200mVAC
Maximum Input Capacitance 0.01uF
Standby Current 59μΑ
Minimum Allowable Alarm Current 5mA
Maximum Allowable Alarm Current 150mA
Startup Current 160μΑ (Max)
Reset Time 100ms (Min)
Reset Voltage 2.5V (Max)
Smoke Density Range 1.80-3.16%/ft @ Open area
1.80-4.55%/ft @300FPM in Duct
1.80-3.96%/ft @1000FPM in Duct
1.80-4.19%/ft @2000FPM in Duct
1.80-4.07%/ft @3000FPM in Duct
1.80-4.20%/ft @4000FPM in Duct
Heat Sensitivity Range 135°F
Detector Compatibility ID HD3
Compatible Bases NS4-100, NS6-100, NS4-220, NS6-220, NS4-221, NS6-221, NS4-224, NS6-224, HSC-220R, HSC-221R, HSC-224R, HSC-4R, HSC-4R12
Operating Temperature Range 32°F ~ 117°F
UL Listed Ambient Temperature 32°F ~ 117°F
Storage Temperature Range -22°F ~ +140°F
Operating Humidity Limit <95%RH at 104°F, <80%RH at 120°F
Dimensions 3.94" diameter x 2.18" tall
Color SOE-24H – Ivory, SOE-24H (WHT) – White
Weight 3.4 oz.

DCD-135 Conventional Fixed Temperature and Rate of Rise Heat Detector

Parameter Value
Sensing Element Heat, Thermistor
Supply Voltage 15-33VDC
Operating Voltage Range 15-33VDC
Absolute Max Voltage 42VDC
Maximum Voltage Ripple Filtered DC, 5V (Max)
Standby Current 35μΑ
Minimum Allowable Alarm Current 6mA
Maximum Allowable Alarm Current 150mA
Startup Current 160μΑ (Max)
Heat Sensitivity Range 135°F or 15°F/min rise (whichever occurs first)
Detector Compatibility ID HD3
Compatible Bases NS4-100, NS6-100, NS4-220, NS6-220, NS4-221, NS6-221, NS4-224, NS6-224, HSC-220R, HSC-221R, HSC-224R, HSC-4R
Operating Temperature Range 14°F ~ 122°F
UL Listed Ambient Temperature 32°F ~ 100°F
Storage Temperature Range -4°F ~ +140°F
Dimensions 3.94" diameter x 1.5" tall
Color DCD-135 – Ivory, DCD-135W – White, DCD-135C – Ivory
Weight 3.4 oz.

DCD-190 Conventional Fixed Temperature and Rate of Rise Heat Detector

Parameter Value
Sensing Element Heat, Thermistor
Supply Voltage 15-33VDC
Operating Voltage Range 15-33VDC
Absolute Max Voltage 42VDC
Maximum Voltage Ripple Filtered DC, 5V (Max)
Standby Current 35μΑ
Minimum Allowable Alarm Current 6mA
Maximum Allowable Alarm Current 150mA
Startup Current 160μΑ (Max)
Heat Sensitivity Range 190°F or 15°F/min rise (whichever occurs first)
Detector Compatibility ID HD3
Compatible Bases NS4-100, NS6-100, NS4-220, NS6-220, NS4-221, NS6-221, NS4-224, NS6-224, HSC-220R, HSC-221R, HSC-224R, HSC-4R
Operating Temperature Range 14°F ~ 122°F
UL Listed Ambient Temperature 32°F ~ 100°F
Storage Temperature Range -4°F ~ +140°F
Dimensions 3.94" diameter x 1.5" tall
Color DCD-190 – Ivory, DCD-190W – White, DCD-190C – Ivory
Weight 3.4 oz.

DFE-135 Conventional Fixed Temperature Dry Contact Heat Detector

Parameter Value
Sensing Element Heat
Current Consumption Maximum Allowable Alarm Current: 100mA @ 60V
Heat Sensitivity Range 135°F
Detector Compatibility ID None
Compatible Bases NS6-100, HSC-220L, HSC-221L, HSC-224L
Operating Temperature Range 14°F ~ 120°F
Storage Temperature Range -4°F ~ +140°F
Dimensions 3.94" diameter x 1.5" tall
Color DFE-135 – Ivory, DFE-135W – White, DFE-135C – Ivory
Weight 3 oz.

DFE-190 Conventional Fixed Temperature Dry Contact Heat Detector

Parameter Value
Sensing Element Heat
Current Consumption Maximum Allowable Alarm Current: 100mA @ 60V
Heat Sensitivity Range 190°F
Detector Compatibility ID None
Compatible Bases NS6-100, HSC-220L, HSC-221L, HSC-224L
Operating Temperature Range 14°F ~ 160°F
Storage Temperature Range -4°F ~ +140°F
Dimensions 3.94" diameter x 1.5" tall
Color DFE-190 – Ivory, DFE-190W – White, DFE-190C – Ivory
Weight 3 oz.

DSC-EA Conventional Rate of Rise Dry Contact Heat Detector

Parameter Value
Sensing Element Heat
Current Consumption Maximum Allowable Alarm Current: 100mA @ 30V
Heat Sensitivity Range 15°F/minute
Detector Compatibility ID None
Compatible Bases HSB-100, HSC-220L, HSC-221L, HSC-224L, NS4-100, NS6-100, NS4-220, NS6-220, NS4-221, NS6-221, NS4-224, NS6-224, HSC-4R, HSC-4R12
Operating Temperature Range 14°F ~ 122°F
Storage Temperature Range -22°F ~ +158°F
Dimensions 3.94" diameter x 1.3" tall
Color DSC-EA – Ivory, DSC-EAW – White
Weight 3 oz.
Models: Conventional Detectors Technical Bulletin, Conventional Detectors, Technical Bulletin

File Info : application/pdf, 11 Pages, 899.53KB

PDF preview unavailable. Download the PDF instead.

HA-06-434 Conventional Detector Technical Bulletin (07-2021) Microsoft Word 2013 Microsoft Word 2013

Related Documents

Preview HOCHIKI HCVR-3 Conventional Releasing Fire Alarm Control Panel Datasheet
Detailed specifications and features of the HOCHIKI HCVR-3 Conventional Releasing Fire Alarm Control Panel, including product listings, compatible devices, and technical data. UL Listed and FM Approved.
Preview Hochiki SLR-24V Photoelectric Smoke Detector Technical Specifications
Detailed technical specifications, features, applications, operation, and wiring diagrams for the Hochiki SLR-24V photoelectric smoke detector. Includes product listings and company information.
Preview Hochiki DH-100-A Analog Addressable Smoke Detector Installation Instructions
Detailed installation instructions for the Hochiki DH-100-A analog addressable smoke detector, including location requirements, mounting, sampling tube assembly, electrical connections, and testing procedures.
Preview Hochiki ACE-V Analog Multi-Criteria Smoke/Heat Detector Specifications and Applications
Detailed information on the Hochiki ACE-V Analog Multi-Criteria Smoke/Heat Detector, covering its applications, operation, standard features, product listings, and technical specifications. Includes UL and FM certifications.
Preview HOCHIKI ACE-V Analog Multi-Criteria Detector - Technical Specifications and Features
Detailed information on the HOCHIKI ACE-V Analog Multi-Criteria Detector, including its applications, standard features, operation, technical specifications, and product listings. Designed for effective smoke and heat detection.
Preview Hochiki FOC-593 DRD-E Conventional Flame Detector Technical Overview
Technical specifications and features of the Hochiki FOC-593 DRD-E conventional flame detector, including its detection range, operating conditions, and compliance.
Preview Hochiki Product Guide ISS30:MAR24 - Fire Detection Systems & Solutions
Comprehensive product guide from Hochiki, detailing their advanced range of fire detection systems, including addressable, conventional, wireless, and air sampling technologies. Learn about Hochiki's commitment to fire safety innovation.
Preview Hochiki DRD-E Infrared Flame Detector Installation Guide
This installation manual provides comprehensive guidance for the Hochiki DRD-E Conventional Infrared Flame Detector, covering its general description, IR detection principles, application suitability, positioning guidelines, installation procedures, functional testing, and detailed specifications.