Hochiki ACE-V Analog Multi-Criteria Smoke/Heat Detector
APPLICATIONS
The Hochiki ACE-V Multi-Criteria Detector is designed to effectively detect smoke from a wide variety of combustibles in diverse environments. It includes a thermistor, strategically positioned for optimal sensitivity, to monitor temperature. Its advanced design ensures quick detection of both flaming and smoldering fires, while minimizing unwanted alarms.
OPERATION
The ACE-V Detector features a new chamber that enhances the smoke entry for early fire smoke detection. The detection chamber utilizes light from IR and Blue LED sources. In the event of fire, particles of smoke enter the chamber and scatter light in proportion to the smoke density, resulting in an increased analog smoke measurement. The chamber contains a unique baffle design which allows smoke to enter the chamber while preventing external light from affecting the photodiode detector.
The heat detection function uses a newly designed precise thermistor circuit with one externally mounted thermistor. The protective cover ensures the thermistor is safeguarded while allowing maximum airflow. The thermistor generates a voltage relative to the ambient temperature, which is then converted to a digital signal for transmission to the control panel. When the temperature exceeds a set threshold, the detector signals the control panel, triggering an alarm. The control panel can adjust the heat sensitivity to meet various applications.
Each SLC loop can support up to 127 devices and up to 127 sounder bases. Detector addresses are programmed using a handheld programmer. The detector is installed on a base for secure placement, providing terminal connections for field wiring and a third contact for a remote indicator/LED.
DETECTOR SPACING
Smoke detector placement should comply with NFPA 72 guidelines. On smooth ceilings, without specific performance-based criteria, smoke sensors should be spaced no more than 30 feet (9.1m) apart, or within a distance equal to or less than 0.7 times the nominal spacing. Sensors must also be positioned within a distance of one-half the nominal spacing, measured at right angles from all walls or partitions extending upward to within the top 15 percent of the ceiling height. For additional instructions see NFPA 72.
STANDARD FEATURES
- UL 268 7th edition listed
- UL 521 7th edition listed
- 11 UL Listed Modes
- New design featuring wide viewing angle alarm indicators for enhanced visibility and performance
- Advanced multi-criteria smoke detection
- Designed to resist unwanted alarms from cooking and other nuisance alarm sources
- Simple and reliable device addressing
- Automatic compensation for detector contamination
- Uses the noise-immune Digital Communication Protocol (DCP), which utilizes interrupts for fast response to fires
PRODUCT LISTINGS
UL Certified, FM Approved
TECHNICAL SPECIFICATIONS
Supply Voltage | Operating Voltage Range (High Signal): 24-41 VDC Signal Voltage (Peak to Peak)¹: 7-9 VDC |
Current Consumption | Normal Standby Current: 340μA Alarm Current (LED Off)²: 340μA Alarm Current (LED On)²: 8.5mA Remote Indicator Current³: 8.0mA Polling Current: 6.75mA |
Smoke Density Range | 40 - 3.30%/ft @ 0-300 FPM Open Area |
Heat Fixed Temperature Range | 135°F ~ 150°F (57.2°C ~ 65.5°C) |
Heat Rate of Rise | 20°F per minute (-6.7°C per minute) |
Compatible Bases | YBN-NSA-47, HSB-NSA-67, SCI-B47, SCI-B67, ASB7, ASBL7 |
Operating Temperature Range | 32°F ~ 117°F (0°C ~ 47.2°C) |
UL Listed Ambient Temperature | 32°F ~ 117°F (0°C ~ 47.2°C) |
Storage Temperature Range | -22°F ~ +140°F (-30°C ~ 60°C) (104°F(40°C) or less at 95%RH, 140°F(60°C) or less at 80%RH) |
Operating Humidity Limit | <95%RH at 104°F(40°C), <80%RH at 120°F(48.9°C) |
Dimension | 3.94" diameter x 2.15" tall (10cm x 5.46cm) |
Color | Ivory |
Weight | 3.4 oz. (96.38g) |
Notes:
- Measured during FACP transmission. 17V Minimum Voltage (Operating Voltage less Signal Voltage).
- When the total number of active alarm LEDs is limited by the FACP, additional detectors in Alarm will consume the Alarm Current (LED Off) current.
- RI is current limited by the detector not to exceed 9.6mA. Actual RI current is equal to the load current for loads less than 9.6mA.
- Polling Current should be added to sum-total Normal Standby Current for each SLC loop. Voltage drop calculations do not need to include Polling Current.