Notifier NRX-M711 Radio System Input / Output Module Installation Instructions

Description

The NRX-M711 radio input-output module is a battery-operated RF device designed for use with the NRXI-GATE radio gateway, running on an addressable fire system using a compatible proprietary communication protocol. It is a dual module with separate input and output capability, combined with a wireless RF transceiver, and is supplied with a wireless back box. This device conforms to EN54-18 and EN54-25 and complies with the requirements of 2014/53/EU for conformance with the RED directive.

Parts List

PartQuantity
Module unit1
SMB500 back box1
Front cover1
Batteries (Duracell Ultra 123 or Panasonic Industrial 123)4
Back box fixing screws and wall plugs2
Module fixing screws2
3-pin terminal block2
2-pin terminal block1
47 k-ohm EOL resistor2
18 k-ohm alarm resistor1
Module installation instructions1
SMB500 back box installation instructions1

Specifications

SpecificationValue
Supply Voltage3.3 V Direct Current max.
Standby Current122 µA@ 3V (typical in normal operating mode)
Red LED Current Max2 mA
Green LED Current Max5.5 mA
Re-Sync Time35s (max time to normal RF communication from device power on)
Batteries4 X Duracell Ultra123 or Panasonic Industrial 123
Battery Life4 years @ 25°C
Radio Frequency865-870 MHz. Channel width: 250kHz
RF Output Power14dBm (max)
Range500m (typ. in free air)
Relative Humidity5% to 95% (non-condensing)
Terminal Wire Size0.5 - 2.5 mm²
IP RatingIP20
Input Module End-of-Line Resistor47K
Input Module Supervision Current34 µA typical
Output Module End-of-Line Resistor47K
Output Module Supervision Current60 µA typical
Relay Contacts2 A @ 30 VDC (resistive load)
External Power Supply Unit Voltage30V DC max. 8V DC min.
External Power Supply Unit Supervision Fault Voltage7V DC typical

Module Dimensions

Figure 1 shows the module and back box dimensions: 58 mm width, 125 mm height, and 125 mm depth.

Terminal Connections

Table 1 details the terminal connections:

TerminalConnection / FunctionInput ModuleOutput Module (Supervised mode)Output Module (Relay mode)
1Input -ve
2Input +ve
3Connect to T8Relay NO (normally open)
4To load +veRelay C (common)
5Connect to T7Relay NC (normally closed)
6Supervision: connect to load -veNot used
7To ext PSU -veNot used
8To ext PSU +veNot used

The input module requires a 47K EOL resistor for normal operation. The output module requires a 47K EOL at the load for normal operation in supervised mode. If the load has low impedance (compared to the EOL), a series diode should be added for correct load supervision, as shown in Figure 2 (Diode Polarity).

Figure 2: Diode Polarity

Diagram illustrating diode polarity for load supervision: Load -VE connected to the anode, Load +VE connected to the cathode, with a diode in series.

Installation

This equipment and any associated work must be installed in accordance with all relevant codes and regulations. Figure 1 details the dimensions of the back box and cover. Spacing between radio system devices must be a minimum of 1m.

Switching Inductive Loads

WARNING: Switching Inductive Loads

See Figure 3. Inductive loads can cause switching surges, which may damage the module relay contacts (i). To protect the relay contacts, connect a suitable Transient Voltage Suppressor (iii) - for example 1N6284CA - across the load (ii) as shown in Figure 3. Alternatively, for unsupervised DC applications, fit a diode with a reverse breakdown voltage greater than 10 times the circuit voltage.

Figure 3 shows a diagram of switching inductive loads, illustrating the connection of a load (ii) with a transient voltage suppressor (iii) across it.

Battery Installation and Handling

Figure 4 details the battery installation and Figure 5 the location of the address switches.

Important: Batteries should only be installed at the time of commissioning.

Warning: Observe the battery manufacturer's precautions for use and requirements for disposal. Possible explosion risk if incorrect type is used. Do not mix batteries from different manufacturers. When changing batteries, all 4 must be replaced. Using these battery products for long periods at temperatures below -20°C can reduce battery life considerably (by up to 30% or more).

Figure 4 shows the rear of the module with the battery compartment and cover, highlighting the need to note polarity.

Module Fixing and Removal

Fixing the module: Remove the 2 screws from the front cover to reveal the RF module. Remove the RF module from the back box. Screw the back box to the desired position on the wall using the fixings provided. Refit the module in the box. Wire the plug-in terminals as required by the system design. Refit the front cover to protect the module.

Removing the module from the back box: Slacken off the 2 fixing screws, twist the module clockwise slightly and lift out. Reverse this process to refit the module.

Device Removal Warning: In a working system, an alert message will be sent to the CIE via the Gateway when the front cover is removed from the back box.

Setting the Address

Set the loop address by turning the two rotary decade switches on the front of the module using a screwdriver. Except when Advanced Protocol (AP) is being used, the dual I/O module will take two module addresses on the loop: the input module address will be the number shown on the switches (N), and the output module address will be incremented by one (N+1). For a panel with 99 addresses, select a number between 01 and 98. In Advanced Protocol (AP), addresses in the range 01-159 are available, depending on panel capability.

Important: Set the loop address on the module Before inserting the batteries.

Figure 5 shows the front of the module with the rotary address switches.

LED Indicators

The radio module has a tri-colour LED indicator that shows the status of the device (see Table 2):

Module StatusLED StateMeaning
Power-on initialisation (no fault)Long Green pulseDevice is un-commissioned (factory default)
3 Green blinksDevice is commissioned
FaultBlink Amber every 1s.Device has an internal trouble
Un-commissionedRed/Green double-blink every 14s (or just Green when communicating).Device is powered and is waiting to be programmed.
SyncGreen/Amber double-blink every 14s (or just Green when communicating).Device is powered, programmed and trying to find/join the RF network.
NormalControlled by panel; can be set to Red ON, Green ON, periodic blink Green or OFF.RF communications is established; device is working properly.
Idle (low power mode)Amber/Green double-blink every 14sCommissioned RF network is in standby; used when the gateway is powered off.

Programming and Commissioning

Configuring the Output Module Mode: The output module is supplied configured as a Supervised Output Module (factory default setting). To change the output to relay mode (Form C - volt-free changeover contacts) requires a separate programming operation using the Device Direct Command in AgileIQ (See Radio Programming and Commissioning Manual - ref. D200-306-00 for details).

Starting with an un-commissioned module:

  1. Remove it from the back box.
  2. Ensure that the address is set to 00 (default setting).
  3. Insert the batteries.
  4. Select the Device Direct Command tab in AgileIQ.
  5. Double click on the screen to reveal the list of options and follow the instructions to configure the output module mode.

Note: Remove the batteries from the device afterwards if the system commissioning operation is not about to be done.

It is recommended that the output module configuration is noted for future reference on the module label after commissioning: OUTPUT MODULE: Supervised ☐ Relay ☐

Commissioning:

  1. Remove the module from the back box.
  2. Ensure that the correct address has been set.
  3. Insert the batteries.
  4. Refit the module and replace the back box front cover.

To load network parameters into the RF module, it is necessary to link the RF gateway and the RF module in a configuration operation using the AgileIQ software tool. At commissioning time, with the RF network devices powered on, the RF gateway will connect and program them with network information as necessary. The RF module then synchronises with its other associated devices as the RF mesh network is created by the Gateway. (For further information, see the Radio Programming and Commissioning Manual - ref. D200-306-00.)

NOTE: Do not run more than one USB interface at a time to commission devices in an area.

Wiring Diagrams

Figure 6 shows the wiring for the Output Module (Supervised mode).

Figure 7 shows the wiring for the Input / Output Module (Relay mode).

EU Declaration of Conformity

Notifier by Honeywell declares that the radio equipment type NRX-M711 is in compliance with directive 2014/53/EU. The full text of the EU DoC can be requested from: HSFREDDoC@honeywell.com

Patents Pending

Information on patents pending.

Models: NRX-M711 Radio System Input-Output Module, NRX-M711, Radio System Input-Output Module, Input-Output Module, Output Module, Module

File Info : application/pdf, 15 Pages, 1.47MB

PDF preview unavailable. Download the PDF instead.

datas Adobe PDF Library 15.0 Adobe InDesign 14.0 (Windows)

Related Documents

Preview Notifier NFS-320 Intelligent Addressable Fire Alarm System Datasheet
Comprehensive datasheet for the Notifier NFS-320 Intelligent Addressable Fire Alarm System, detailing its features, intelligent sensing capabilities, FlashScan protocol, system specifications, compatible devices, and agency approvals.
Preview Notifier M710E-CZ Conventional Zone Interface Module Installation Guide
Comprehensive installation guide for the Notifier M710E-CZ Conventional Zone Interface Module, detailing specifications, wiring, mounting, and operational features for fire alarm systems.
Preview Notifier FCM-1 Supervised Control Module: Installation and Maintenance Instructions
Detailed installation and maintenance guide for the Notifier FCM-1 Supervised Control Module, covering specifications, wiring, and operational procedures for fire alarm systems.
Preview NOTIFIER LCD-80 Installation Manual: Features, Modes, and Setup
This installation manual provides detailed information on the NOTIFIER LCD-80 Liquid Crystal Display, covering its features, ACS and Terminal modes, system compatibility with various NOTIFIER fire alarm panels, and essential installation and configuration procedures.
Preview Notifier AFC-600 Intelligent Addressable Fire Alarm Control Panel with FlashScan® Datasheet
Comprehensive datasheet for the Notifier AFC-600 Intelligent Addressable Fire Alarm Control Panel, detailing its features, specifications, system capacity, programming options, compatible devices, and agency approvals. Includes information on FlashScan® protocol and AWACS™™ sensing technology.
Preview Notifier XP10-M(A) Ten-Input Monitor Module Technical Specifications
Detailed technical specifications and features for the Notifier XP10-M(A) Ten-Input Monitor Module, an addressable device for intelligent alarm systems.
Preview NOTIFIER NFS-3030 Intelligent Addressable Fire Alarm System | Technical Data Sheet
Explore the NOTIFIER NFS-3030, an intelligent addressable fire alarm control panel from the ONYX Series. Engineered for medium to large facilities, it offers advanced detection, modularity, and extensive device support for critical fire safety applications.
Preview Notifier AM-8000 Intelligent Addressable Fire Detection Installation Manual
This document provides comprehensive installation instructions for the Notifier AM-8000 Intelligent Addressable Fire Detection system. It covers system overview, technical specifications, electrical features, power supply, wiring diagrams, testing procedures, and periodic maintenance.