Honeywell F74C Reverse Rinsing Filter & MV876 Automatic-Backwash Controls

Installation Instructions

This is a legacy product document supported by Resideo. It is no longer manufactured.

Application

The F74C Reverse Rinsing Water Filters are used at the point-of-entry (POE) to remove sediment and debris from residential or commercial water systems, ensuring a continuous supply of filtered water. The fine filter prevents the ingress of foreign bodies, such as rust particles and grains of sand. The flow, filtering capacity, and ease of cleaning make the F74C an ideal filter for demanding applications. Both horizontal and vertical installations are possible.

The MV876 Automatic-Backwash Control is available as an accessory. This control fits onto the drain valve and is programmed by the user to automatically perform the backwash function according to a desired interval.

Specifications

IMPORTANT: The specifications provided do not include normal manufacturing tolerances. Units may not exactly match listed specifications. Products are tested and calibrated under closely controlled conditions, and minor performance differences may occur if conditions change.

F74C:

Models: Water filters with 100 micron screens and hose connections.

  • F74C1015: 3/4 in. sweat and NPT threaded tailpieces.
  • F74C1023: 1 in. sweat and NPT threaded tailpieces.

Materials of Construction:

  • Body: Engineered plastic.
  • Inlet/Outlet Adapter: Bronze.
  • Sump: Engineered plastic.
  • Screen: Stainless steel.
  • Internal Construction: Acetal copolymer.
  • Seals: NBR.
  • Ball Valve: Brass with PTFE seals.

Inlet Pressure:

  • Minimum: 22 psi (with unrestricted backwash discharge).
  • Maximum: 232 psi.

Medium:

Water.

Maximum Operating Temperature:

86°F (30°C).

Pipe Size:

3/4 in. and 1 in.

Mounting Position:

For vertical or horizontal installation (filter bowl always downwards).

Dimensions:

See Fig. 1 and Table 1.

Fig. 1. Dimension drawing of F74C.

Diagram showing the dimensions of the F74C filter, with labels for height (H, h), length (L), inlet/outlet connections (l, D, r), and sump height (t, T).
Table 1. Dimensions of F74C in in. (mm).
DimensionConnection Size
3/41
H12-13/16 (324)12-13/16 (324)
h11-3/16 (285)11-3/16 (285)
L6-3/8 (162)7-1/4 (184)
l3-9/16 (90)3-15/16 (100)
D4-1/8 (105)4-1/8 (105)
r1-1/16 (27)1-1/16 (27)
t2-5/8 (66)2-5/8 (66)
T5-5/16 (150)5-5/16 (150)

Weight: 3/4 in.: 6 lb (2.7 kg). 1 in.: 7 lb (3.2 kg).

Operating Pressure Drop Versus Flow: See Fig. 2. Maximum recommended: 3 psi to 7 psi (with clean screen).

Fig. 2. F74C Pressure drop vs. flow.

Graph illustrating the relationship between pressure drop (in psi) and flow rate (in GPM) for the F74C filter, showing data for F74C1015 and F74C1023 models, with a line indicating maximum recommended pressure drop.

Connections: Union on inlet and outlet: External NPT threaded or sweat. Inlet/outlet assembly can be rotated to fit on vertical or horizontal piping.

Screen Sizes: Shipped with Device: 100 microns.

MV876 Automatic-Backwash Control:

MV876B1018: Bayonet mounted shaft of 24 Vac motor and timer replaces ball valve manual control for automatic backwash at preprogrammed intervals. 24V transformer not included. For use with F74C and F76S Filters only.

Specifications:

  • Power: 4 VA.
  • Current: 170 mA.
  • Voltage: 24 Vac.
  • Cycle time: 20 seconds (approximate).
  • Timer: Variable. See Table 3.
Table 2. Flow Capacity of F74C in Gallons per Minute (gpm).
ModelSizePressure Drop in psiCv
1234515
F74C10153/49.012.715.618.020.134.99
F74C1023110.114.317.520.222.639.110.1
Table 3. MV876B Timer Selections.
Program ValueBackwash Interval
14 minutes
28 minutes
316 minutes
432 minutes
51 hour
62 hours
74 hours
88 hours
917 hours
1034 hours
113 days
126 days
1311 days
1423 days
1545 days
163 months

Planning the Installation

The F74C should be sized based on the required flow rate and the resulting pressure drop across the filter. As a guideline for most applications, the F74C should be sized for a pressure drop between 3 psi and 7 psi.

EXAMPLE: What size F74C is required to provide a flow rate of 20 gpm? Reading Table 2 at 20 gpm, a 3/4 in. model has 5 psi drop and a 1 in. model has 4 psi drop. As both models meet the 3 to 7 psi range, the selection should be based on size preference.

An increased pressure drop across the filter results when higher velocities are maintained to increase the capacity through any given size filter. Severe pressure drops will be encountered as capacity approaches that of the pipe size. To ensure the backwash cycle operates properly and cleaning action is not reduced, follow all recommendations in Fig. 3. Refer to Fig. 3a for an ideal installation.

All filter installations are different. The size, type, and amount of dirt and debris, and the flow rate must always be considered when choosing a screen and deciding to install multiple F74C Water Filters in parallel.

Fig. 3. Ideal F74C installation.

An illustration showing an ideal F74C installation, featuring a funnel positioned directly under the backwash port for optimal layout.

Fig. 4. Make sure the inlet pipe is not downsized.

Diagram emphasizing the importance of not downsizing the inlet pipe connected to the F74C filter.

Fig. 5. Make sure the backwash outlet pipe is not downsized, long or crimped.

Illustration showing the backwash outlet pipe. It advises against downsizing, making it too long, or crimping it, recommending a short, oversized pipe instead. It also cautions against using a low-capacity solenoid valve for automatic backwash.

Fig. 6. Make sure the backwash outlet is not raised above the F74C.

Diagram illustrating the backwash outlet. It states the outlet should not be raised above the F74C. If it must be raised, it advises increasing inlet pressure by 5 psi for every 10 feet of elevation.

Fig. 7. Make sure the F74C is not used with an undersized pump.

Illustration warning against using the F74C with an undersized pump, as this may result in insufficient pressure or flow.

Fig. 8. Make sure the F74C is not installed in a bypass across a pump.

Diagram showing an incorrect installation where the F74C is installed in a bypass across a pump.

Installation

When Installing this product...

Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

Check ratings given in these instructions and on the product to make sure the product is suitable for your application.

Make sure the installer is a trained, experienced service technician.

Use these instructions to check out product operation after installation.

CAUTION: Equipment Damage Hazard.

Excessive pressure or temperature can damage the device. Make sure water temperature and pressure are below maximum ratings specified.

CAUTION: Equipment Damage Hazard.

Excessive heat can damage internal parts. Before sweat soldering, separate the tailpieces and nuts from the inlet/outlet adapter.

F74C Installation:

When installing an F74C, use the following procedure:

  1. Shut off water supply by closing the water supply valve.
  2. Install inlet/outlet adapter so that filter is vertical.
  3. Install the F74C in the water line with the arrow pointing in the direction of water flow.

IMPORTANT: When using an MV876, stop here and install the MV876.

  1. Open a downstream tap.
  2. Slowly open the water supply valve.
  3. Once the F74C sump fills with water, close the downstream tap and fully open the water supply valve.

MV876 Installation:

  1. Open the backwash outlet ball valve. Remove the backwash outlet handle.
  2. Install the MV876. See Fig. 9 and 10.
  3. When rotating the MV876 on installation, it closes the backwash outlet ball valve.
  4. Connect the MV876 to a 24 Vac power supply. See Fig. 14.
  5. Open a downstream tap.
  6. Slowly open the water supply valve.
  7. Once the F74C sump fills with water, close the downstream tap and fully open the water supply valve.
  8. Program the desired backwash interval by pushing the program button until the desired interval number appears in the display.

Fig. 9. Installing the MV876.

Step-by-step visual guide for installing the MV876 automatic-backwash control onto the F74C filter, showing screw removal and cover detachment.

Fig. 10. Final position of MV876 and F74C.

Image depicting the final assembled position of the MV876 Automatic-Backwash Control attached to the F74C Reverse Rinsing Filter.

Fitting Batteries and Fuses

The batteries (not included) provide power to the MV876 in the event of a power loss. This is desirable, especially when power loss occurs during the reverse rinsing cycle. To provide this, the MV876 requires four AA alkaline batteries. Install these batteries in the cover of the MV876 as follows:

WARNING: Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before installing the batteries or fuses.

Fig. 11. Removing the MV876 cover.

Visual guide for removing the MV876 cover, showing the location of the four housing screws.

Fig. 12. Installing batteries in the MV876.

Illustration demonstrating the installation of four AA alkaline batteries into the MV876 unit.

IMPORTANT: Make sure the connecting cable is protected from damage when the MV876 cover is removed.

  1. Remove the MV876 cover. See Fig. 11.
  2. Insert four AA alkaline batteries. See Fig. 12.
  3. Replace the cover.
  4. Replace and tighten the four housing screws.
  5. To avoid unnecessary battery drainage, connect the MV876 to power as soon as possible after inserting new batteries.
  6. To ensure the availability of battery power, replace the batteries after a power loss.

If the 800 mA fuse blows, replace it as follows:

WARNING: Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before installing the batteries or fuses.

  1. Unscrew the four housing screws and set them aside (see Fig. 11).
  2. Remove the MV876 cover.
  3. Remove and discard the old fuse (see Fig. 13).
  4. Insert a new 800 mA fuse.
  5. Replace the cover.
  6. Replace and tighten the four housing screws.
  7. Reconnect the power supply.

Fig. 13. Replacing the MV876 fuse.

Diagram showing the process of replacing the MV876 fuse, including locating and removing the old fuse and inserting a new one.

Wiring

WARNING: Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before wiring.

IMPORTANT: All wiring must comply with applicable codes and ordinances.

  1. Mount the 24 Vac transformer and wire as shown in Fig. 14.
  2. Reconnect power to the system. When the system is powered, the MV876 will run through one backwash cycle (approximately 20 seconds).
  3. Set MV876 backwash interval to the desired setting. See the Operation section.
  4. Check MV876 operation by interrupting primary power to the transformer. When power is switched back on, the MV876 will backwash the F74C once.

Fig. 14. Wiring diagram for F74C with MV876.

Wiring diagram for connecting the MV876 to the F74C, showing the 24 Vac transformer connection to the power supply.

Parts and Accessories

As the F74C operates, screens become plugged. Backwash the F74C when the pressure gauge measures about five psi lower than when first installed. However, each installation is different. Residential applications can require backwash only once a week, or once every few weeks.

For residential applications, backwashing the F74C once a week, regardless of need, is an excellent guideline to follow to ensure F74C peak operating efficiency.

Table 4. Parts and Accessories for F74C.
Part NumberLetter in Fig. 15DescriptionContents
U76S5051A3/4 in. sweat tailpieceTailpiece
U76S5023A1 in. sweat tailpieceTailpiece
U76T1014B3/4 in. NPT tailpieceTailpiece
U76T1022B1 in. NPT tailpieceTailpiece
901444CUnion gasket, 3/4 in.10 gaskets in package
901445CUnion gasket, 1 in.10 gaskets in package
AF74-1ADReplacement filter assembly for F74C, 3/4 in. and 1 in., 100 micron.Includes the filter insert complete (O-ring, mesh with mesh support, impeller), sump O-ring (mounted between the filter housing and the sump).
KF74-1AEReplacement sump assembly for F74CIncludes the sump assembly complete (ball valve, plastic air gap adaptor), sump O-ring (mounted between the filter housing and the sump).

Fig. 15. F74C Exploded View.

Exploded view of the F74C filter, with parts labeled (A through E) corresponding to the replacement parts list.

Company Information

Home and Building Control

Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422

Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9

Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.

www.honeywell.com

Models: F74C Reverse Rinsing Filter MC876 Automatic Backwash Controls

File Info : application/pdf, 8 Pages, 668.00KB

PDF preview unavailable. Download the PDF instead.

62-0165 Acrobat Distiller 8.1.0 (Windows)

Related Documents

Preview Honeywell F76S Water Filters & MV876B Automatic-Backwash Controls: Product Data and Installation Guide
Comprehensive product data, specifications, installation, and operation guide for Honeywell's F76S Water Filters and MV876B Automatic-Backwash Controls. Learn about features, maintenance, and replacement parts for these water filtration systems.
Preview Honeywell MiniPlus FF06 / FF06-AAM Fine Water Filter Installation Manual
Installation, maintenance, and troubleshooting guide for the Honeywell MiniPlus FF06 and FF06-AAM fine water filters, ensuring clean drinking water.
Preview Honeywell FK06 DialSet® Low Lead Pressure Regulating Filter Combination Installation and Maintenance Guide
This document provides comprehensive installation, operation, maintenance, and troubleshooting instructions for the Honeywell FK06 DialSet® Low Lead Pressure Regulating Filter Combination. It details safety guidelines, technical specifications, scope of delivery, assembly, commissioning, cleaning, disposal, and spare parts.
Preview Honeywell FK06 DialSet® Low Lead Pressure Regulating Filter Combination: Installation and Maintenance Guide
Comprehensive guide for the Honeywell FK06 DialSet® low lead pressure regulating filter combination, covering installation, operation, maintenance, troubleshooting, and technical specifications.
Preview Honeywell FK06 DialSet® Pressure Reducing Valve and Filter: Installation, Maintenance, and Troubleshooting Guide
This guide provides comprehensive instructions for the Honeywell FK06 DialSet® pressure reducing valve and filter, covering installation, operation, maintenance, cleaning, troubleshooting, spare parts, and accessories.
Preview Honeywell CM927 Wireless Programmable Room Thermostat User Guide | Efficient Heating Control
Discover how to install, program, and operate the Honeywell CM927 wireless programmable room thermostat for optimal home comfort and energy savings. This user guide covers features, setup, and troubleshooting.
Preview Honeywell RTH6350/RTH6450 Series Programmable Thermostat Quick Installation Guide
A concise guide to installing the Honeywell RTH6350/RTH6450 Series Programmable Thermostat. This legacy product guide details easy setup steps and provides customer support information for optimal home climate control.
Preview Honeywell CM707 Programmable Thermostat: Specifications & Installation Guide
Detailed product specifications, features, and installation guide for the Honeywell CM707 programmable thermostat. Learn about its setup, functions, and technical details for home heating control. Legacy product.