R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA103-C32-500-4

Article No.: 293903

Product Overview

The R. STAHL 8530/1-MCB-STA103-C32-500-4 is an LS Miniature Circuit Breaker designed for robust performance and safety. It offers good short-circuit current limitation and high switching capacity of 10, 15, or 25 kA, ensuring minimal load on lines and high selectivity with upstream fuses. The modular design allows for 1- to 4-pole configurations and nominal currents from 0.5–63 A, with a maximum installation capacity of 4.5 module widths (TE).

Technical Data

Explosion Protection

ParameterValue
Einsatzbereich (Zonen)1, 2
Einsatzbereich (Zonen) HinweisUsable in Zone 21 / 22 when protected by enclosure Ex tb / tc
IECEx Bescheinigung GasIECEx FMG 19.0029U
IECEx GasexplosionsschutzEx db eb IIC Gb
ATEX Bescheinigung GasFM19ATEX0191U
ATEX GasexplosionsschutzII 2 G Ex db eb IIC Gb
BescheinigungenATEX (FM), Brazil (ULB), IECEx (FM), People's Republic of China (CQST)
KonformitätserklärungenConformity Certificate (ATEX)

Electrical Data

ParameterValue
Bemessungsbetriebsspannung AC (Rated Operating Voltage AC)230/400 V
Bemessungsbetriebsstrom (Rated Operating Current)32 A
Frequenz (Frequency)50/60 Hz
Bemessungsschaltvermögen (Rated Switching Capacity)10 kA
Elektrische Lebensdauer (Electrical Service Life)104
Mechanische Lebensdauer (Mechanical Service Life)2 x 104
Hilfsfunktion (Auxiliary Function)1 changeover auxiliary contact + 1 changeover fault signaling contact
Bemessungsspannung 1. Hilfsfunktion AC (Rated Voltage 1st Auxiliary Function AC)230 V
Max. Bemessungsstrom 1. Hilfsfunktion (Max. Rated Current 1st Auxiliary Function)2 A
2. Hilfsfunktion (2nd Auxiliary Function)none
Max. Spannung 2. Hilfsfunktion DC (Max. Voltage 2nd Auxiliary Function DC)-
Auslösecharakteristik (Trip Characteristic)C
Polzahl (Number of Poles)3-pole

Umgebungsbedingungen (Environmental Conditions)

ParameterValue
Umgebungstemperatur (Ambient Temperature)-40 °C ... 70 °C
Umgebungstemperatur (Ambient Temperature)-40 °F ... 158 °F
Umgebungstemperatur Hinweis (Ambient Temperature Note)Deviating ambient temperatures based on current certificates are available upon request.

Mechanische Daten (Mechanical Data)

ParameterValue
Schutzart (IP) (IEC 60529)IP2X
Gehäusematerial (Housing Material)Thermoplast
Anschlussquerschnitt min. (Connection Cross-section min.)1.5 mm²
Anschlussquerschnitt max. (Connection Cross-section max.)25 mm²
Anschlussquerschnitt AWG min.16 AWG
Anschlussquerschnitt AWG max.4 AWG
Anschlussquerschnitt 2 min.1.5 mm²
Anschlussquerschnitt 2 max.10 mm²
Anschlussquerschnitt 2 AWG min.16 AWG
Anschlussquerschnitt 2 AWG max.8 AWG
Anschlussquerschnitt HIKO min.0.5 mm²
Anschlussquerschnitt HIKO max.4 mm²
Anschlussquerschnitt HIKO AWG min.18 AWG
Anschlussquerschnitt HIKO AWG max.14 AWG
Anzugsdrehmoment min. (Tightening Torque min.)2 N·m
Anzugsdrehmoment max. (Tightening Torque max.)3 N·m
Anschlussquerschnitt Hinweis (Connection Cross-section Note)2-conductor connection (upper and lower chamber simultaneously): Max. 16 / 10 mm² for upper and lower chamber (A cross-section difference between the upper and lower chamber may be clamped). Permitted combinations of connection cross-sections can be found in the operating manual.
Breite (Width)110 mm
Breite Zoll (Width inch)4.33 in
Länge (Length)165 mm
Länge Zoll (Length inch)6.5 in
Einbautiefe (Mounting Depth)138.3 mm
Einbautiefe Zoll (Mounting Depth inch)5.44 in
Gewicht (Weight)1.8 kg
Gewicht (Weight lb)3.969 lb

Montage / Installation (Mounting / Installation)

ParameterValue
Anzugsdrehmoment (Tightening Torque)2-3 N·m
Anzugsdrehmoment lbf in (Tightening Torque lbf in)17.7 ... 26.6 lbf-in
Anzugsdrehmoment Hilfskontakt (Tightening Torque Auxiliary Contact)0.4-0.6 Nm
Anzugsdrehmoment Hilfskontakt lbf in (Tightening Torque Auxiliary Contact lbf in)3.5 ... 5.3 lbf in

Technical Drawings and Diagrams

Trip Characteristic C Curve

The diagram shows the tripping time in seconds against multiples of the rated current (I/In) for the C characteristic. It indicates the tripping behavior for AC and DC circuits, with a limit curve from a cold state.

Dimensional Drawings

Detailed dimensions are provided in millimeters [inches] for the overall unit, including width, length, and mounting depth. The unit is described as 8530/1, occupying 4 division units.

Accessories

Lock-out Device (4-way)

A lock-out / tag-out shackle for individually securing the component, allowing the use of up to 4 cylinder locks.

Mounting Set

A mounting set for attaching the component to the mounting plate without a top-hat rail.

Cylinder Lock

For locking (shackle Ø 3)

Note: Technical data, dimensions, weights, designs, and availability are subject to change without notice. Illustrations are non-binding.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-c32-500-4-293903-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-C32-000-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C32-000-3 Miniature Circuit Breaker, including electrical data, explosion protection, mechanical data, and accessories. Suitable for use in Ex zones.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C25-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C25-500-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA103-C16-500-4 - Technical Data and Features
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA103-C16-500-4. Includes information on explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-B16-500-4 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B16-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C63-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103-C6-000-3 LS Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C6-000-3 LS Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.