Fujitsu ASYG14LECA Room Air Conditioner Service Manual

SPLIT TYPE, ROOM AIR CONDITIONER, WALL MOUNTED TYPE

Indoor Unit: ASYG14LECA

Outdoor Unit: AOYG14LEC

CONTENTS

SPECIFICATIONS

ELECTRICAL DATA

Cool & heat inverter
TYPECool & heat inverter
INDOOR UNITASYG14LECA
OUTDOOR UNITAOYG14LEC
COOLING CAPACITY4.00 kW
HEATING CAPACITY5.00 kW
POWER SOURCE230 V
FREQUENCY50 Hz
RUNNING CURRENTCooling: 5.3 A
Heating: 6.0 A
INPUT WATTSCooling: 1.105 kW
Heating: 1.305 kW
E.E.R.Cooling: 3.62 kW/kW
COPHeating: 3.83 kW/kW
MOISTURE REMOVAL2.1 L/h
AIR CIRCULATION HIGHCooling: 770 m³/h
Heating: 770 m³/h
MAXIMUM CURRENTCooling: 9.0 A
Heating: 10.5 A

FAN MOTOR

High speedMedium speedLow speedQuiet
INDOOR UNIT Cooling1,400 r.p.m.1,230 r.p.m.1,000 r.p.m.750 r.p.m.
INDOOR UNIT Heating1,400 r.p.m.1,230 r.p.m.1,050 r.p.m.770 r.p.m.
OUTDOOR UNIT Cooling800 r.p.m.
OUTDOOR UNIT Heating750 r.p.m.

NOISE LEVEL

High speedMedium speedLow speedQuiet
INDOOR UNIT Cooling44 dB40 dB33 dB25 dB
INDOOR UNIT Heating44 dB40 dB35 dB27 dB
OUTDOOR UNIT Cooling49 dB
OUTDOOR UNIT Heating50 dB

COMPRESSOR AND REFRIGERANT

COMPRESSOR TYPEHermetic type, 4 pole, 3 phase, DC inverter motor, Rotary
DISCRIMINATIONDA89X1C-20FZ2
WEIGHT (with oil)9.2 kg
PRECHARGED REFRIGERANT1,050 g
REFRIGERANT TYPER410A
Pipe length15 m
FULL CHARGE20 m: 1,050 g
20 m: 1,150 g
ADDITIONAL REFRIGERANT20 g/m
MAXIMUM PIPING HEIGHT15m

DIMENSIONS

INDOOR UNIT H x W x D280 x 790 x 203 mm
OUTDOOR UNIT H x W x D540 x 790 x 290 mm

WEIGHT

INDOOR UNIT Shipping / Net10.5 kg / 8 kg
OUTDOOR UNIT Shipping / Net38 kg / 34 kg

DIMENSIONS

unit: mm

INDOOR UNIT

Diagram showing the dimensions of the indoor unit:

OUTDOOR UNIT

Diagram showing the dimensions of the outdoor unit:

REFRIGERANT SYSTEM DIAGRAM

Diagram illustrating the refrigerant flow:

CIRCUIT DIAGRAM

INDOOR UNIT CIRCUIT DIAGRAM

OUTDOOR UNIT CIRCUIT DIAGRAM

INDOOR PCB CIRCUIT DIAGRAM

Diagram of the Indoor Unit Control Unit (EZ-0101YHSE) and associated components:

OUTDOOR PCB CIRCUIT DIAGRAM

Diagram of the Outdoor Unit Inverter Assembly (EZ-0100MHUE):

ERROR DETECTION

INDOOR UNIT REMOTE CONTROL

Error codes are indicated by blinking patterns on the photo detector unit's lamp (wireless remote) or displayed on the remote control display (wired remote).

Error Display During Operation:

Error Code Table:

Indoor unit lamp (green)Indoor unit lamp (orange)Indoor unit lamp (green)Wired remote control lamp (green)Description
(1)(1)11Serial communication error
(1)(2)12Wired remote control communication error
(1)(5)15Check run unfinished
(2)(2)22Indoor unit capacity error
(2)(3)23Combination error
(3)(2)32Indoor unit PCB model information error
(3)(5)35Manual auto switch error
(4)(1)41Room temp. sensor error
(4)(2)42Indoor unit Heat Ex. Middle temp. sensor error
(5)(1)51Indoor unit fan motor error
(5)(3)53Drain pump error
(5)(7)57Damper error
(5)(15)SUIndoor unit error
(6)(2)62Outdoor unit main PCB model information error or communication error
(6)(3)63Inverter error
(6)(4)64Active filter error, PFC circuit error
(6)(5)65Trip terminal L error
(6)(10)6ADisplay PCB microcomputers communication error
(7)(1)71Discharge temp. sensor error
(7)(2)72Compressor temp. sensor error
(7)(3)73Outdoor unit Heat Ex. liquid temp. sensor error
(7)(4)74Outdoor temp. sensor error
(7)(5)75Suction Gas temp. sensor error
(7)(6)762-way valve temp. sensor error, 3-way valve temp. sensor error
(7)(7)77Heat sink temp. sensor error
(8)(2)82Sub-cool Heat Ex. gas inlet temp. sensor error
(8)(3)83Sub-cool Heat Ex. gas outlet temp. sensor error
(8)(4)84Current sensor error
(8)(6)86Discharge pressure sensor error, Suction pressure sensor error, High pressure switch error
(9)(4)94Trip detection
(9)(5)95Compressor rotor position detection error (permanent stop)
(9)(7)97Outdoor unit fan motor error
(9)(9)994-way valve error
(10)(1)A1Discharge temp. error
(10)(3)A3Compressor temp. error
(10)(4)A4High pressure error
(10)(5)A5Low pressure error

OUTDOOR UNIT

LEDERROR
onDischarge temperature abnormal
0.5 second on / 0.5 second offIPM overcurrent protection
0.1 second on / 0.1 second offThermistor abnormal
2.0 second on / 2.0 second offCT abnormal
0.1 second on / 2.0 second offCompressor location abnormal
5.0 second on / 5.0 second offFan abnormal

PARTS (INDOOR UNIT)

Diagrams and parts lists for the indoor unit components:

PARTS (OUTDOOR UNIT)

Diagrams and parts lists for the outdoor unit components:

ACCESSORIES

OPTION

PDF preview unavailable. Download the PDF instead.

Fujitsu-ASYG14LECA-Service-Manual My Name

Related Documents

Preview Fujitsu ASYA12LCC AOYR12LCC Split Type Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type, wall-mounted room air conditioners, models ASYA12LCC and AOYR12LCC. Includes specifications, diagrams, error codes, disassembly instructions, parts lists, and accessories.
Preview Fujitsu ASYA18LEC / AOYR18LEC Split Type Room Air Conditioner Service Manual
This service manual provides detailed specifications, diagrams, error codes, and parts lists for the Fujitsu ASYA18LEC indoor unit and AOYR18LEC outdoor unit, split-type room air conditioners.
Preview Fujitsu ASYG07LMCE/ASYG09LMCE Wall Mounted Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type wall-mounted air conditioners, models ASYG07LMCE and ASYG09LMCE. Includes specifications, dimensions, refrigerant system diagram, circuit diagrams, error detection codes, and detailed parts lists for both indoor and outdoor units.
Preview Fujitsu Split Type Room Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type room air conditioners, covering models ASYA14LCC, AOYR14LCC, ASYA14LCL, ASYA18LCC, AOYR18LCC, and AOYR18LCL. Includes specifications, diagrams, error codes, and parts lists.
Preview Fujitsu ASYG14LMCA / AOYG14LMCA Split Type Room Air Conditioner Service Manual
Comprehensive service manual for the Fujitsu ASYG14LMCA and AOYG14LMCA split type wall-mounted room air conditioners, covering specifications, diagrams, error detection, and parts.
Preview Fujitsu Split Type Room Air Conditioner Service Manual - ABY45RBA3W, AOY45RPA3L
Comprehensive service manual for Fujitsu Split Type Room Air Conditioner, Ceiling type (50Hz), models ABY45RBA3W and AOY45RPA3L. Covers specifications, diagrams, error codes, disassembly procedures, parts lists, and standard accessories.
Preview Fujitsu Split Type Room Air Conditioner Wall Mounted Type Service Manual
This service manual provides detailed specifications, diagrams, error contents, parts lists, and accessories for Fujitsu Split Type Room Air Conditioners, Wall Mounted Type, including models ASYA07LGC, ASYA09LGC, ASYA12LGC, AOYR07LGC, AOYR09LGC, and AOYR12LGC.
Preview Fujitsu Split Type Room Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type wall-mounted room air conditioners, models ASYG07LMCA, ASYG09LMCA, and ASYG12LMCA. Includes specifications, dimensions, circuit diagrams, error detection, and parts lists for both indoor and outdoor units.